Plan Review Notes
Plan Review Notes For Permit 08110426
Permit Number 08110426
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-12-03 15:14:13550 SOUTH ROSEMARY AVENUE
 INSTALLATION OF FIRE ALARM SYSTEM
  
 1. PLEASE PROVIDE DOCUMENTATION TO THIS OFFICE
 INDICATING THE REASON FOR THE INSTALLATION OF CEILING
 MOUNTED SPEAKER STROBES.
  
 2. PLEASE DECLARE ON THE PLANS WHAT THE VOICE
 EVACUATION MESSAGE WILL INDICATE TO THE OCCUPANTS IN
 THE EVENT OF AN EMERGENCY. ALSO PLEASE INDICATE WHERE
 THE ALERT TONES ARE POSITIONED IN THIS MESSAGE.
  
 3. ON PAGE FA-2 OF 3, THE PLANS INDICATE THAT WHEN A
 DUCT DETECTOR ACTIVATES, IT WILL CAUSE A SUPERVISORY
 SIGNAL. PLEASE REVISE THE PLANS TO DECLARE THAT WHEN A
 DUCT DETECTOR ACTIVATES, IT WILL CAUSE A GENERAL FIRE
 ALARM CONDITION.
  
 4. THE FIRE ALARM PANEL SHALL BE CAPABLE OF
 TRANSMITTING THE FOLLOWING SIGNALS TO THE MONITORING
 COMPANY; GENERAL ALARM, WATERFLOW, SUPERVISORY, AND
 TROUBLE SIGNALS.
  
 5. THE ENTIRE FIRE ALARM SYSTEM INSTALLATION SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE
 ALARM CODE AND NFPA 70, THE NATIONAL ELECTRIC CODE AND
 OTHER APPROPRIATE STANDARDS.
  
 6. THE ENTIRE INSTALLATION IS SUBJECT TO FIELD
 INSPECTION AND APPROVAL. WHEN COMPLETED THE ENTIRE
 SYSTEM SHALL BE INSPECTED, TESTED, AND APPROVED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved