| Date |
Text |
| 2008-12-09 10:55:15 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 EXISTING BUILDING |
| | CITY WPB MUNICIPAL CODE |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. INDICATE ON THE PLANS THE CRITERIA FOR THE DESIGN OF |
| | THE PLANS. PLANS SHALL BE DESIGNED PER FBC-2004 WITH |
| | 2005, 2006 & 2007 REVISIONS. SECTION 106.1.1. |
| | |
| | 2. INDICATE THE LEVEL OF ALTERATION AS REQUIRED IN |
| | CHAPTER 3 OF THE EXISTING BUILDING CODE. SECTION |
| | 106.1.1. |
| | |
| | 3. APPLICATION INDICATES NO CHANGE OF OCCUPANCY. THE |
| | EXISTING SPACE WAS A MERCANTILE SPACE PREVIOUSLY AND IS |
| | NOW AN ASSEMBLY OCCUPANCY. PLEASE INDICATE ON THE |
| | APPLICATION AND SHOW THE OCCUPANCY ON THE PLANS. |
| | SECTION 106.1.2 AND TABLES 1004.1.2 & 403.1. |
| | |
| | 4. PER SECTION 1210.2 THE WALLS WITHIN 2 FEET OF A |
| | WATER CLOSET OR URINAL SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE TO A HEIGHT OF 4 FEET ABOVE THE |
| | FLOOR. PLEASE SUBMIT A DETAIL OR A FINISH SCHEDULE TO |
| | SHOW COMPLIANCE. |
| | |
| | 5. THE VALUE OF THE WORK IS INDICATED AS $2100.00, |
| | (SINCE UPPED TO $6700.00 BY L. MARTINEZ). IF IN THE |
| | OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION |
| | OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. SECTION 108.3. - WITH THE FOLLOWING WORK |
| | INDICATED ON THE PLANS, I BELIEVE THE VALUATION IS |
| | UNDERESTIMATED. |
| | DEMO: |
| | REMOVE CEILING, NON-BEARING WALL, WALL OPENING BETWEEN |
| | EXISTING RESTAURANT & NEW SPACE ADDED, & DOOR. |
| | NEW WORK: |
| | CLOSE DOORWAY, FINISH OPENING BETWEEN EXISTING |
| | RESTAURANT & NEW SPACE, NEW TILE IN TOILET ROOMS, NEW |
| | TILE FLOOR AT ENTRANCE, NEW WOOD FLOOR, ENGINEERING OF |
| | OPENING TO NEW RESTAURANT. |
| | NEW WORK PLUMBING: |
| | REMOVE EXISTING TOILET FIXTURES AND REPLACE WITH |
| | NEW,(2-W/C'S & 2 LAVS). NEW SINKS AT BAR AREA, (1 HAND |
| | SINK, & 1 TRIPLE COMP. SINK, (INDICATED ON RISER |
| | DIAGRAM), OR 2 COMP. SINK, (INDICATED ON FLOOR PLAN), |
| | PLEASE CORRELATE. ONE ICE BIN WITH FLOOR SINK OR HUB |
| | DRAIN. |
| | NEW WORK ELECTRICAL: |
| | NEW TRAC LIGHTING, (7 TRACKS & 7 HANGING LIGHTS WITH |
| | ALL WIRING). |
| | |
| | 6. THE EXISTING GREASE INTERCEPTOR WILL HAVE TO BE |
| | INSPECTED AND APPROVED FOR THE EXTRA LOAD INDICATED ON |
| | THE PLANS, (36 TABLE AND 6 BAR). PLEASE CONTACT HOLLY |
| | MCGRATH, LABORATORY SUPERVISOR, PUBLIC UTILITIES |
| | DEPARTMENT AT (561) 822-2200 EXT 2271, BY FAX (561) |
| | 822-2279 OR BY E-MAIL [email protected]. A WRITTEN |
| | DERTIMINATION IS REQUIRED TO BE SUBMITTED FOR PERMIT |
| | APPROVAL. |
| | |
| | 7 SHOW COMPLIANCE WITH SECTION 13 OF THE ENERGY CODE. |
| | |
| | 8. PER SECTION 806.1 ACCESSIBILITY IN PORTIONS OF |
| | BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 9. SANITARY RISER DIAGRAM. PLEASE INDICATE ALL PIPE |
| | SIZES AND TRAP SIZES FOR THE BRANCH ARM AND FIXTURES |
| | FOR THE SINKS AND THE ICE BIN. TABLES 709.1 & 710.1(2) |
| | AND SECTION 106.1.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |