Plan Review Notes
Plan Review Notes For Permit 08110404
Permit Number 08110404
Review Stop B
Sequence Number 2
Notes
Date Text
2008-12-31 10:19:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. ADDRESSED.
  
 2. ACCESSIBLE PARKING IS TO BE ON AN ACCESSIBLE ROUTE
 MINIMUM 44", FBC11-4.6.2(1). THE PLAN REFERS TO SHEET
 S, BUT THIS WAS NOT SUBMITTED. PLEASE INCLUDE ALL
 NECESSARY DIMENSIONS ON THE PLAN.
  
 2ND REVIEW, ADDRESSED FOR THE AREA BY THE SIDEWALK, BUT
 NOT ADDRESSED FOR THE ROUTE FROM THE PARKING TO
 ACCESSIBLE ENTRANCE. THERE ARE NO DIMENSIONS SHOWING
 WIDTH OF THE ACCESSIBLE ROUTE BETWEEN THE END OF THE
 TRUNCATED DOME AREA AND THE ACCESSIBLE ENTRANCE. IT
 APPEARS TO BE COMPLIANT BUT THE REQUIRESTED DIMENSIONS
 WERE NOT PROVIDED (BETWEEN COLUMNS AND BUILDING).
 ACCESSIBLE ROUTE TO THE ACCESSIBLE ENTRANCE IS NOT
 FULLY SHOWN; NO DOOR IS SHOWN ON THE PLAN. THE CODE
 STATES THAT THE ACCESSIBLE PARKING IS TO BE ON THE
 SHORTEST SAFEST ACCESSIBLE ROUTE TO AN ACCESSIBLE
 ENTRANCE, DIFFICULT TO DETERMINE WITHOUT KNOWLEDGE OF
 WHERE THE ACCESSIBLE ENTRANCE IS.
  