| 2008-12-07 12:35:22 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | NOTE: ALTHOUGH MECHANICAL PLAN CONTAINS A NOTE FOR |
| | MODIFIED PLANS TO BE SUBMITTED AT A LATER DATE, MINIMUM |
| | CODE COMPLIANCE MUST BE DEMONSTRATED ON PLANS AT THIS |
| | TIME, PRIOR TO PERMIT ISSUANCE. |
| | |
| | 1. PROPOSED NEW MASTER BATHROOM SHOWN NO OPERABLE |
| | WINDOWS TO THE OUTDOORS OR EXHAUST FAN. SHOW HOW |
| | REQUIRED VENTILATION FOR THIS ROOOM IS TO BE PROVIDED |
| | IN ACCORDANCE WITH FBC R303.3 THROUGH R303.5. |
| | |
| | 2. PLANS CALL FOR CLOTHES DRYER IN THE PROPOSED NEW |
| | GARAGE. SHOW MEANS AND LOCATION OF DRYER EXHAUST IN |
| | ACCORDANCE WITH FBCR M1501.1 THROUGH M1501.3. |
| | |
| | 3. NO ENERGY CALCULATIONS WERE PROVIDED WITH THIS |
| | APPLICATION. PROVIDE A PROPERLY COMPLETED FORM 600 |
| | ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH FBCB |
| | 13-101.2.2. ALSO, A COOLING AND HEATING LOAD |
| | CALCULATION SHALL BE PERFORMED ON THE BUILDING AND |
| | SHALL BE ATTACHED TO THE FORM 600 SUBMITTED WHEN |
| | APPLICATION IS MADE FOR A BUILDING PERMIT IN ACCORDANCE |
| | WITH FBCB 13-607.1.ABC.1. |
| | |
| | 4. PROVIDE AN EQUIPMENT SCHEDULE TO CONFIRM EQUIPMENT |
| | BEING PROPOSED WILL BE IN COMPLIANCE WITH ENERGY CODE |
| | MINIMUM EFFICIENCIES AS SPECIFIED IN FORM 600 AND |
| | COOLING/HEATING LOAD CALCULATIONS AS STATED ABOVE. |
| | |
| | 5. PROVIDE INSTALLATION DETAIL FOR ATTACHMENT OF |
| | OUTDOOR CONDENSING UNIT FOR WIND RESISTANCE IN |
| | ACCORDANCE WITH FBCR M1307.3. |
| | |
| | 6. IT IS NOT CLEAR ON PLANS WHETHER ALL NEW PROPOSED |
| | HABITABLE AREAS HAVE SUFFICIENT WINDOW AND DOOR |
| | OPENINGS FOR ADEQUATE VENTILATION. PLEASE PROVIDE |
| | VENTILATIONS CALCULATIONS SHOWING TOTAL DOOR/WINDOW |
| | OPENABLE AREAS WITH RESPECT TO FLOOR AREA BEING |
| | VENTILATED IN ACCORDANCE WITH FBC R303.1 AND R303.2. |
| | |
| | 7. NOTE 1.3 ON SHEET 5 CALLS FOR A 10X10 TRANSFER W/ 8" |
| | DUCT BETWEEN THE FLORIDA ROMM AND "ADJACENT ROOM." THE |
| | LOCATION OF THIS TRANSFER AND WHICH ADJACENT ROOM IS |
| | NOT SHOWN ON PLANS. PLEASE CLARIFY THE LOCATION AND |
| | INTENT OF THIS DUCT IN ACCORDANCE WITH FBCR M1602.4. |
| | |
| | 8. THERE ARE DUCTS FROM THE PROPOSED NEW AHU WHICH ARE |
| | MISSING SIZES ON THE PLANS. PLEASE PROVIDE MISSING |
| | INFORMATION. AN AIR DISTRIBUTION SYSTEM SHALL BE |
| | DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED |
| | DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCR M1601.1 AND |
| | M1601.3. |
| | |