Plan Review Notes
Plan Review Notes For Permit 08110326
Permit Number 08110326
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-20 11:03:282004 FBC W/2007 AMENDMENTS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) REVISE THE CODE REFERENCED TO THE 2004 FBC WITH 2007
 AMENDMENTS.
  
 4) THE ENERGY CALCULATION FORMS ARE INCORRECT. THE
 CLIMATE ZONE IS 8, THE CONDITIONED FLOOR AREA IS 336
 SQFT, THE EXTERIOR WALL TYPE IS WOOD FRAME WITH R-11
 INSULATION AND THE SLAB ON GRADE IS NOT INSULATED. FBC
 13-600
  
 5) SPECIFY THE SIZE OF THE EXTERIOR DOOR ON THE PLANS.
 FBC R301.2.1
  
 6) INDICATE THE THE NAME AND CONTACT INFORMATION FOR
 THE PERSON RESPONSIBLE FOR THE DESIGN ON THE PLANS. FBC
 106.1.3* CITY AMENDMENTS
  
 7) SPECIFY THE SIZE OF THE FOOTINGS ON THE PLANS. THE
 MINIMUM FOOTING SIZE FOR MONOLITHIC SLABS IS 20" THICK
 AND 12" WIDE PER IBHS GUIDELINES FOR HURRICANE
 RESISTANT CONSTRUCTION. FBC R301.2.1.1
  
 8) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 9) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE. CONCRETE AND MASONRY FOUNDATION WALLS SHALL
 EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE.
  
 10) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 11) SPECIFY THE SPACING FOR THE 2 X 4 WALL STUDS ON THE
 PLANS. TABLE R602.2(3)
  
 12) THE WALL TO FOUNDATION ANCHORAGE REQUIRES 5/8"
 DIAMETER ANCHOR BOLTS AT 18" O.C. PER IBHS GUIDELINES
 FOR HURRICANE RESISTANT CONSTRUCTION AND FBC
 R301.2.1.1. PLEASE REVISE PLANS.
  
 13) THE EXTERIOR WALL HEADER ABOVE THE TWO 25 SH
 WINDOWS IS REQUIRED TO BE TWO 2 X 8 ON EDGE PER
 R602.2.8. REVISE WALL SECTION.
  
 14) THE PRODUCT APPROVALS FOR THE HARDI PLANK SIDING
 REQUIRES 5/8" PLYWOOD SHEATHING AND A WATERPROOFING PER
 FBC 2121.6.2.1 BEHIND IT. PLEASE REVISE WALL SECTION.
 ALSO SEE FBC R 703.2 FOR WATERPROOFING REQUIREMENTS OF
 15# FELT OR OTHER APPROVED WATERPROOFING.
  
 15) R803.2.3.1 SHEATHING FASTENINGS. WOOD STRUCTURAL
 PANEL SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH
 8D RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND
 6 INCHES ON CENTER AT INTERMEDIATE FRAMING. PLEASE
 CLARIFY THE ROOF SHEATHING FASTENING NOTES ON THE WALL
 SECTION.
  
 16) ROOF UNDERLAYMENT IS REQUIRED TO BE FASTENED AT 6"
 ON CENTER AT THE EDGES AND TWO (2) ROWS AT 12" O.C. IN
 THE FIELD PER RAS 117. PLEASE REVISE NOTES ON THE WALL
 SECTION.
  
 17) R905.2.2 SLOPE. ASPHALT SHINGLES SHALL ONLY BE USED
 ON ROOF SLOPES OF TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (2:12) OR GREATER. FOR ROOF SLOPES FROM TWO
 UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) UP TO FOUR
 UNITS VERTICAL IN 12 UNITS HORIZONTAL (4:12), TWO
 LAYERS OF UNDERLAYMENT COMPLYING WITH ASTM D 226 TYPE I
 OR TYPE II, ASTM D 4869 TYPE I OR TYPE II OR ASTM D
 6757 IS REQUIRED IN ACCORDANCE WITH SECTION R905.2.7.
 SPECIFY TWO LAYERS OF UNDERLAYMENT ON THE PLANS.
 R905.2.7
  
 18) THE PLANS SPECIFY SIMPSON H10 CONNECTORS AT THE
 EXTERIOR WALL OF THE EXISTING STRUCTURE WHERE THE NEW
 RAFTERS ARE ATTACHED TO THE EXISTING ONES. AN H10-2
 WILL BE REQUIRED AT THIS LOCATION WHERE THE RAFTERS ARE
 DOUBLED. PLEASE REVISE. R301.1
  
 19) TWO COPIES OF THE PRODUCT APPROVALS ARE REQUIRED.
 ONLY ONE COPY WAS SUBMITTED. FBC 106.1* CITY AMENDMENTS
  
 20) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS THAT WILL BE USED TO ATTACH
 THE TWO SINGLE HUNG WINDOWS. FAC RULE 9B-72
  
 21) GENERAL NOTE #4 ON THE ENCLOSED PATIO PLAN
 SPECIFIES IMPACT RATED WINDOWS. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED IS FOR NON-IMPACT RATED WINDOWS AND
 REQUIRE STORM PANELS. PLEASE SUBMIT PRODUCT APPROVALS
 FOR STORM PANELS OR FOR IMPACT RATED WINDOWS.
 R301.2.1.2
  
 22) THE VALUE FOR THE ADDITION SPECIFIED ON THE PLANS
 IS TOO LOW. IT HAS BEEN INCREASED TO $12,673.00 BASED
 ON MARSHALL AND SWIFT BUILDING VALUATION DATA.
 ADDITIONAL PERMIT FEES ARE OWED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]