2009-04-13 12:10:19BUILDING PLAN REVIEW
 PERMIT: 08110304
 ADD: 7001 PARKER AVE.
 CONT: WEITZ GOLF INTERNATIONAL LLC
 TEL: (561)799-7800
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW AS PERMIT APPLICATION
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME
 REVIEW) AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE
 2007 FBC BUILDING WITH THE 2009 SUPPLEMENTS.
  
 1C) PLANS SUBMITTED TO THE CITY FOR REVIEW ARE NOT
 SIGNED NOR SEALED ,
 2) SHEETS PS1 & PS2 INDICATE THE INSTALLATION OF A
 FIBERGLASS COMPOSITE PUMP STATION:
  
 2A) MISSING INFORMATION,110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING &
 FOR CERTIFICATE OF OCCUPANCY:
 2A)(1) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 2A)(2)) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 2A)(3)) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER
 6, TABLE 601.
  
 2B) SHEET PS2, NOTE 5.2.1.A SHELTERS NEEDING TO BE
 RATED FOR 140MPH, 3 SECOND GUST NEED PLANS TO BE SIGNED
 AND SEALED BY A FLORIDA P.E.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2C) DESCREPANCY IN PLANS PS1 IT APPEARS THERE IS A
 I-BEAM FLOOR SYSTEM WHERE AS PS 2 DETAIL INDICATES
 FLOOR SLAB SYSTEM, NOR IS THERE STRUCTURAL INFORMATION
 ON THE PIT OR WELL WALL AND FLOOR SYSTEMS. PS2 OPTIONS
 INDICATE FLOOR SYSTEM FIBERGLASS, WOOD, ALUMINUM OR
 STEEL.
 106.1.2 ADDITIONAL INFORMATION REQUIRED/ 1609.6.2.1.
  
 2D) WIND DESIGN INFORMATION MISSING:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 3) COMPLIED.
  
 4) SHEET 37, RAIN SHELTERS:
  
 4A) COMPLIED.
  
 4B) COMPLIED.
  
 4C)COMPLIED.
  
 4D) COMPLIED.
  
 4E) SECOND REQUEST, THE RAIN SHELTER ROOF PURLINS ARE
 INDICATED TO 1X4 AT 2'-0" O.C., PLEASE IDENTIFY THE
 TYPE OF METAL ROOFING TO BE USED. PLANS INDICATE A
 METAL STANDING SEAM SYSTEM, IS THIS A STRUCTURAL
 ROOFING SYSTEM NOT REQUIRING SHEATHIN BUT STRUCTURAL
 2X4 PURLINS 2308.10.5 OR WILL IT BE A ARCHITECURAL
 SYSTEM REQUIRING A SOLID OR CLOSELY FITTED DECK
 (1507.4.1).
  
 4F) SECOND REQUEST THE WATER FOUNTAIN SHELTER USES 1X4
 PURLINS AT 1'-0" O.C., PLEASE IDENTIFY THE TYPE OF
 METAL ROOFING TO BE USED. PLANS INDICATE A METAL
 STANDING SEAM SYSTEM, IS THIS A STRUCTURAL ROOFING
 SYSTEM NOT REQUIRING SHEATHIN BUT STRUCTURAL 2X4
 PURLINS 2308.10.5 OR WILL IT BE A ARCHITECURAL SYSTEM
 REQUIRING A SOLID OR CLOSELY FITTED DECK (1507.4.1).
  
 4G) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
  
 4G)(1) TRUSS ANCHORS, CLIPS
  
 4G)(2) ROOF COVERINGS: STANDING METAL SEAM
  
 4H) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4I) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved