Plan Review Notes
Plan Review Notes For Permit 08110425
Permit Number 08110425
Review Stop B
Sequence Number 1
Notes
Date Text
2008-12-10 16:20:412004 FBC W/2007 REVISIONS
 ADDITION AND REMODEL
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) THE TYPE OF CONSTRUCTION SPECIFIED ON SHEET 1 IS
 III-B, WHICH REQUIRES THE EXTERIOR BEARING WALLS TO
 HAVE A TWO HOUR FIRE-RESISTANCE RATING. PLEASE CHANGE
 TO TYPE V-B. FBC SECTION 602 AND TABLE 601
  
 3) ON SHEET 5 THE STRUCTURE IS SPECIFIED AS BEING
 LOCATED IN EXPOSURE CATEGORY C. HOWEVER, THE COMPONENT
 AND CLADDING PRESSURES SPECIFIED FOR THE WINDOWS AND
 DOORS ON SHEET 3 ARE FOR EXPOSURE B. THE STRUCTURE IS
 LOCATED IN EXPOSURE B. PLEASE REVISE ONE OR THE OTHER
 SO THAT THEY CORRESPOND. SEE R301.2.1.4 AND TABLE
 R301.2(2).
  
 4) SHOW COMPLIANCE WITH R320.1 TERMITE PROTECTION SHALL
 BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION (SEE SECTION 202, REGISTERED
 TERMITICIDE). UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: ?THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 5) SPECIFY THE UPLIFT CAPACITY FOR THE SIMPSON MGT
 CONNECTOR IN THE SCHEDULE ON SHEET 7. R 801.2.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS OR
 SPECIFY THE FL#S FOR THEM IN THE CONNECTOR SCHEDULE.
 FAC RULE 9B-72
  
 7) SPECIFY THE OPENING WIDTH FOR THE HORIZONTAL SLIDING
 KITCHEN WINDOW ON THE PLANS. THE OPENING HEIGHT IS
 SPECIFIED ON SECTION 2 ON SHEET 4 AS 5'-0". R301.2.1
  
 8) SUBMIT PRODUCT APPROVALS FOR THE SLIDING HORIZONTAL
 SLIDING KITCHEN WINDOW. THE ONES THAT WERE SUBMITTED
 ARE FOR A SLIDING GLASS DOOR WITH MINIMUM HEIGHT OF
 6'-8". RULE 9B-72
  
 9) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK. FAC
 RULE 9B-72
  
 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 PGT PROJECTED WINDOW IS EXPIRED. PLEASE SUBMIT CURRENT
 PRODUCT APPROVALS. FAC RULE 9B-72
  
 11) SPECIFY THE WIDTH OF THE REAR FRENCH DOOR AND
 SIDELITES. R301.2.1
  
 12) THE BEDROOM WINDOWS WILL NOT COMPLY WITH THE
 REQUIRED EMERGENCY ESCAPE AND RESCUE OPENING CLEAR
 OPENING HEIGHT IF SINGLE HUNG WINDOWS ARE INSTALLED.
 SEE R310.1AND R310.1.2 MINIMUM OPENING HEIGHT. THE
 MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES.
  
 13) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 HAVE ALL NEW PRODUCT APPROVALS REVIEWED BY THE D.O.R.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]