2008-12-06 16:30:25REVIEW #: 1ST
 ACTION: PASSED WITH CONDITIONS (SEE BELOW)
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-2 CALLS FOR CU ATTACHMENT TO SLAB IN
 ACCORDANCE WITH 301.13.1. THIS SECTION AND PRESCRIPTIVE
 METHOD IS ONLY APPLICABLE TO R-3 OCCUPANCIES. PLEASE
 PROVIDE DETAIL WITH WIND CALCULATIONS OR MANUFACTURER'S
 INFORMATION FOR WIND LOAD ATTACHMENT IN ACCORDANCE WITH
 FBCM 301.13.
  
 2. PLANS HAVE BEEN MODIFIED WITH WHITE-OUT. WHEN
 REVISING PLANS TO ADDRESS THE ABOVE COMMENT, PLEASE
 MAKE NECESSARY CORRECTIONS WITHOUT ALTERING THE PLANS
 IN ACCORDANCE WITH FBCB 106.1.3.
  
 NOTE: ENERGY CALCULATIONS WILL BE SIGNED/STAMPED WHEN
 PLUMBING COMMENTS HAVE BEEN ADDRESSED.
  