Plan Review Notes For Permit 08110341
Permit Number 08110341
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-04 14:25:09DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. 1 OF 8 DESIGN CRITERIA TO INDICATE 2007 REVISIONS TO
 THE FBC-2004.
  
 2. WHITE OUT IS NOT APPROVED ON SHEETS SUBMITTED FOR
 PUBLIC RECORD. (SHTS 2 0F 8 & 6 OF 8). SECTION 106.1.3.
  
 3. SHTS 2 OF 8 & 7 OF 8 (RISER DIAGRAM). THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO BRANCH
 DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES IN
 DIAMETER. SECTION 406.3. PLEASE CORRECT ON THE FLOOR
 PLAN AND THE RISER DIAGRAM. 2" SHOWN ON THE FLOOR PLAN
 & RISER DIAGRAM.
  
 4. SHT 7 OF 8 SANITARY RISER DIAGRAM PLEASE SHOW THE
 AIR ADMITTENCE VALVE ON THE RISER DIAGRAM, AND THE
 DISHWASHER SHALL CONNECT UPSTREAM OF THE TRAP OF THE
 KITCHEN SINK. SECTIONS 106.1.1, 103.5.1.3(6) & 1002.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  