Plan Review Notes
Plan Review Notes For Permit 08110332
Permit Number 08110332
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-18 11:35:00DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS A TITLE BLOCK SHALL BE USED ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND IF PRACTICING
 THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS. FAC 61G15-23.002(2) & FS
 471.025.
  
 2. SHT CV 1 OF 1 PLEASE INDICATE THE 2007 REVISIONS TO
 THE FBC-2004 IN THE BUILDING CODE SUMMARY. SECTION
 1-6.1.1.
  
 3. SHT A1.0 HOT & COLD WATER RISER DIAGRAM. AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DELETE FROM RISER.
 SECTION 604.9. WATER HAMMER ARRESTORS ARE REQUIRED FOR
 QUICK CLOSING VALVES ONLY. IF INSTALLED THEY SHALL BE
 INSTALLED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING. PDI-WH 201.
  
 4. SHTS K1, K2 & K3 THE PERSON DESINGING THE PLANS
 SHALL PRINT THEIR NAME ANS AFFIX THEIR SIGNATURE AS THE
 PERSON RESPONSIBLE FOR THE PLANS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  