2008-12-04 15:55:52DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHTS 9 & 10 FLOOR PLAN AND SANITARY RISER DIAGRAM.
 EVERY DRY VENT, (RELIEF VENT FOR THE AAV), CONNECTING
 TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE. SECTION 905.3.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6
 INCHES ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR
 TRAPPED FIXTURE BEING VENTED. SECTION 905..4. -- THAT
 SAID, THE RELIEF VENT IS NOT REQUIRED FOR THE AAV PER
 SECTION 917.3.1.
  
 2. SHT 10 WATER RISER DIAGRAM. THE WATER SUPPLY PIPES,
 (HOT & COLD), REQUIRE WATER HAMMER ARRESTORS. SECTION
 604.9. PLEASE SHOW ON THE RISER DIAGRAM AND ON THE
 WASHING MACHINE PIPING DETAIL.
  
 3. SHT 10 WATER HEATER DETAIL. THE P&T RELIEF VALVE
 DISCHARGE LINE SHALL HAVE NO TRAPPED SECTIONS AND SHALL
 HAVE A VISIBLE AIR GAP OR AIR GAP FITTING IN THE SAME
 ROOM AS THE WATER HEATER. SECTION 504.6.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  