| Plan Review Notes For Permit 08110285 |
| Permit Number |
08110285 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-12-16 08:48:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. SEE THE INSTALLATINO SCHEDULE AND SHEET 10 OF THE | | | PRODUCT APPROVAL. YOU'VE SPECIFIED SHUTTER MOUNTING | | | TYPE 3 FOR THE BOTTOM CONNECTION, HAVE HIGHLIGHTED THAT | | | ON THE PRODUCT APPROVAL, HIGHLIGHTED 10" SPACING, BUT | | | ON THE INSTALLATION SCHEDULE SPECIFIED 12" SPACING. IT | | | APPEARS THAT IT SHOULD BE 10". PLEASE REVISE EITHER THE | | | SHUTTER CONNECTION MOUNTING TYPE OR THE ANCHOR SPACING. | | | | | | 2. PLEASE INCLUDE OPENING NUMBERS TO CORRELATE WITH THE | | | FLOOR PLAN. IN THE COLUMN FOR OPENING NUMBER, THE | | | OPENING WIDTH HAS BEEN SPECIFIED. AS THE INSTALLATION | | | SCHEDULE MUST BE REVISED DUE TO COMMENT 1, PLEASE | | | REVISE THIS ALSO. | | | |
|