Plan Review Notes
Plan Review Notes For Permit 08110304
Permit Number 08110304
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-20 10:54:17 
  
  
 ** FAILED REVIEW **
  
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR * PLAN REVIEW * ONLY.
 PLEASE KNOW ONCE PLANS ARE FOUND TO BE CODE COMPLIANCE
 FOR ISSUANCE THE REVIEW WILL STILL REMAIN IN A FAILED
 STATUS UNTIL PERMIT APPLICATION BY A LICENSED
 CONTRACTOR HAS BEEN SUBMITTED. REVIEW OF CURRENT
 LICENSING OF CONTRACTOR(S), DESIGNER(S) AND FIRM WILL
 BE DONE AT THIS TIME.
 PLEASE ALSO KNOW THAT IN ORDER TO LOCK IN REVIEW AND
 DESIGN UNDER CURRENT ADOPTED CODE(S) PERMIT APPLICATION
 MUST BE MADE. THERE IS NO SCHEDULE OF CODE CHANGE UNTIL
 MARCH 1ST, 2009.
 ** IF THERE ARE ANY QUESTIONS ON THIS PROCESS PLEASE
 CONTACT THIS OFFICE/REVIEWER/.
  
 2) NOTE: ALL PLANS ARE REQUIRED UNDER FLORIDA
 ADMINISTRATIVE CODE TO CONTAIN THE TITLE BLOCKS FOR
 ARCHITECT, ARCHITECTURAL FIRMS, AND ENGINEERING FIRMS
 ETC. THESE TITLE BLOCKS ARE REQUIRED TO INCLUDE
 INFORMATION AND ADDRESS OF PROJECT.
 THEY ARE REQUIRED TO CONTAIN ALL LICENSING INFORMATION
 FOR THE FIRMS, PRINTED LICENSE NUMBER, ADDRESS, AND
 PHONE NUMBER ETC.
 PLEASE SEE FAC 61G1-16.004 FOR ARCHITECT, ARCHITECTURAL
 FIRMS.
 PLEASE SEE FAC 61G15-23.002 FOR ENGINEERS AND
 ENGINEERING FIRMS.
  
  
 ** PLEASE KNOW THAT A CERTIFICATE OF AUTHORIZATION
 LICENSE NUMBER IS REQUIRED FOR ALL ARCHITECTURAL FIRMS
 INCLUDING LANDSCAPING ARCHITECTURAL FIRMS PER FLORIDA
 STATUTES 481.219.
  
 ** PLEASE KNOW THAT A CERTIFICATE OF AUTHORIZATION
 LICENSE NUMBER IS REQUIRED FOR ALL ENGINEERING FIRMS
 PER FS 471.023
  
 ** THESE COMMENTS ARE FOR ALL TRADES AND ALL SHEETS
 WHETHER OR NOT COMMENTS ARE MADE BY OTHER TRADE
 REVIEWS. THESE ARE NOT NEW REQUIREMENTS IN FACT THEY
 HAVE BEEN AROUND SINCE LATE NINETEEN SEVENTIES.
 IF THERE ARE ANY QUESTIONS ON REQUIREMENTS PLEASE
 CONTACT THIS OFFICE/REVIEW OR DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION FOR THE STATE OF FLORIDA.
  
 3) NOTE: SOME SHEETS IN SETS ARE NOT SIGNED, DATED OR
 SEALED BY ANY DESIGN PROFESSIONAL. PLEASE KNOW ALL
 PLANS SHALL CONTAIN PERSON RESPONSIBLE FOR DESIGN EVEN
 WHEN MEETING EXCEPTIONS TO FS 481.229 AND 471.003.
 THIS PROJECT DOES NOT MEET EXCEPTIONS AND THEREFORE
 MUST BE COMPLETED BY THE LICENSE DESIGNER OF RECORD.
 481.221,471.025.
  
 4) NOTE: PLEASE SUBMIT ELECTRICAL PLANS AND DETAILS FOR
 ELECTRICAL SCOPE OF WORK FOR SHELTERS ETC.
 PLEASE SHOW CONDUCTORS, OVER CURRENT PROTECTION,
 CIRCUITING ETC.
 PLEASE BE SURE TO SEE 2005 NEC, 2004 FBC FOR MINIMUM
 DESIGN FOR COMPLIANCE.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  