| Plan Review Notes For Permit 08110310 |
| Permit Number |
08110310 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-03 15:02:01 | ROSARIAN ACADEMY | | | 807 NORTH FLAGLER DRIVE | | | INSTALL FIRE ALARM SYSTEM | | | | | | 1. PLEASE DECLARE ON THE PLANS WHAT THE VOICE | | | EVACUATION MESSAGE WILL ADVISE OCCUPANTS TO DO IN THE | | | EVENT OF AN EMERGENCY. PLEASE INDICATE THE LOCATIONS OF | | | ANY ALERT TONES IN THE VOICE EVACUATION MESSAGE | | | PORTION. | | | | | | 2. THE ENTIRE FIRE ALARM SYSTEM SHALL BE INSTALLED IN | | | ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE ALARM CODE | | | AND NFPA 60, THE NATIONAL ELECTRICAL CODE AND OTHER | | | APPROPRIATE STANDARDS. | | | | | | 3. ON PAGE 8 IT INDICATES THAT DUCT SMOKE DETECTORS | | | WHEN ACTIVATED WILL CAUSE A SUPERVISORY SIGNAL. DUCT | | | DETECTORS WHEN ACTIVATED SHALL CAUSE A FIRE GENERAL | | | ALARM CONDITION. | | | | | | 4. ENTIRE INSTALLATION IS SUBJECT TO FIELD INSPECTION | | | AND APPROVAL. WHEN COMPLETED THE ENTIRE SHALL BE | | | INSPECTED, TESTED, AND APPROVED. | | | | | | 5. THE FIRE ALARM SHALL IDENTIFY AND TRANSMIT THE | | | FOLLOWING SIGNALS TO THE MONITORING COMPANY; GENERAL | | | ALARM, WATERFLOW, SUPERVISORY, AND TROUBLE. | | | | | | 6. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL | | | LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION | | | SERVICE. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|