| 2008-11-25 15:01:52 | BUILDING PLAN REVIEW |
| | PERMIT: 08110461 |
| | ADD: 2455 METROCENTRE BLVD |
| | CONT: CROWTHER ROOFING |
| | TEL: (239)337-1300 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | HOMEWOOD SUITES |
| | ACTION: DENIED |
| | |
| | 1) SHEET LWC LAYOUT SHEET INDICATES THAT AT THE ROOF |
| | DRAINS THERE IS NO INSULATION ONLY THE LIGHT WEIGHT |
| | CONCRETE THEN THE INSULATION BOARD IS STAGERED IN |
| | HEIGHT 1" THROUGH 7". PLEASE REVIEW THE ENERGY |
| | CALCULATIONS REQUIRING A MINIMUM OF 6" AT THE ROOF |
| | DRAIN. THE DATA INPUT REPORT INDICATES A MINIMUM OF 6" |
| | INSULATION WITH 3" LIGHT WEIGHT CONCRETE ON TOP. PLEASE |
| | SEE 13-404.1.A THE MINIMUM PERFORMANCE LEVEL OF |
| | INSULATION IS JUST THAT IT IS NOT AN AVERAGE BUT THE |
| | MINIMUM AMOUNT REQUIRED. |
| | |
| | THE PRODUCT HOL-E-BOARD R-VALUES ONLY GO TO 5" PLEASE |
| | PROVIDE FOR THE THICKER REQUIREMENTS REQUIRED FOR THIS |
| | JOB. |
| | |
| | CONCERNS ARE WITH THE AMOUNT OF INSULATION REQUIRED, |
| | WILL THERE BE FASTENERS ON THE MARKET TO SECURE THE |
| | PRODUCT IN QUESTION OR WILL THERE NEED TO BE MORE ROOF |
| | DRAINS CLOSER TOGETHER TO REDUCE THE AMOUNT OF MATERIAL |
| | IT WILL TAKE TO HAVE A COMPLIANT ROOF. |
| | |
| | 2) TITEN STRUCTURAL ENGINEERING ENHANCED FASTENING |
| | DOCUMENT WILL NEED TO BE ORIGINAL SIGNATURE AND SEAL |
| | NOT COPIES. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | PLEASE NOTE THE TSE REPORT SUBMITTED REFRENECES JOHN |
| | MANSVILLE PERMA PLY 28 (NOA 06-0626.05) BASE SHEET |
| | FASTENER PATTERNS FOR ZONES 2 & 3 BUT THE REPORT WAS |
| | NOT SUBMITTED. |
| | REPORTS SUBMITTED: |
| | |
| | NOA 07-0228.07 JOHN MANSFIELD MOD BIT OVER LIGHTWEIGHT |
| | CONCRETE DECK |
| | |
| | NOA 05-0803.04 TPO SINGLE PLY OVER LIGHTWEIGHT CONCRETE |
| | DECK |
| | |
| | NOA 03-0923.03 EXPIRED 10-19-08 CELCORE LIGHTWEIGHT |
| | INSULATING CONCRETE |
| | ------------------------------------------------------- |
| | -------- |
| | NOA 07-1023.09 SPANISH "S" ROOF TILE |
| | |
| | NOA 04-1116.01 POLYSET ONE ROOF TILE ADHESIVE |
| | |
| | NOA 07-0124.02 DENS DECK |
| | |
| | FL 8380.1DCSM STEEL RIDGE ANCHOR |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |