| Date |
Text |
| 2009-01-08 16:31:35 | |
| | |
| | APPLICATION #08110405 ELECTRICAL PLAN REVIEW |
| | 716 NEW YORK STREET 1/8/09 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET 7.1, UNLESS OTHERWISE |
| | NOTED |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY. |
| | |
| | 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL |
| | SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLES 230 |
| | AND 225 CAN BE REVIEWED. |
| | |
| | 4} PROVIDE LOAD CALCULATIONS FOR THE SERVICE SHOWN |
| | (INCLUDING THE MAIN HOUSE) PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| | |
| | 5} THERE ARE TWO RECTANGULAR BOXES IN THE FEED FROM THE |
| | PANEL TO THE 100 AMP PANELS IN THE BACK BUILDING. |
| | INDICATE IF THESE ARE EQUIPMENT, AND IF SO WHAT. ADD TO |
| | ELECTRICAL SYMBOLS LEGEND ALONG WITH AN EXPLANATORY |
| | NOTE. 215.5 NEC |
| | |
| | 6} LOCATE ALL PANELS AND DISCONNECTS ON THE FLOOR PLAN |
| | FOR THE UNITS, THIS SHEET. 215.5 NEC. |
| | |
| | 7 } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE |
| | FEEDERS ON THE RISER DIAGRAM. |
| | |
| | 8} THE A/C IS LISTED AS 5 KW IN THE LOAD CALCULATIONS |
| | BUT SHOWN AS 10 KW IN THE PANEL SCHEDULES, BOTH FLOORS. |
| | THERE ARE NO MANUFACTURES SPECIFICATIONS FOR THE AIR |
| | HANDLERS ON SHEET 6.1, PROVIDE SAME SO THE CORRECT |
| | CALCULATIONS AND PANEL SCHEDULE OCP AND CONDUCTOR SIZES |
| | MAY BE REVIEWED. 220, 240 NEC. SEE NOTE 16 THIS SHEET. |
| | |
| | 9} THE BATH CIRCUITS REQUIRED BY 210.11(C)(3) ARE NOT |
| | LISTED ON THE PANEL SCHEDULE. |
| | |
| | 10} THERE ARE DISHWASHERS ON THE PANEL SCHEDULES (BOTH) |
| | THAT ARE NOT SHOWN IN THE UNITS OR LISTED IN THE |
| | CALCULATIONS. 408.4 NEC. |
| | |
| | 11} THERE ARE NO SMOKE ALARMS IN THE FIRST FLOOR UNIT. |
| | 313.1.1 |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | |