| 2008-11-20 10:54:17 | |
| | |
| | |
| | ** FAILED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: PLANS ONLY SUBMITTED FOR * PLAN REVIEW * ONLY. |
| | PLEASE KNOW ONCE PLANS ARE FOUND TO BE CODE COMPLIANCE |
| | FOR ISSUANCE THE REVIEW WILL STILL REMAIN IN A FAILED |
| | STATUS UNTIL PERMIT APPLICATION BY A LICENSED |
| | CONTRACTOR HAS BEEN SUBMITTED. REVIEW OF CURRENT |
| | LICENSING OF CONTRACTOR(S), DESIGNER(S) AND FIRM WILL |
| | BE DONE AT THIS TIME. |
| | PLEASE ALSO KNOW THAT IN ORDER TO LOCK IN REVIEW AND |
| | DESIGN UNDER CURRENT ADOPTED CODE(S) PERMIT APPLICATION |
| | MUST BE MADE. THERE IS NO SCHEDULE OF CODE CHANGE UNTIL |
| | MARCH 1ST, 2009. |
| | ** IF THERE ARE ANY QUESTIONS ON THIS PROCESS PLEASE |
| | CONTACT THIS OFFICE/REVIEWER/. |
| | |
| | 2) NOTE: ALL PLANS ARE REQUIRED UNDER FLORIDA |
| | ADMINISTRATIVE CODE TO CONTAIN THE TITLE BLOCKS FOR |
| | ARCHITECT, ARCHITECTURAL FIRMS, AND ENGINEERING FIRMS |
| | ETC. THESE TITLE BLOCKS ARE REQUIRED TO INCLUDE |
| | INFORMATION AND ADDRESS OF PROJECT. |
| | THEY ARE REQUIRED TO CONTAIN ALL LICENSING INFORMATION |
| | FOR THE FIRMS, PRINTED LICENSE NUMBER, ADDRESS, AND |
| | PHONE NUMBER ETC. |
| | PLEASE SEE FAC 61G1-16.004 FOR ARCHITECT, ARCHITECTURAL |
| | FIRMS. |
| | PLEASE SEE FAC 61G15-23.002 FOR ENGINEERS AND |
| | ENGINEERING FIRMS. |
| | |
| | |
| | ** PLEASE KNOW THAT A CERTIFICATE OF AUTHORIZATION |
| | LICENSE NUMBER IS REQUIRED FOR ALL ARCHITECTURAL FIRMS |
| | INCLUDING LANDSCAPING ARCHITECTURAL FIRMS PER FLORIDA |
| | STATUTES 481.219. |
| | |
| | ** PLEASE KNOW THAT A CERTIFICATE OF AUTHORIZATION |
| | LICENSE NUMBER IS REQUIRED FOR ALL ENGINEERING FIRMS |
| | PER FS 471.023 |
| | |
| | ** THESE COMMENTS ARE FOR ALL TRADES AND ALL SHEETS |
| | WHETHER OR NOT COMMENTS ARE MADE BY OTHER TRADE |
| | REVIEWS. THESE ARE NOT NEW REQUIREMENTS IN FACT THEY |
| | HAVE BEEN AROUND SINCE LATE NINETEEN SEVENTIES. |
| | IF THERE ARE ANY QUESTIONS ON REQUIREMENTS PLEASE |
| | CONTACT THIS OFFICE/REVIEW OR DEPARTMENT OF BUSINESS |
| | AND PROFESSIONAL REGULATION FOR THE STATE OF FLORIDA. |
| | |
| | 3) NOTE: SOME SHEETS IN SETS ARE NOT SIGNED, DATED OR |
| | SEALED BY ANY DESIGN PROFESSIONAL. PLEASE KNOW ALL |
| | PLANS SHALL CONTAIN PERSON RESPONSIBLE FOR DESIGN EVEN |
| | WHEN MEETING EXCEPTIONS TO FS 481.229 AND 471.003. |
| | THIS PROJECT DOES NOT MEET EXCEPTIONS AND THEREFORE |
| | MUST BE COMPLETED BY THE LICENSE DESIGNER OF RECORD. |
| | 481.221,471.025. |
| | |
| | 4) NOTE: PLEASE SUBMIT ELECTRICAL PLANS AND DETAILS FOR |
| | ELECTRICAL SCOPE OF WORK FOR SHELTERS ETC. |
| | PLEASE SHOW CONDUCTORS, OVER CURRENT PROTECTION, |
| | CIRCUITING ETC. |
| | PLEASE BE SURE TO SEE 2005 NEC, 2004 FBC FOR MINIMUM |
| | DESIGN FOR COMPLIANCE. |
| | IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |