Plan Review Notes
Plan Review Notes For Permit 08110469
Permit Number 08110469
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-09 10:55:15DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 EXISTING BUILDING
 CITY WPB MUNICIPAL CODE
 FBC-2004 CHAPTER 1
  
 1. INDICATE ON THE PLANS THE CRITERIA FOR THE DESIGN OF
 THE PLANS. PLANS SHALL BE DESIGNED PER FBC-2004 WITH
 2005, 2006 & 2007 REVISIONS. SECTION 106.1.1.
  
 2. INDICATE THE LEVEL OF ALTERATION AS REQUIRED IN
 CHAPTER 3 OF THE EXISTING BUILDING CODE. SECTION
 106.1.1.
  
 3. APPLICATION INDICATES NO CHANGE OF OCCUPANCY. THE
 EXISTING SPACE WAS A MERCANTILE SPACE PREVIOUSLY AND IS
 NOW AN ASSEMBLY OCCUPANCY. PLEASE INDICATE ON THE
 APPLICATION AND SHOW THE OCCUPANCY ON THE PLANS.
 SECTION 106.1.2 AND TABLES 1004.1.2 & 403.1.
  
 4. PER SECTION 1210.2 THE WALLS WITHIN 2 FEET OF A
 WATER CLOSET OR URINAL SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE TO A HEIGHT OF 4 FEET ABOVE THE
 FLOOR. PLEASE SUBMIT A DETAIL OR A FINISH SCHEDULE TO
 SHOW COMPLIANCE.
  
 5. THE VALUE OF THE WORK IS INDICATED AS $2100.00,
 (SINCE UPPED TO $6700.00 BY L. MARTINEZ). IF IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. SECTION 108.3. - WITH THE FOLLOWING WORK
 INDICATED ON THE PLANS, I BELIEVE THE VALUATION IS
 UNDERESTIMATED.
 DEMO:
 REMOVE CEILING, NON-BEARING WALL, WALL OPENING BETWEEN
 EXISTING RESTAURANT & NEW SPACE ADDED, & DOOR.
 NEW WORK:
 CLOSE DOORWAY, FINISH OPENING BETWEEN EXISTING
 RESTAURANT & NEW SPACE, NEW TILE IN TOILET ROOMS, NEW
 TILE FLOOR AT ENTRANCE, NEW WOOD FLOOR, ENGINEERING OF
 OPENING TO NEW RESTAURANT.
 NEW WORK PLUMBING:
 REMOVE EXISTING TOILET FIXTURES AND REPLACE WITH
 NEW,(2-W/C'S & 2 LAVS). NEW SINKS AT BAR AREA, (1 HAND
 SINK, & 1 TRIPLE COMP. SINK, (INDICATED ON RISER
 DIAGRAM), OR 2 COMP. SINK, (INDICATED ON FLOOR PLAN),
 PLEASE CORRELATE. ONE ICE BIN WITH FLOOR SINK OR HUB
 DRAIN.
 NEW WORK ELECTRICAL:
 NEW TRAC LIGHTING, (7 TRACKS & 7 HANGING LIGHTS WITH
 ALL WIRING).
  
 6. THE EXISTING GREASE INTERCEPTOR WILL HAVE TO BE
 INSPECTED AND APPROVED FOR THE EXTRA LOAD INDICATED ON
 THE PLANS, (36 TABLE AND 6 BAR). PLEASE CONTACT HOLLY
 MCGRATH, LABORATORY SUPERVISOR, PUBLIC UTILITIES
 DEPARTMENT AT (561) 822-2200 EXT 2271, BY FAX (561)
 822-2279 OR BY E-MAIL [email protected]. A WRITTEN
 DERTIMINATION IS REQUIRED TO BE SUBMITTED FOR PERMIT
 APPROVAL.
  
 7 SHOW COMPLIANCE WITH SECTION 13 OF THE ENERGY CODE.
  
 8. PER SECTION 806.1 ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 9. SANITARY RISER DIAGRAM. PLEASE INDICATE ALL PIPE
 SIZES AND TRAP SIZES FOR THE BRANCH ARM AND FIXTURES
 FOR THE SINKS AND THE ICE BIN. TABLES 709.1 & 710.1(2)
 AND SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved