| 2010-03-17 15:33:00 | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. NOTE: REVIEW WAS DONE UNDER THE 2008 NEC. IF UNDER |
| | THE 2005 NEC PLEASE DISREGARD AREA COMMENTS NOTED WITH |
| | 2008 NEC. |
| | |
| | 2. NOTE: THERE IS CONFUSION OVER THE SERVICE AS SHOWN. |
| | THE ELECTRICAL RISER STATES *EXISTING ELECTRICAL RISER |
| | DIAGRAM*. HOWEVER, THERE ARE SEVERAL ITEMS WHICH ARE |
| | ALSO SHOWN AS NEW. REVIEW IS BASED ON THESE ITEMS AS |
| | NEW AND NOT EXISTING. THERE IS INFORMATION NOT YET |
| | SHOWN TO CONFIRM A COMPLETE REVIEW. |
| | A) PLEASE SEE 250.94 FOR REQUIRED INTERSYSTEM BOND. |
| | 2008 NEC. |
| | B) PLEASE INDICATE THE SIZE OF THE EXISTING SERVICE TO |
| | INCLUDE SERVICE ENTRANCE CONDUCTORS. 240.4, 31.16, |
| | 310.15 ETC. |
| | C) PLEASE COORDINATE PANELS AND RISER. PANELS ARE SHOWN |
| | RATED AT 150AMPS, YET THE RISER INDICATES PANELS AS |
| | 100AMPS. |
| | D) PLEASE SEE RISER AS BOTH DISCONNECTS SHOWN FOR BOTH |
| | UPSTAIRS AND DOWNSTAIRS PANELS ARE RATED AT 200AMPS. IT |
| | IS NOT PERMITTED TO HAVE 200AMP RATED OVER CURRENT |
| | PROTECTION FEEDING 100AMP OR 150AMP RATED PANELS. |
| | E) THE SAME 200AMP RATED DISCONNECTS ARE SHOWN ON |
| | FEEDERS RATED FOR 100AMPS. THIS IS NOT PERMITTED. |
| | PLEASE VERIFY MAINS AND OVERCURRENT PROTECTION. 310.16, |
| | 240.4, 310.15B6 |
| | |
| | 3. NOTE: PLEASE SEE 210.12 OF THE 2008 NEC AND LIST ALL |
| | REQUIRED ARC FAULT PROTECTED CIRCUITS. PLEASE SEE SAME |
| | CODE SECTION UNDER THE 2005 NEC AND LIST ACCORDINGLY. |
| | |
| | 4. NOTE: PLEASE SEE 406.8 FOR REQUIRED RECEPTACLES |
| | OUTSIDE IN DAMP OR WET LOCATIONS. 2008 NEC |
| | |
| | 5. NOTE: PLEASE SEE 250.32, 250.66, 250.50 FOR |
| | GROUNDING ELECTRODE SYSTEM REQUIRED AT DETACHED |
| | BUILDING. |
| | |
| | 6. NOTE: PLEASE SEE 250.66 FOR SIZING OF THE GROUNDING |
| | ELECTRODE CONDUCTOR AT SERVICE. AS THE SERVICE ENTRANCE |
| | CONDUCTORS AND THE SIZE OF SERVICE ARE NOT SHOWN, THE |
| | #4 AS SHOWN CANNOT BE CONFIRMED TO BE CODE COMPLIANT. |
| | BASED ON THE LOAD AND SIZE OF ALL OVER CURRENT |
| | PROTECTIVE DEVICES SHOWN, THE GROUNDING ELECTRODE IS |
| | TOO SMALL. |
| | |
| | 7. NOTE: CLOSET LIGHT FIXTURES SHOWN DO NOT APPEAR TO |
| | MEET 410.8 |
| | |
| | 8. NOTE: PLANS DO NOT CONTAIN ANY DESIGN PROFESSIONAL |
| | MEETING 481, 471, 489 OR 481.229, 471.003 EXCEPTIONS |
| | PLEASE BE SURE PLANS CONTAIN RESPONSIBLE DESIGNER UNDER |
| | SECTIONS NOTED. |
| | |
| | 9. NOTE: ALL RECEPTACLES SERVING KITCHEN COUNTER SPACE |
| | ARE REQUIRED TO BE GFI/GFI PROTECTED. 210.8A6 |
| | |
| | 10. NOTE: OVER CURRENT PROTECTION FOR 5KW AHU IS TOO |
| | HIGH. 422.11 |
| | |
| | 11. NOTE: LIGHTING FIXTURE REQUIRED IN KITCHEN AND ALSO |
| | SHOWS LIGHT SWITCH NOT CONTROLLING ANYTHING? 210.70 |
| | NEW OR EXISTING LIGHT FIXTURES IN STAIRS? |
| | NEW OR EXISTING LIGHT IN SECOND FLOOR BATH? |
| | |
| | 12. NOTE: MISSING SMOKE ALARM PER 11.5.1, 11.8.3 OF |
| | NFPA-72 ON LOWER LEVEL OF STAIRS LEADING TO FLOOR |
| | ABOVE. |
| | |
| | 13. NOTE: PANEL SCHEDULES NEED TO BE SPECIFIC. FIRST |
| | FLOOR ONLY INDICATES ONE CIRCUIT FOR GENERAL LIGHTING. |
| | WHERE ARE THE OTHER GENERAL LIGHTING AND RECEPTACLE |
| | CIRCUITS? THESE ARE ALSO REQUIRED TO BE SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THEY FEED. THE USE OF GENERAL |
| | LIGHTING AND RECEPTACLES IS NO LONGER ACCEPTACLE UNDER |
| | THE 2005 AND 2008 NEC. 408.4 |
| | |
| | 14. NOTE: NO ELECTRICAL SHOWN ON PLANS FOR SECOND FLOOR |
| | WASHER/DRYER? FBC 106.3.5.1.2, 210.52F, 210.11C2 |
| | |
| | 15. NOTE: DISCONNECTS FOR PANELS AT DETACHED STRUCTURE |
| | ARE SHOWN ON PLANS, HOWEVER NOT ON RISER. 225.31-225.39 |
| | |
| | |
| | DEWEY PALMER |
| | |