Plan Review Notes
Plan Review Notes For Permit 08110285
Permit Number 08110285
Review Stop B
Sequence Number 3
Notes
Date Text
2008-12-16 08:48:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE THE INSTALLATINO SCHEDULE AND SHEET 10 OF THE
 PRODUCT APPROVAL. YOU'VE SPECIFIED SHUTTER MOUNTING
 TYPE 3 FOR THE BOTTOM CONNECTION, HAVE HIGHLIGHTED THAT
 ON THE PRODUCT APPROVAL, HIGHLIGHTED 10" SPACING, BUT
 ON THE INSTALLATION SCHEDULE SPECIFIED 12" SPACING. IT
 APPEARS THAT IT SHOULD BE 10". PLEASE REVISE EITHER THE
 SHUTTER CONNECTION MOUNTING TYPE OR THE ANCHOR SPACING.
  
 2. PLEASE INCLUDE OPENING NUMBERS TO CORRELATE WITH THE
 FLOOR PLAN. IN THE COLUMN FOR OPENING NUMBER, THE
 OPENING WIDTH HAS BEEN SPECIFIED. AS THE INSTALLATION
 SCHEDULE MUST BE REVISED DUE TO COMMENT 1, PLEASE
 REVISE THIS ALSO.
  