| 2008-12-24 15:45:26 | ** DENIED 2ND REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS ELECTRICAL |
| | REVIEW. |
| | THE LIGHTING LEVELS NEED TO COMPLY WITH FBC |
| | 13-415.2,13-415.2.ABC.1.1,.1.2 AND TABLE 13-415.2.B AS |
| | SUBMITTED. |
| | THE LEVELS SHOWN EXCEED ALLOWANCES. MUST MEET |
| | PRESCRIPTIVE REQUIREMENTS. THE BASE BUILDING FOR |
| | EXISTING LIGHTING USED TRADE OFFS HOWEVER THIS IS NOT |
| | POSSIBLE WITH THE SPECIFIC SCOPE AS SHOWN. |
| | THE FOLLOWING IS EXTRACTED FROM 13-415.2.B.2. THIS IS |
| | THE SECOND SENTENCE IN PARAGRAPH. |
| | |
| | **ADDITIONAL POWER SHALL BE ALLOWED ONLY IF THE |
| | SPECIFIED LIGHTING IS INSTALLED, SHALL BE USED ONLY FOR |
| | THE SPECIFIED LUMINAIRES, AND SHALL NOT BE USED FOR ANY |
| | OTHER PURPOSE OR IN ANY OTHER SPACE.** |
| | |
| | THERE IS NOT ENOUGH INFORMATION ON FIXTURE *C* TO |
| | VERIFY ALLOWANCE, THE TOTAL NUMBER OF FIXTURES, THE |
| | TOTAL WATTAGES ETC. |
| | PLEASE KNOW THAT BASED ON THE WATTAGE SHOWN ON FIXTURE |
| | *B*, THE AMOUNT SHOWN ON CALCULATIONS IS LOWER. |
| | |
| | 2) NOTE: RISER AS SUBMITTED IS NOT ACUTAL COMPLETE |
| | ELECTRICAL RISER AND SERVICE OF BUILDING. THE RISER AS |
| | SHOWN IS ONLY PART OF THE BASE BUIDLING ELECTRICAL |
| | SERVICE. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |