Plan Review Notes
Plan Review Notes For Permit 08110283
Permit Number 08110283
Review Stop P
Sequence Number 1
Notes
Date Text
2009-01-20 11:36:44DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1 (ADMIN)
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****PLAN REVIEW ONLY****
  
 1. ALL SHEETS WITH G.M. REMBOWSKI ARCHITECT INC. THE
 BUSINESS LICENSE, (CERTIFICATE OF AUTHORIZATION), IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(2) & FS 481.219, 481.2055.
  
 2. SHT A00A BUILDING CODES TO INCLUDE THE 2007
 REVISIONS. PLEASE BE ADVISED, SINCE THE PLANS HAVE BEEN
 SUBMITTED FOR PLAN REVIEW ONLY AT THIS TIME, IF THE
 PERMIT IS NOT APPLIED FOR PRIOR TO MARCH 1. 2009 THE
 PROJECT SHALL BE DESIGNED TO THE THE REQUIREMENTS OF
 THE FBC-2007 CODE.
  
 3. SHT A00A FBC CHAPTER 11 ACCESSIBILITY INDICATES 7
 GUESTROOMS WITH MOBILITY FEATURES. PER THE TABLE FOR
 SECTION 11-9.1.2, FIVE ARE REQUIRED WITH AN ADDITIONAL
 2 SLEEPING ROOMS WITH ROLL IN SHOWERS WHICH IS
 INDICATED ON THE PLANS. BUT PER THE FLORIDA SPECIFIC
 AREA OF SECTION 11-9.1.2, FIVE PERCENT OF THE
 GUESTROOMS, MINUS THE NUMBER OF ACCESSIBLE GUESTROOM
 REQUIRED BY THE TABLE, (5), SHALL PROVIDE ADDITIONAL
 SPECIAL ACCESSIBILITY FEATURES OF SECTION 11-9.2.3.
 THIS NUMBER COMES OUT TO 3 UNITS, (150 X .05 = 7.5
 MINUS 5 = 2.5 ROUNDED UP TO 3 UNITS). PLEASE INDICATE
 WHICH 3 ROOMS ARE COMPLIANT WITH THIS REQUIREMENT.
 SECTION 106.1.2.
  
 4. SHT A100 GUESTROOM SUMMARY SHOWS DOUBLE QUEEN,
 DOUBLE QUEEN SUITE, NARROW KING, KING & KING SUITE
 CLASSES OF ACCOMMODATIONS. THE ONLY ACCESSIBLE UNITS
 SHOWN ARE THE DOUBLE QUEEN AND THE KING UNITS. PER
 SECTION 11-9.1.4 IN ORDER TO PROVIDE PERSONS WITH
 DISABILITIES A RANGE OF OPTIONS EQUIVALENT TO THOSE
 AVAILABLE TO OTHER PERSONS SERVED BY THE FACILITY,
 SLEEPING ROOMS AND SUITES REQUIRED TO ACCESSIBLE BY
 SECTION 11-9.1.2 SHALL BE DISPERSED AMONG THE VARIOUS
 CLASSES OF SLEEPING ACCOMMODATIONS AVAILABLE TO PATRONS
 OF THE PLACE OF TRANSIENT LODGING. NO ACCESSIBLE UNITS
 ARE INDICATED FOR THE DOUBLE QUEEN SUITE, THE NARROW
 KING AND THE KING SUITES. PLEASE INDICATE HOW
 COMPLIANCE WITH SECTION 11-9.1.4 WILL BE ADDRESSED.
  
 5. SHT A100 SHOWS 10 ACCESSIBLE ROOMS BUT SHT A00A FBC
 CHAPTER 11 ACCESSIBILITY INDICATES GUESTROOMS WITH
 MOBILITY FEATURES TOTALS 7 (2 TO HAVE ROLL-IN SHOWERS),
 AS WELL AS 12 GUESTROOMS WITH COMMUNICATION FEATURES.
 PLEASE CLARIFY & CORRELATE. SECTIONS 11-9.1.2 &
 11-9.1.3..
  
 6. SHT A100 FOOD PREP AREA MAY REQUIRE A GREASE
 INTERCEPTOR. PLEASE CONTACT THE UTILITY DEPT.,
 INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT HOLLY MCGRATH, LABORATORY SUPERVISOR AT
 HER OFFICE, (561) 822-2271, OR BY FAX (561) 822-2279.
 OR BY E-MAIL [email protected]. INTERCEPTOR SIZE WILL BE
 DETERMINED AND A WRITTEN DETERMINATION WILL BE
 SUBMITTED WITH RESPONSE COMMENTS. ARTICLE III SECTION
 90-124(7).
  
 7. SHTS A102 & A103 SHOWS ACCESSIBLE KING SUITE WHICH
 DOES NOT REFLECT THE GUESTROOM SUMMARY ON SHT A100
 WHICH INDICATES ACCESSIBLE KING UNIT. PLEASE CLARIFY &
 CORRELATE. SECTIONS 106.1.1 & 11-9.1.4.
  
 8. SHTS A102 & A103 ROOMS FOR PERSONS WITH HEARING
 IMPAIRMENTS SHALL BE IN ADDITION TO ROOMS THAT ARE
 ACCESSIBLE. SECTION 11-9-1.3. PLEASE INDICATE THE
 LOCATION OF THESE UNITS.
  
 9. SHTS A104 & L5/6 ROOF INFORMATION DOES NOT MATCH.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 1101.1 AND TABLE
 1106.3.
  
 10. SHT A104 NO SECONDARY ROOF DRAINAGE IS SHOWN.
 SECTION 1107. PLEASE INDICATE LOCATION OF REQUIRED
 SECOND ROOF DRAINAGE.
  
 11. A104 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF/DECK DRAINS. SHOW THE AREA BEING DRAIN
 FOR EACH DRAIN AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH AREA TO
 VERIFY DRAIN & RWL SIZES. SECTIONS 106.1.2, 1106 & 1107
 & TABLES 1106.3 & 1106.7. -- PLEASE DESIGNATE EACH
 DRAIN AND RWL WITH A NUMBER OR LETTER TO VERIFY
 CALCULATIONS AND TRACK PIPE SIZING THROUGH THE BUILDING
 FROM ROOF TO UNDERGROUND.
  
 12. SHT A104 NO INFORMATION FOR THE ROOF DRAINAGE OVER
 THE STAIR B OR THE ELEVATOR HAS BEEN SUBMITTED.
 INDICATE THE PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107. INDICATE IF THERE ARE PARAPET
 WALLS AROUND THESE ROOFS.
  
 13. SHT A105 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF/DECK DRAINS. SHOW THE AREA BEING DRAIN
 FOR EACH DRAIN AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH AREA.
 SECTIONS 106.1.2, 1106 & 1107 & TABLES 1106.3 & 1106.7.
  
 14. SHT A106 SUBMIT A DETAIL FOR THE OVERFLOW SCUPPERS.
 INDICATE HEIGHT & WIDTH AS WELL AS THE DISTANCE OFF THE
 ROOF TO THE FLOW LINE OF THE OVERFLOW SCUPPER. SECTIONS
 106.1.2, 1503.4.3 & TABLE 1106.7.
  
 15. SHT A309 BREAKROOM SINK SHALL BE ACCESSIBLE. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24-3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 16. SHTS A310 & A311 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.5 FLUSH CONTROLS
 ___STALL
 A. 11-4.17.3 SIZE & ARRANGEMENT - FIG 30(E)
 ___URINAL:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 ___LAVS:
 A. 11-4.19.2 CLEARANCES (29")
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
 ___TOILET ROOMS:
 A. 11-4.22.3 UNOBSTRUCTED TURNING AREA
  
 17. SHT A311 DETAIL E. THE CABINET IS NOT APPROVED FOR
 THE LAV. FORWARD APPROACH CLEAR FLOOR SPACE IS REQUIRED
 PER SECTION 11-4.19.3. THE LAV SHALL BE A MINIMUM 15"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO BE
 CENTERED ON THE 30" DIMENSION OF THE CLEAR FLOOR SPACE.
 PLEASE INDICATE ON PLANS.
  
 18. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.15 WITH ALL SUBSECTIONS
 AS WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 19. SHTS A323 & A327 INDICATES 10 ACCESSIBLE UNITS, BUT
 SHT A00A FBC CHAPTER 11 ACCESSIBILITY INDICATES 7.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 11-9.1.2.
  
 20. SHTS A347 & A349 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___W/C'S:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS (36" SHOWN FOR SIDEWALL - 42"
 REQD) - (NOT SHOWN ON DETAIL 2E SHT A349)
 C. 11-4.16.5 FLUSH CONTROLS
 ___LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & CLEARANCE
 C. 11-4.19.5 FAUCETS
 ___SHOWER:
 A. 11-4.21.2 SIZE & CLEARANCE
 B. 11-4.21.3 SEAT (HEIGHT)
  
 21. SHT FS1-1 EQUIPMENT SCHEDULE ITEM #4 INDICATES
 QTY-2, BUT FLOOR PLAN ONLY SHOWS 1. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 701.1. INDICATE THE LOCATION OF BOTH
 ITEMS.
  
 22. SHT D102 DEMO SHEET FOR THE 2ND AND 3RD FLOORS HAS
 NOT BEEN SUBMITTED. PER SECTION 106.1 TWO OR MORE SETS
 OF PLANS ARE REQUIRED. PLEASE SUBMIT COMPLETE SETS OF
 PLANS FOR REVIEW.
  
 23. SHTS P102, P103, P104 & P105. INDICATE THE RISER
 NUMBERS FOR EACH WATER RISER IN ORDER TO TRACK THE
 RISERS THROUGH THE BUILDING AND VERIFY CODE COMPLIANCE
 OF RISERS. SECTIONS 106.1.2, & 601.1.
  
 24. SHT P106 NOTE STATES POOL SHOWER BY POOL
 CONTRACTOR. THE SHOWER SHALL BE INSTALLED BY A LICENSED
 PLUMBING CONTRACTOR PER FS 489. PLEASE CORRECT NOTE.
  
 25. SHTS P202, P203, P204 & P205. SHOW THE LOCATION OF
 ALL SANITARY RISERS AND IDENTIFY RISERS WITH RISERS
 NUMBERS TO REFLECT THE RISERS ON SHTS P703, P704 &
 P705. THIS WILL ENABLE THE REVIEWER TO TRACK PIPING
 THROUGH THE BUILDING FROM BUILDING DRAIN TO VTR FOR
 EACH RISER AND VERIFY CODE REQUIREMENTS. SECTIONS
 106.1.2 & TABLES 710.1(1) & 710.1(2).
  
 26. SHT P205 DOES NOT RELFECT RISER DIAGRAMS ON SHTS
 P703, P704 & P705 WHICH SHOWS THE VENTS CONNECTING TO
 THE LAVS AND SHOWERS. PLEASE CORRELATE. SECTION 106.1.1
 & TABLE 916.1.
  
 27. SHT P307 MAIN BUILDING STORM RISER. TOP OF RISER
 SHOWING 2 AREA DRAINS 1,708 SF & ONE AREA DRAIN 745 SF
 ALSO SHOWS A 5" LINE ABOVE THE ROOF. MORE INFORMATION
 IS REQUIRED. PLEASE INDICATE WHERE THIS STORM LINE
 TERMINATES AND IF THERE ARE MORE AREAS DRAINING INTO
 THE RISER. SECTION 106.1.2 & TABLE 1106.3.
  
 28. SHT P308 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED TO ISSUE PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. LENGHTS NOT SHOWN.
  
 B. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 D. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 INFORMATIONAL: - (WELD PIPE INDICATED. - WELD
 CERTIFICTIONS & WELDING PROCEDURE REQUIRED AT TIME OF
 APPLICATION FOR GAS PERMIT)
  
 29. SHT P402 DETAIL #2 INDICATE WHERE SUPPLY LINES FOR
 THE BAR CONNECT TO THE WATER MAINS. SECTIONS 106.1.2 &
 601.1.
  
 30. SHT P403 DETAIL #2 A RELIEF VENT IS REQUIRED FOR
 THE AIR ADMITTANCE VALVE. SECTION 917.3.2. PLEASE
 INDICATE ON FLOOR PLAN AND RISER DIAGRAM.
  
 31. SHT P405 DETAIL #1 SHOWS NO WATER SUPPLY TO THE
 URINAL. PLEASE SHOW ON PLANS. SECTIONS 106.1.2 & 601.1.
  
 32. SHT P405 DETAIL #3 SHOWS THE WATER HAMMER ARRESTORS
 IN THE CEILING. WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201.
  
 33. SHT P501 WATER PIPING NOTES #2. NO COPPER JOINTS
 UNDER THE SLAB. SECTION 303.2. PLEASE INDICATE IN NOTE.
  
 34. SHT P501 WATER PIPING NOTES #3 BACKFLOW PREVENTOR
 TO BE INSTALLED BY A LICENSED PLUMBING CONTRACTOR PER
 FS 489. PLEASE INDICATE IN NOTE.
  
 35. SHT P501 WATER HEATER SCHEDULE NOTE #2 CODE
 REQUIREMENT IS THE FBC-2004 PLUMBING & MECHANICAL WITH
 2007 AMENDMENTS, NOT THE STANDARD CODE AS INDICATED.
 PLEASE CORRECT THE CODE REFERENCE. SECTION 106.1.1.
  
