Plan Review Notes For Permit 08110304
Permit Number 08110304
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-24 09:52:45BUILDING PLAN REVIEW
 PERMIT: 08110304
 ADD: 7001 PARKER AVE.
 CONT: MAJOR WORKING DRAWING/ VINCENT NOEL
 TEL: (561)622-7288
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 1C) PLANS SUBMITTED TO THE CITY FOR REVIEW ARE NOT
 SIGNED NOR SEALED ,
 2) SHEETS PS1 & PS2 INDICATE THE INSTALLATION OF A
 FIBERGLASS COMPOSITE PUMP STATION:
  
 2A) MISSING INFORMATION,110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING &
 FOR CERTIFICATE OF OCCUPANCY:
 2A)(1) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 2A)(2)) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 2A)(3)) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER
 6, TABLE 601.
  
 2B) SHEET PS2, NOTE 5.2.1.A SHELTERS NEEDING TO BE
 RATED FOR 140MPH, 3 SECOND GUST NEED PLANS TO BE SIGNED
 AND SEALED BY A FLORIDA P.E.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2C) DESCREPANCY IN PLANS PS1 IT APPEARS THERE IS A
 I-BEAM FLOOR SYSTEM WHERE AS PS 2 DETAIL INDICATES
 FLOOR SLAB SYSTEM, NOR IS THERE STRUCTURAL INFORMATION
 ON THE PIT OR WELL WALL AND FLOOR SYSTEMS.
 106.1.2 ADDITIONAL INFORMATION REQUIRED/ 1609.6.2.1.
  
 2D) WIND DESIGN INFORMATION MISSING:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 3) SHEET OV & L2 INDICATE THE PUMP STATION OPERATES IN
 A HIGHLY CORROSIVE ENVIROMENT, WHAT CAUSES THE HIGHLY
 CORROSIVE ENVIROMENT, IS THERE CORROSIVE CHEMICALS TO
 BE STORED THERE OR INTRODUCED INTO THE IRRIGATION
 SYSTEM WITHIN THIS STRUCTURE? 106.1.2 ADDITIONAL
 INFORMATION REQUIRED, PLEASE SEE SECTION 307.6 FOR H-4
 TYPE OCCUPANCY AND TABLE 307.7(1).
  
 4) SHEET 37, RAIN SHELTERS:
  
 4A) MISSING INFORMATION,110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING &
 FOR CERTIFICATE OF OCCUPANCY:
 4A)(1) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 4A)(2)) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 4A)(3)) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER
 6, TABLE 601.
  
 4B) 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR
 THE SELECTION OF EXTERIOR COMPONENTS AND CLADDING
 MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 4C) PLANS CALL FOR 2X8 RAFTERS, PLEASE SUPPLY THE
 SPECIES OF WOOD, GRADE, DEFLECTION AND SPANS 2308.10.3.
  
 4D) PLANS ALSO CALL FOR A 2X8 RIDGE, PLEASE SEE
 2308.10.4 THE RIDGE SHALL BE NOT LESS IN DEPTH THAN THE
 CUT END OF THE RAFTER, NORMALLY ONE SIZE LARGER (2X10).
  
 4E) THE RAIN SHELTER ROOF PURLINS ARE INDICATED TO 1X4
 AT 2'-0" O.C., PLEASE IDENTIFY THE TYPE OF METAL
 ROOFING TO BE USED. PLANS INDICATE A METAL STANDING
 SEAM SYSTEM, IS THIS A STRUCTURAL ROOFING SYSTEM NOT
 REQUIRING SHEATHIN BUT STRUCTURAL 2X4 PURLINS 2308.10.5
 OR WILL IT BE A ARCHITECURAL SYSTEM REQUIRING A SOLID
 OR CLOSELY FITTED DECK (1507.4.1).
  
 4F) THE WATER FOUNTAIN SHELTER USES 1X4 PURLINS AT
 1'-0" O.C., PLEASE IDENTIFY THE TYPE OF METAL ROOFING
 TO BE USED. PLANS INDICATE A METAL STANDING SEAM
 SYSTEM, IS THIS A STRUCTURAL ROOFING SYSTEM NOT
 REQUIRING SHEATHIN BUT STRUCTURAL 2X4 PURLINS 2308.10.5
 OR WILL IT BE A ARCHITECURAL SYSTEM REQUIRING A SOLID
 OR CLOSELY FITTED DECK (1507.4.1).
  
 4G) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
  
 4G)(1) TRUSS ANCHORS, CLIPS
  
 4G)(2) ROOF COVERINGS
  
 4H) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4I) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.