| 2008-12-01 10:53:53 | |
| | ** FAILED REVIEW |
| | |
| | |
| | 1) NOTE: PLEASE SEE ELECTRICAL RISER AS SHOWN ON E2.01 |
| | IS NOT THE LATEST RISER FOR THE BUILDING. PLEASE |
| | ADJUST. |
| | PLEASE SEE FOR EXAMPLE PANEL L47A INDICATES THIS PANEL |
| | AS A MLO. THIS DOES NOT COORDINATE WITH BASE BUILDING. |
| | THE FEEDERS ARE TAPPED CONDUCTORS WHICH ARE REQUIRED TO |
| | TERMINATE IN OVER CURRENT PROTECTION. |
| | 240.21,408.36 |
| | 230, 240, ETC |
| | FBC 106.1.1 |
| | |
| | 2) NOTE: PLEASE PROVIDE EMERGENCY EGRESS LIGHTING PER |
| | NFPA-101 7.8,7.9 AND CIRCUITING PER 700.12. |
| | |
| | 3) NOTE: PLEASE REMOVE NOTES ON LIGHTING PERFORMANCE |
| | CALCULATIONS WHICH DO NOT APPLY. |
| | FOR EXAMPLE: THIS IS NOT A RETAIL SPACE THEREFORE NO |
| | ALLOWANCES CAN BE MADE. |
| | FOR EXAMPLE: IN ORDER TO USE ALLOWANCES FOR ACCENT |
| | LIGHTING, ACCENT LIGHTING FOR THAT PURPOSE MUST BE |
| | INSTALLED. THE PLANS ONLY INDICATE GENERAL LIGHTING. |
| | 13-415.2, 13-415.2.ABC.1.1,.1.2. |
| | NOTE PERTAINING TO TRADE OFFS DOES NOT APPLY AS ONLY |
| | PRESCRIPTIVE FOR HALLWAYS/CORRIDOR ALLOWANCES ARE |
| | APPLICABLE. |
| | |
| | 4) NOTE: PLANS STATE 2006 REVISIONS TO THE 2004 FBC |
| | HOWEVER IT SHOULD READ 2004 FBC W/ 2007 REVISIONS. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |