Plan Review Notes
Plan Review Notes For Permit 08110340
Permit Number 08110340
Review Stop M
Sequence Number 1
Notes
Date Text
2008-11-24 20:12:56REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 FBCR = FLORIDA BUILDING CODE, RESIDENTIAL
  
 1. NO INFORMATION WAS PROVIDED SHOWING HOW THIS
 APPLIANCE IS TO BE ATTACHED FOR WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING PER FBCR M1307.3. PROVIDE
 ENGINEERED DETAIL FOR CURB ATTACHMENT TO STRUCTURE AND
 RTU ATTACHMENT TO CURB.
  
 2. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL.
 CONDENSATE FROM ALL COOLING COILS OR EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE IN ACCORDANCE WITH FBCR M1411.3. ALSO,
 CONDENSATE LINES SHALL DISCHARGE AT LEAST 1 FOOT AWAY
 FROM THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND
 PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS IN ACCORDANCE
 WITH FBCR R320.6.
  
 3. PROVIDE AUXILIARY OR SECONDARY DRAIN PROTECTION IN
 ACCORDANCE WITH FBCR M1411.3.1.
  