2008-12-24 13:36:20BUILDING PLAN REVIEW
 PERMIT: 08110316
 ADD: 501 27TH STREET
 CONT: CHILD KAREN
 TEL: (561)310-8207
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12-24-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **NO RESPONSE NOT ADDRESSED**
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 RESIDENTIAL WITH THE 2007 SUPPLEMENTS. INDICATE THIS
 INFORMATION ON THE PLANS.
  
 **NO RESPONSE NOT ADDRESSED**
 3) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE
 DRAWINGS.
  
 **SHEET SK-2 IS MISSING THE ENGINEER SEAL FOR BOTH SETS
 OF PLANS. 61G15-23.002(2): EACH SHEET OF PLANS AND
 PRINTS SHALL BE SEALED SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. A TITLE
 BLOCK SHALL BE USED ON EACH SHEET CONTAINING THE
 PRINTED NAME, ADDRESS, AND LICENSE NUMBER OF THE
 ENGINEER.**
 4) 106.1.3* BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE UPON SUBSTANTIAL PAPER. CONSTRUCTION
 DOCUMENTS SHALL ALSO BE DIMENSIONED. THE DRAWINGS
 SUBMITTED DO NOT CLEARLY INDICATE WHAT WORK TO BE
 CONSTRUCTED THE PROPOSED LOCATION. SUBMIT DETAILED
 ARCHITECTURAL DRAWINGS TO CLEARLY INDICATE THE PROPOSED
 WORK. IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS
 STATE REGULATING PRACTICE OF ARCHITECTURE AS PROVIDED
 IN CHAPTER 481 AND 471 FLORIDA STATUTES PART 1, THEN HE
 OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE
 AND DATE TO THE DRAWINGS. FBC 106.1.
  
 ** THE DRAWINGS FAIL TO INDICATE HOW THE NEW 2X6 AND
 4X4 WOOD STUDS ARE ATTACHED TO THE BOTTOM
 PLATE/FLOOR**.
 5) R601.2 PROVIDE INFORMATION TO SHOW THE CONTINUOUS
 LOAD PATH BETWEEN THE FOUNDATIONS WALLS, AND ROOFS.
 PLEASE INDICATE THE TYPE OF FASTENING DEVICES USED FOR
 THE RAFTERS. THE ROOF TIE-DOWN SHALL BE IN COMPLIANCE
 WITH R802.2.9. INDICATE ALL HURRICANE STRAPS AND TIES
 USED, AND SHOW WHERE THEY ARE INSTALLED.
  
 6) OK
 7) OK.
  
 **NO RESPONSE NOT ADDRESSED**
 8) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]
  