| Date |
Text |
| 2008-12-02 10:08:40 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SUBMIT A SANITARY AND WATER RISER DIAGRAM TO REFLECT |
| | ALL WORK SHOWN ON THE FLOOR PLAN. FOR THE SANITARY SHOW |
| | ALL PIPE SIZES, TRAPS, VENTS, CONNECTIONS TO WASTE |
| | STACKS & VENT THRU THE ROOF. FOR WATER SHOW ALL PIPE |
| | SIZES, VALVES AND, (WHERE REQUIRED BY SECTION 604.9), |
| | WATER HAMMER ARRESTORS. SECTIONS |
| | 106.3.5.1.3(3)(4)(5)(6)(10)(13) 601.1, 604.1, 604.5, |
| | 701.1, 704.1, 708, 709, 710, 901.1, 904, 905 & 916. |
| | |
| | 2. THE ENERGY EFFICIENCY CALCULATIONS INDICATE "N/A" |
| | FOR THE HOT WATER, BUT THE PLANS INDICATE A TANKLESS |
| | WATER HEATER FOR THE P-4 SINK IN THE BREAK ROOM. PLEASE |
| | CLARIFY/CORRELATE. SECTION 13. |
| | |
| | 3. SHT A-1.01 HAS WHITE OUT FOR THE APPLICABLE CODES ON |
| | THE DATE FOR THE 2007 SUPPLEMENTS. PER SECTION 106.1.3 |
| | WHITE OUT IS NOT APPROVED ON PLANS SUBMITTED FOR PUBLIC |
| | RECORD. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |