 SHEET 7 OF 40:
 1. KEY COLORING ON THIS SHEET DOES NOT MATCH 6 OF 40.
 CHANGE COLORING TO REDUCE CONFUSION.
 2. RAIN SHELTER IS NOT LOCATED AS SHOWN. IT IS
 APPROXIMATELY 87' NORTH AND 157' WEST OF CART PATH.
 SHEET 9 OF 40:
 1. SINCE YOU HAVE SHOWN THE PROPERTY LINE ON THIS SET
 OF DRAWINGS THE WORK SEEMS TO BE EXTENDING OFF THE
 PROPERTY. CHECK WITH THE PROJECT MANAGER V. NOEL
 (561-494-1096) FOR THE PROPER PROPERTY LINE. IF IT IS
 AS SHOWN THEN REDUCE THE "PERIMETER ZONE" WORK TO A
 POINT IT IS INSIDE CITY PROPERTY.
 SHEET 12, 14, 16, AND 18 OF 40:
 1. SEE NOTE ON 21 OF 40, THE OUTCOME OF HOW THE PUMP
 STATION IS DESIGNED WILL CHANGE THIS NOTE.
 2. THE NOTE STATES: "TO BE DISCONNECTED, OWNER TO
 DISPOSE OF PUMPS." THE DEMOLITION SHEET (5 OF 40) DOES
 NOT STATE THAT THE PUMP HOUSE, CONTROL PANEL, ELECTRIC
 LINES, OR CONCRETE PAD FOR THE EXISTING PUMPS ARE TO BE
 REMOVED. ARE THEY TO BE REMOVED, CAPPED OFF?
 SHEET 21 OF 40:
 1. I DO NOT HAVE THE PREVIOUS PLAN TO COMPARE TO THIS
 PLAN, BUT THIS PLAN SHOWS THE FINISHED FLOOR ELEVATION
 AS 15'-9". THE PLAN THEN GOES ON TO STATE THAT THE PUMP
 SET EXTENDS DOWN FROM THIS ELEVATION 11', WHICH PLACES
 IT AT ELEVATION 4'-9". THE ELEVATION ON THE INVERT OF
 THE INTAKE PIPE IS 1'-0". WHICH MEANS THAT THE BOTTOM
 OF THE WET WELL IS 2'-9" HIGHER THAN THE INTAKE PIPE.
 IT APPEARS THAT THE BOTTOM OF THE WETWELL SHOULD BE
 AROUND MINUS 2'-0" AND THAT THE PUMP SET SHOULD BOTTOM
 OUT AT AROUND MINUS 1'-0" OR 17' LONG. THIS WOULD MAKE
 THE WETWELL APPROXIMATELY 18' DEEP, WHICH WOULD AFFECT
 THE NOTES ON SHEETS 12,14, 16, AND 18 OF 40.
 2. INFORMATIONAL NOTE: SHEETS 12, 14, 16, AND 18 OF 40
 ALL HAVE A NOTE THAT STATE THE WETWELL SHALL BE "60"
 CONCRETE". HUGGER BANDS WILL NOT WORK WITH PVC PIPE,
 WHICH IS THE MATERIAL THAT HAS BEEN SUBMITTED WITH THIS
 SET OF PLANS (J-M PIPE, 24" CLASS 235 PSI, DR18, OR
 CLASS 165 PSI DR26), NEITHER CLASS WAS CHOSEN, BUT BOTH
 ARE PVC AND REQUIRE A DIFFERENT TYPE OF ADAPTER THAN
 THE "HUGGER BAND" THAT IS SHOWN ON THE PLAN. THE
 PREVIOUS REVIEWER WAS INTERESTED TO SEE WHAT MATERIAL
 WAS TO BE USED (IT DOES NOT STATE ON THIS SHEET, WHICH
 IT SHOULD). IT DOES GIVE A LIST OF PIPE MATERIALS THAT
 CAN BE USED ON SHEETS 12, 14, 16, AND 18 OF 40. THE
 MATERIALS DO NOT NEED TO BE SUBMITTED AT THIS TIME, TO
 CONSTRUCTION SERVICES, BUT LATER TO THE PROJECT MANAGER
 AT ENGINEERING SERVICES. TOWARDS THAT END ONE OF THE
 FOLLOWING ADAPTERS WILL BE REQUIRED TO ADAPT TO THE
 WETWELL FOR PVC;
 PVC MANHOLE TO PIPE ADAPTERS:
 USED TO SEAL THE PIPE TO THE MANHOLE. ALL ADAPTERS WILL
 BE MADE TO FIT PVC, SDR-26 PIPE. ADAPTERS FOR USE WITH
 ALL NEW CONSTRUCTION. PVC ADAPTERS SHALL HAVE DOUBLE
 GASKETED BELL, WITH SANDCOATING CAST INTO THE OUTSIDE
 TO ALLOW FOR ADHERENCE TO THE CONCRETE SEAL.
