| 2008-11-19 10:06:04 | ** FAILED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETE ELECTRICAL PLANS AND |
| | RISER FOR NEW ELECTRICAL SCOPE OF WORK INCLUDING THE |
| | ADDITION OF NEW ELECTRICAL PANEL INSTALLED AT THE |
| | GARAGE. |
| | SUBMIT ELECTRICAL PANEL SCHEDULE FOR NEW CIRCUITS |
| | SHOWING THE CONDUCTOR SIZES ALONG WITH THE OVER CURRENT |
| | PROTECTION ON EACH CIRCUIT. |
| | 215.5,230.70,230.71,230.72,310.16,250.50,240.4 ETC |
| | FLORIDA BUILDING CODE 105.1, 106.3.5.4 |
| | |
| | THERE ARE NO RECORDS OF ELECTRICAL PERMITS FOR THIS |
| | SCOPE OF WORK. PLEASE SUBMIT ELECTRICAL DRAWING/PLANS |
| | FOR THE NEW LIGHTING, SWITCHES ETC ON HOW CONTROLS. |
| | |
| | THE PERMIT APPLICATION SUBMITTED WILL NEED TO HAVE A |
| | SIGN ON FOR THE ELECTRICAL PERMIT REQUIRED. THIS WOULD |
| | BE REQUIRED TO BE DONE IN PERSON BEFORE PLANS CAN BE |
| | RESUBMITTED. |
| | |
| | 2) NOTE: PLEASE SEE 210.52G, 210.8A FOR GARAGE |
| | RECEPTACLE REQUIRED. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |