| 2008-12-16 14:33:33 | * DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE FLORIDA BUILDING CODE 108.3. THE |
| | VALUES FOR COMPLETE SCOPE OF WORK FOR ELECTRICAL SHALL |
| | INCLUDE ALL LABOR, MATERIALS EQUIPMENT, DESIGN COST ETC |
| | EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED. THE |
| | APPLIED VALUE OF $7500.00 DOES NOT COVER THE COST OF |
| | ELECTRICAL EQUIPMENT LET ALONE ALL OTHER ITEMS IN SCOPE |
| | OF WORK. |
| | |
| | 2) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL RISER |
| | DIAGRAM FOR SCOPE OF HOOKING UP NEW ELECTRICAL SYSTEMS. |
| | PLEASE SHOW COMPLIANCE FOR AIC RATINGS OF EQUIPMENT. |
| | 110.9 |
| | PLEASE INCLUDE CONDUCTORS FOR ALL. (SERVICES, FEEDERS |
| | ETC) 310.16,240.4 |
| | PLEASE COMPLETE ALL GROUNDING ON RISER TO BE SUBMITTED |
| | PER 250.50,250.20,250.30, 250.66 ETC |
| | PLEASE SEE 230.70,,71,72,76,79 FOR REQUIRED SERVICE. |
| | ** KEEP IN MIND THESE ARE SOME CODE SECTIONS GIVEN AND |
| | OTHERS MAY APPLY DEPENDING ON ELECTRICAL SCOPE WHICH IS |
| | NOT SHOWN AT THIS TIME. |
| | |
| | 3 NOTE: PLEASE SEE 450.3B FOR MAXIMUM OCP OF 277/480V |
| | TRANSFORMER ON PRIMARY SIDE. |
| | ** SEE NOTES OF TABLE. |
| | |
| | 4) NOTE: THERE IS A LETTER ATTACHED FROM HOLLIS |
| | ENGINEERING CONSULTANTS WHICH IS ADDRESSED TO |
| | MIAMI-DADE BUILDING OFFICIAL IN ELECTRICAL. THIS LETTER |
| | IS MADE OUT TO A MUNICIPALITY WHICH THE WORK IS NOT |
| | BEING APPLIED. |
| | PLEASE ALSO SEE THIS LETTER CONTAINS A RAISED SEAL OVER |
| | A PHOTO-COPIED SIGNATURE WHICH IS A VIOLATION OF FAC |
| | 61G15-23.022 AND FS 471.025 |
| | |
| | 5) NOTE: LETTER AS NOTED ABOVE AS WELL AS COVER SHEET |
| | MENTIONS INSTALLATION TO NRTL STANDARDS HOWEVER PLEASE |
| | PROVIDE DOCUMENTATION ON ELECTRICAL EQUIPMENT AND |
| | ASSEMBLY BEING INSTALLED. THESE MUST BE A LISTED SYSTEM |
| | BY A NRTL NOT ONLY INSTALLED BY THEIR REQUIREMENTS OR |
| | STANDARDS. |
| | 110.3,90.7 |
| | PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS ON LISTED |
| | EQUIPMENT. |
| | |
| | 6) NOTE: TEMPORARY INSTALLATIONS AS DEFINED IN THE NEC |
| | AS WELL AS FBC IS 180DAYS. (6MONTHS) |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |