2009-04-16 10:05:06** DENIED 2ND REVIEW**
  
  
  
 1) NOTE: TITLE BLOCKS ARE STILL MISSING THE REQUIRED
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER
 FS 471.023. THIS IS REQUIRED ON ALL SHEETS WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
 THE PRINTED LICENSE NUMBER OF THE ENGINEER WAS ADDED
 HOWEVER THIS IS NOT THE C OF A REQUIRED TO BE ON TITLE
 BLOCKS.
 FAC 61G15-23.002
  
 2) NOTE: CODES NOT STATED ON ELECTRICAL PLANS. THE
 PLANS SIMPLY STATE THE LATEST ADOPTED CODES WHICH IS
 NOT ACCEPTABLE. IF THE LATEST ADOPTED CODES WERE USED
 THIS WOULD PLACE THE ENTIRE PROJECT UNDER THE 2007 FBC
 WITH 2009 GLITCH AMENDMENTS.
 PLEASE STATE THE FOLLOWING AT A MINIMUM FOR THIS REVIEW
 TRADE ON ELECTRICAL PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 3) NOTE: AS NOTED ALSO ON PREVIOUS REVIEW THE PLANS
 CONTAIN CODE REFERENCES FROM THE 1996 NEC. THE 1996 NEC
 HAS NOT BEEN AN ADOPTED CODE FOR MANY CODE CYCLES. THIS
 HAS BEEN MORE THAN 10YEARS.
 PLEASE ADJUST. (SEE NOTES ON E-SHEET).
 250.122, NEC 2005
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  