2009-06-01 10:55:26DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1 (ADMIN)
  
 1. SHT 8A (NEW) SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN ON SHEET 9. THE SANITARY RISER DIAGRAM
 DOES NOT SHOW THE WASH MACHINE PIPING, NOR DOES IT
 REFLECT THE PIPING SHOWN ON THE FLOOR PLAN. IF THE
 FLOOR PLAN HAS CHANGED THEN A NEW FLOOR PLAN SHOWING
 ALL THE PLUMBING FIXTURES AND PIPING THAT REFLECTS THE
 RISER DIAGRAM IS REQUIRED. IF THE FLOOR PLAN HAS NOT
 CHANGED, THEN THE PIPING SHALL BE CHANGED TO REFLECT
 THE FLOOR PLAN. SECTIONS 106.1.1 & 406.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  