| 2008-12-10 16:20:41 | 2004 FBC W/2007 REVISIONS |
| | ADDITION AND REMODEL |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) THE TYPE OF CONSTRUCTION SPECIFIED ON SHEET 1 IS |
| | III-B, WHICH REQUIRES THE EXTERIOR BEARING WALLS TO |
| | HAVE A TWO HOUR FIRE-RESISTANCE RATING. PLEASE CHANGE |
| | TO TYPE V-B. FBC SECTION 602 AND TABLE 601 |
| | |
| | 3) ON SHEET 5 THE STRUCTURE IS SPECIFIED AS BEING |
| | LOCATED IN EXPOSURE CATEGORY C. HOWEVER, THE COMPONENT |
| | AND CLADDING PRESSURES SPECIFIED FOR THE WINDOWS AND |
| | DOORS ON SHEET 3 ARE FOR EXPOSURE B. THE STRUCTURE IS |
| | LOCATED IN EXPOSURE B. PLEASE REVISE ONE OR THE OTHER |
| | SO THAT THEY CORRESPOND. SEE R301.2.1.4 AND TABLE |
| | R301.2(2). |
| | |
| | 4) SHOW COMPLIANCE WITH R320.1 TERMITE PROTECTION SHALL |
| | BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL |
| | APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES |
| | APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE |
| | PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT |
| | TO NEW CONSTRUCTION (SEE SECTION 202, REGISTERED |
| | TERMITICIDE). UPON COMPLETION OF THE APPLICATION OF THE |
| | TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF |
| | COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT |
| | BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE |
| | FOLLOWING STATEMENT: ?THE BUILDING HAS RECEIVED A |
| | COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN |
| | TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND |
| | LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF |
| | AGRICULTURE AND CONSUMER SERVICES.? |
| | |
| | 5) SPECIFY THE UPLIFT CAPACITY FOR THE SIMPSON MGT |
| | CONNECTOR IN THE SCHEDULE ON SHEET 7. R 801.2. |
| | |
| | 6) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS OR |
| | SPECIFY THE FL#S FOR THEM IN THE CONNECTOR SCHEDULE. |
| | FAC RULE 9B-72 |
| | |
| | 7) SPECIFY THE OPENING WIDTH FOR THE HORIZONTAL SLIDING |
| | KITCHEN WINDOW ON THE PLANS. THE OPENING HEIGHT IS |
| | SPECIFIED ON SECTION 2 ON SHEET 4 AS 5'-0". R301.2.1 |
| | |
| | 8) SUBMIT PRODUCT APPROVALS FOR THE SLIDING HORIZONTAL |
| | SLIDING KITCHEN WINDOW. THE ONES THAT WERE SUBMITTED |
| | ARE FOR A SLIDING GLASS DOOR WITH MINIMUM HEIGHT OF |
| | 6'-8". RULE 9B-72 |
| | |
| | 9) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK. FAC |
| | RULE 9B-72 |
| | |
| | 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | PGT PROJECTED WINDOW IS EXPIRED. PLEASE SUBMIT CURRENT |
| | PRODUCT APPROVALS. FAC RULE 9B-72 |
| | |
| | 11) SPECIFY THE WIDTH OF THE REAR FRENCH DOOR AND |
| | SIDELITES. R301.2.1 |
| | |
| | 12) THE BEDROOM WINDOWS WILL NOT COMPLY WITH THE |
| | REQUIRED EMERGENCY ESCAPE AND RESCUE OPENING CLEAR |
| | OPENING HEIGHT IF SINGLE HUNG WINDOWS ARE INSTALLED. |
| | SEE R310.1AND R310.1.2 MINIMUM OPENING HEIGHT. THE |
| | MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES. |
| | |
| | 13) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | HAVE ALL NEW PRODUCT APPROVALS REVIEWED BY THE D.O.R. |
| | |