 36. SHT P601 DETAIL #1 DOES NOT RELFECT THE FLOOR PLAN
 AT THE EWC-A. PLEASE CORRELATE. SECTION 106.1.1.
  
 37. SHT P601 DETAIL #1 SUPPLY RISERS (LOWER LEVEL)
 SHOWS 3 COLD WATER SUPPLY LINES TO 3 WASH MACHINES AND
 2 COLD WATER SUPPLY LINES TO THE LAST WASH MACHINE.
 PLEASE CLAIFY. SUBMIT A DETAIL SHOWING THE PIPING TO
 THE WASH MACHINES. SECTIONS 106.1.2 & 601.1
  
 38. SHT P601 DETAIL #1 SUPPLY RISERS (LOWER LEVEL).
 WATER HAMMER ARRESTORS ARE REQUIRED ON THE SUPPLY LINES
 TO THE WASH MACHINES AND SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE". SECTION 604.9 &
 PDI-WH 201.
  
 39. SHT P602 A WATER HAMMER ARRESTOR IS REQUIRE A THE
 ICE MAKER PER SECTION 604.9 AND SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE". SECTION 604.9 &
 PDI-WH 201.
  
 40. SHT P602 RISER 3A NEAR ANNEX BUILDING DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1 & 601.1.
  
 41. SHT P602 NO WATER SUPPLY CONNECTION TO THE WATER
 MAINS TO THE BAR AREA. PLEASE CLARIFY. SECTIONS
 106.1.1, 106.1.2 & 601.1.
  
 42. SHT P602 TWO RISERS DESIGNATED 7A ARE REVERSE FROM
 THE FLOOR PLAN. PLEASE INDICATE ON THE FLOOR PLAN, (7A
 REVERSE), OR SUBMIT A REVERSE RISER DIAGRAM THAT
 REFLECT THE FLOOR PLAN. SECTIONS 106.1.1, 106.1.2 &
 601.1.
  
 43. SHT P701 SANITARY RISERS (LOWER LEVEL). THE SUMP
 PUMP FROM THE ELEVATOR CONNECTION TO THE SANITARY
 SYSTEM IS PROHIBITED. SECTION 301.6. A LINE TO WHERE
 THE CONTENTS CAN BE PUMPED TO A CONTAINER AND DISPOSED
 IN AN APPROVED HAZARDOUS WASTE FACILITY IS REQUIRED.
  
 44. SHT P701 SANITARY RISERS (LOWER LEVEL) SHOWS A 4"
 VENT UP THAT IS NOT FOUND ON SHT P702. PLEASE CLARIFY.
 SECTION 106.1.1 & TABLE 916.1.
  
 45. SHT P702 SANITARY RISERS (1ST FLOOR) DOES NOT
 REFLECT THE FLOOR PLAN. RISER 9A IS NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1 & 901.1.
  
 46. SHT P702 SANITARY RISERS (1ST FLOOR) DOES NOT
 REFLECT THE FLOOR PLAN. NOTE: "SEE SHT P701 FOR
 CONTINUATION" PIPING WAS NOT FOUND ON THE FLOOR PLAN.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 901.1.
  
 47. SHT P702 SANITARY RISERS (1ST FLOOR) DOES NOT
 REFLECT THE FLOOR PLAN. A BRANCH LINE TO 4" SS UP
 UPSTREAM OF THE ELEVATOR BRANCH LINE IS SHOWN ON THE
 FLOOR PLAN BUT NOT ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 901.1.
  
 48. SHT P702 SANITARY RISERS (1ST FLOOR). SHOW PIPE
 SIZES FOR THE FLOOR DRAIN AND THE FLOOR SINK BY THE
 PREP HAND SINK. TABLES 710.1.(1) & 710.1(2).
  
 49. SHTS P703, P704 & P705 ALL VENT STACKS SHALL
 CONNECT AT THE BASE OF THE WASTE/SOIL STACKS. SECTION
 903.4. PLEASE SHOW ON RISERS.
  
 50. SHT P706 DETAIL #1 RISER DOES NOT REFLECT THE FLOOR
 PLAN ON SHT P205 AT 4" VENT UP NEAR RISER 15B. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 901.1.
  
 51. SHT P801 ELEVATOR SUMP CONNECTION DETAIL NOT
 APPROVED. SECTION 301.6. A LINE TO WHERE THE CONTENTS
 CAN BE PUMPED TO A CONTAINER AND DISPOSED IN AN
 APPROVED HAZARDOUS WASTE FACILITY IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  