| | APPLICATION #08110405 ELECTRICAL PLAN REVIEW |
| | 716 NEW YORK STREET 1/8/09 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET 7.1, UNLESS OTHERWISE |
| | NOTED |
| | |
| | THESE COMMENTS FROM THE PREVIOUS REVIEW NEED FURTHER |
| | RESPONCE, INDICATED BY *** |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY*** NOT DONE AND NO RESPONSE GIVEN. |
| | |
| | 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL |
| | SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLES 230 |
| | AND 225 CAN BE REVIEWED*** THE SITE PLAN SHOWS THERE |
| | ARE NO DISCONNECTS ON THE BACK BUILDING PER |
| | 230.70(A)(1) "READILY ACCESSIBLE LOCATION THE SERVICE |
| | DISCONNECTING MEANS SHALL BE INSTALLED AT A READILY |
| | ACCESSIBLE LOCATION EITHER OUTSIDE OF A BUILDING OR |
| | STRUCTURE OR INSIDE NEAREST THE POINT OF ENTRANCE OF |
| | THE SERVICE CONDUCTORS". ALSO SEE 250.32 FOR GROUNDING |
| | OF SEPARATE STRUCTURES. INCLUDE ON THE RISER. |
| | |
| | 7 } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE |
| | FEEDERS ON THE RISER DIAGRAM.***THIS COMMENT MUST BE |
| | RESPONDED TOO SO THE COMPLIANCE FOR 250.122, |
| | 310.15(B)(6) CAN BE REVIEWED. THE RESPONSE OF THE |
| | SERVICE BEING INSTALLED UNDER ANOTHER PERMIT IS ONLY |
| | PARTIALLY CORRECT AS THAT PERMIT (#06120063) EXPIRED |
| | WITHOUT HAVING PASSED ANY INSPECTIONS. THE CONDUCTORS |
| | AND CONDUIT SIZE AND TYPE NEED TO BE VERIFIED AS |
| | COMPLIANT. INDICATE ON DRAWINGS. |
| | |
| | PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD |
| | SHEETS (ONE SET) TO EXPEDITE REVIEW AND SUBMIT WRITTEN |
| | RESPONSE TO THE COMMENTS MADE IN THIS REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | |