| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| | REVIEW COMMENTS IN WRITING. |
| | ALL COMMENTS RELATE TO SHEET 5 OF 8, UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} THERE IS AN ADDED AIR HANDLER LOCATED IN THE GARAGE, |
| | BUT NOT SHOWN IN THE LOAD CALCULATION. SUBMIT |
| | MANUFACTURERS SPECIFICATIONS FOR THAT SYSTEM. SHOW THE |
| | LOCATION OF THE A/C EQUIPMENT ON THE PLAN. ALSO SHOW |
| | COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14, |
| | RECEPTACLE PER 210.63. SEE SEE 220.83 EXISTING DWELLING |
| | UNIT |
| | THIS SECTION SHALL BE PERMITTED TO BE USED TO DETERMINE |
| | IF THE EXISTING SERVICE OR FEEDER IS OF SUFFICIENT |
| | CAPACITY TO SERVE ADDITIONAL LOADS. WHERE THE DWELLING |
| | UNIT IS SERVED BY A 120/240-VOLT OR 208Y/120-VOLT, |
| | 3-WIRE SERVICE, IT SHALL BE PERMISSIBLE TO CALCULATE |
| | THE TOTAL LOAD IN ACCORDANCE WITH 220.83(A) OR (B). |
| | |
| | 2} KITCHEN RECEPTACLES MUST COMPLY WITH 210.8(A)(6) |
| | GFI.SEE THAT PER THE LEGEND THEY ARE NOT. |
| | |
| | NOTE: THE NEW DINING ROOM AND NEW BREAKFAST ROOM MUST |
| | COMPLY WITH 210.52(B)(1). EVEN THOUGH EXISTING THEY |
| | MUST BE CHANGED TO SMALL APPLIANCE CIRCUITS. LOCATE THE |
| | RECEPTACLES IN THE DINING ROOM PER 210.52 AND MAKE A |
| | NOTE ON THE PLAN INDICATING COMPLIANCE WITH |
| | 210.52(B)(1) TO AVOID CONFUSION IN THE FIELD. |
| | |
| | 3} THE BATH FAN IS NOT INCLUDED ON THE ELECTRICAL |
| | PLAN.106.1.1 FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |