| 2008-12-15 16:46:38 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002, FLORIDA STATUTES 471.023 AS THE TITLE |
| | BLOCKS ARE MISSING REQUIRED LICENSING. THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER IS MISSING AND REQUIRED. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE. |
| | |
| | 2) NOTE: THE FOLLOWING CODES SHALL BE STATED ON |
| | ELECTRICAL PLANS FOR THIS REVIEWER AT A MINIMUM. PLEASE |
| | BE SURE ALL CODES ON PLANS ARE UPDATED. FOR EXAMPLE |
| | THERE IS A CODE SECTION REFERENCE FROM THE 1996 |
| | NATIONAL ELECTRICAL CODE. THIS CODE HAS NOT BEEN |
| | ADOPTED IN MANY CODE CYCLES. |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON |
| | EXISTING MAIN PANEL PP IN WHICH THE NEW PANEL CBB IS |
| | BEING ADDED WITH NEW LOADS AS WELL AS EXISTING. |
| | PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%. |
| | 220,230.42,215.3 ETC |
| | |
| | FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY OF PLANS. |
| | |
| | 4) NOTE: PLEASE SUBMIT A RISER DIAGRAM FOR NEW FEEDERS |
| | ETC. |
| | 215.5, 310.16,240.4 ETC |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |