Plan Review Notes
Plan Review Notes For Permit 08110326
Permit Number 08110326
Review Stop E
Sequence Number 2
Notes
Date Text
2009-01-08 10:09:27 
  
  
 REVISION DENIED
  
 1} HAND DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE
 FOR RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3
 FBC AS AMENDED.
  
 2} THE ELECTRICAL PLAN SHEET MUST BE REVISED.THE
 REVISION SUBMITTED WAS HAND DRAWN ON THE "NEW ENCLOSED
 PATIO PLAN-SITE LAYOUT. THIS DOES NOT REVISE THE
 ELECTRICAL SHEET THAT WAS REVIEWED FOR THE PERMIT.
 106.1.3 FBC
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.
  
 4} TWO SETS OF PLANS ARE REQUIRED FOR REVIEW. ONE SET
 SUBMITTED WAS THE PERMIT SET, 2 REVISED SETS ARE
 REQUIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  