2008-12-07 12:35:22REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: ALTHOUGH MECHANICAL PLAN CONTAINS A NOTE FOR
 MODIFIED PLANS TO BE SUBMITTED AT A LATER DATE, MINIMUM
 CODE COMPLIANCE MUST BE DEMONSTRATED ON PLANS AT THIS
 TIME, PRIOR TO PERMIT ISSUANCE.
  
 1. PROPOSED NEW MASTER BATHROOM SHOWN NO OPERABLE
 WINDOWS TO THE OUTDOORS OR EXHAUST FAN. SHOW HOW
 REQUIRED VENTILATION FOR THIS ROOOM IS TO BE PROVIDED
 IN ACCORDANCE WITH FBC R303.3 THROUGH R303.5.
  
 2. PLANS CALL FOR CLOTHES DRYER IN THE PROPOSED NEW
 GARAGE. SHOW MEANS AND LOCATION OF DRYER EXHAUST IN
 ACCORDANCE WITH FBCR M1501.1 THROUGH M1501.3.
  
 3. NO ENERGY CALCULATIONS WERE PROVIDED WITH THIS
 APPLICATION. PROVIDE A PROPERLY COMPLETED FORM 600
 ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH FBCB
 13-101.2.2. ALSO, A COOLING AND HEATING LOAD
 CALCULATION SHALL BE PERFORMED ON THE BUILDING AND
 SHALL BE ATTACHED TO THE FORM 600 SUBMITTED WHEN
 APPLICATION IS MADE FOR A BUILDING PERMIT IN ACCORDANCE
 WITH FBCB 13-607.1.ABC.1.
  
 4. PROVIDE AN EQUIPMENT SCHEDULE TO CONFIRM EQUIPMENT
 BEING PROPOSED WILL BE IN COMPLIANCE WITH ENERGY CODE
 MINIMUM EFFICIENCIES AS SPECIFIED IN FORM 600 AND
 COOLING/HEATING LOAD CALCULATIONS AS STATED ABOVE.
  
 5. PROVIDE INSTALLATION DETAIL FOR ATTACHMENT OF
 OUTDOOR CONDENSING UNIT FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBCR M1307.3.
  
 6. IT IS NOT CLEAR ON PLANS WHETHER ALL NEW PROPOSED
 HABITABLE AREAS HAVE SUFFICIENT WINDOW AND DOOR
 OPENINGS FOR ADEQUATE VENTILATION. PLEASE PROVIDE
 VENTILATIONS CALCULATIONS SHOWING TOTAL DOOR/WINDOW
 OPENABLE AREAS WITH RESPECT TO FLOOR AREA BEING
 VENTILATED IN ACCORDANCE WITH FBC R303.1 AND R303.2.
  
 7. NOTE 1.3 ON SHEET 5 CALLS FOR A 10X10 TRANSFER W/ 8"
 DUCT BETWEEN THE FLORIDA ROMM AND "ADJACENT ROOM." THE
 LOCATION OF THIS TRANSFER AND WHICH ADJACENT ROOM IS
 NOT SHOWN ON PLANS. PLEASE CLARIFY THE LOCATION AND
 INTENT OF THIS DUCT IN ACCORDANCE WITH FBCR M1602.4.
  
 8. THERE ARE DUCTS FROM THE PROPOSED NEW AHU WHICH ARE
 MISSING SIZES ON THE PLANS. PLEASE PROVIDE MISSING
 INFORMATION. AN AIR DISTRIBUTION SYSTEM SHALL BE
 DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCR M1601.1 AND
 M1601.3.
  