  HARCO - THE HARRINGTON CORP., P.O. BOX 10335,
 LYNCHBURG, VA 24306
 FLOW CONTROL
 OTHER MANHOLE TO PIPE ADAPTERS:
 USED TO SEAL THE PIPE TO THE MANHOLE. ALL ADAPTERS WILL
 BE MADE TO FIT PVC, SDR-26 PIPE. ADAPTERS FOR USE WITH
 ALL NEW CONSTRUCTION. ADAPTERS SHALL HAVE STAINLESS
 STEEL RING SEALS TO SEAL THE ADAPTER TO THE PIPE AND TO
 THE MANHOLE IF THEY ARE NOT POURED IN PLACE.
  PRESS SEAL GASKET CORPORATION
 PRESS-BOOT
 U.S. PRECAST MANHOLE W/HDPE LINER CAST-IN BOOT TO
 SLEEVE CONNECTION
 U.S. PRECAST HDPE LINER SYSTEM "TURN BACK" JOINT
 INSTALLED AFTER CAST
 3. I AM NOT A STRUCTURAL ENGINEER, BUT I WOULD THINK
 THAT THERE NEEDS TO BE SOME STEEL IN THE CONCRETE SLAB,
 AND THE SLAB NEEDS TO BE ON TOP OF THE WETWELL.
 4. SHEET 12 OF 40 HAS A NOTE THAT STATES: "WATER LEVEL
 NOVEMBER 18TH 1974 ELEV. 8.60', LOWEST ANTICIPATED
 WATER ELEV. 2.85'. SO WHY IS THERE A COMMENT THAT THE
 ELEVATION OF THE WATER (8.60') IS UNCONFIRMED ON THIS
 SHEET?
 5. SINCE THE WATER TABLE IS APPROXIMATELY 8.60' AND THE
 WETWELL IS AS DEEP AS IT MAY END UP, A NOTE NEEDS TO BE
 ADDED STATING THAT THE WETWELL NEEDS TO BE DESIGNED BY
 A PE AND CERTIFIED THAT IT WILL NOT FLOAT.
 34 OF 40:
 1. ADD TO ALL DETAILS THE USE OF FILTER FABRIC AROUND
 THE TOPS, SIDES AND BOTTOMS OF ALL OF THE GRAVEL.
 2. CHANGE THE NOTES "1/4 TO 3/4" WASHED GRAVEL TO 3/4"
 WASHED ROCK.
 35 OF 40:
 1. ADD TO DETAIL THE USE OF FILTER FABRIC AROUND THE
 TOPS, SIDES AND BOTTOMS OF ALL OF THE GRAVEL.
 2. CHANGE THE NOTES "1/4 TO 3/4" WASHED GRAVEL TO 3/4"
 WASHED ROCK.
 3. WHERE ARE THE CHANNEL DRAINS GOING TO BE PLACED THAT
 ARE SHOWN IN THIS DETAIL? STATE THERE SPECIFIC
 LOCATION.
 4. WATER FOUNTAIN SHELTER UTILITY PLAN IS CONFUSING.
 ADD TO THE END OF THE TITLE "(SEE SHEET F2, 28 OF 40)".
 5. I DO NOT KNOW HOW BUT CHANGE THE NOTE CONCERNING
 ABANDONING THE ELECTRIC AND WATER LINES, IT APPEARS YOU
 WANT TO CUT THEM OFF FROM THE BATHROOM. I WOULD THINK
 THAT YOU WOULD NEED THE WATER LINE FOR THE WATER
 FOUNTAIN.
  