| 2009-01-20 11:36:44 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 (ADMIN) |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | ****PLAN REVIEW ONLY**** |
| | |
| | 1. ALL SHEETS WITH G.M. REMBOWSKI ARCHITECT INC. THE |
| | BUSINESS LICENSE, (CERTIFICATE OF AUTHORIZATION), IS |
| | REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC |
| | 61G1-16.004(2) & FS 481.219, 481.2055. |
| | |
| | 2. SHT A00A BUILDING CODES TO INCLUDE THE 2007 |
| | REVISIONS. PLEASE BE ADVISED, SINCE THE PLANS HAVE BEEN |
| | SUBMITTED FOR PLAN REVIEW ONLY AT THIS TIME, IF THE |
| | PERMIT IS NOT APPLIED FOR PRIOR TO MARCH 1. 2009 THE |
| | PROJECT SHALL BE DESIGNED TO THE THE REQUIREMENTS OF |
| | THE FBC-2007 CODE. |
| | |
| | 3. SHT A00A FBC CHAPTER 11 ACCESSIBILITY INDICATES 7 |
| | GUESTROOMS WITH MOBILITY FEATURES. PER THE TABLE FOR |
| | SECTION 11-9.1.2, FIVE ARE REQUIRED WITH AN ADDITIONAL |
| | 2 SLEEPING ROOMS WITH ROLL IN SHOWERS WHICH IS |
| | INDICATED ON THE PLANS. BUT PER THE FLORIDA SPECIFIC |
| | AREA OF SECTION 11-9.1.2, FIVE PERCENT OF THE |
| | GUESTROOMS, MINUS THE NUMBER OF ACCESSIBLE GUESTROOM |
| | REQUIRED BY THE TABLE, (5), SHALL PROVIDE ADDITIONAL |
| | SPECIAL ACCESSIBILITY FEATURES OF SECTION 11-9.2.3. |
| | THIS NUMBER COMES OUT TO 3 UNITS, (150 X .05 = 7.5 |
| | MINUS 5 = 2.5 ROUNDED UP TO 3 UNITS). PLEASE INDICATE |
| | WHICH 3 ROOMS ARE COMPLIANT WITH THIS REQUIREMENT. |
| | SECTION 106.1.2. |
| | |
| | 4. SHT A100 GUESTROOM SUMMARY SHOWS DOUBLE QUEEN, |
| | DOUBLE QUEEN SUITE, NARROW KING, KING & KING SUITE |
| | CLASSES OF ACCOMMODATIONS. THE ONLY ACCESSIBLE UNITS |
| | SHOWN ARE THE DOUBLE QUEEN AND THE KING UNITS. PER |
| | SECTION 11-9.1.4 IN ORDER TO PROVIDE PERSONS WITH |
| | DISABILITIES A RANGE OF OPTIONS EQUIVALENT TO THOSE |
| | AVAILABLE TO OTHER PERSONS SERVED BY THE FACILITY, |
| | SLEEPING ROOMS AND SUITES REQUIRED TO ACCESSIBLE BY |
| | SECTION 11-9.1.2 SHALL BE DISPERSED AMONG THE VARIOUS |
| | CLASSES OF SLEEPING ACCOMMODATIONS AVAILABLE TO PATRONS |
| | OF THE PLACE OF TRANSIENT LODGING. NO ACCESSIBLE UNITS |
| | ARE INDICATED FOR THE DOUBLE QUEEN SUITE, THE NARROW |
| | KING AND THE KING SUITES. PLEASE INDICATE HOW |
| | COMPLIANCE WITH SECTION 11-9.1.4 WILL BE ADDRESSED. |
| | |
| | 5. SHT A100 SHOWS 10 ACCESSIBLE ROOMS BUT SHT A00A FBC |
| | CHAPTER 11 ACCESSIBILITY INDICATES GUESTROOMS WITH |
| | MOBILITY FEATURES TOTALS 7 (2 TO HAVE ROLL-IN SHOWERS), |
| | AS WELL AS 12 GUESTROOMS WITH COMMUNICATION FEATURES. |
| | PLEASE CLARIFY & CORRELATE. SECTIONS 11-9.1.2 & |
| | 11-9.1.3.. |
| | |
| | 6. SHT A100 FOOD PREP AREA MAY REQUIRE A GREASE |
| | INTERCEPTOR. PLEASE CONTACT THE UTILITY DEPT., |
| | INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE. |
| | PLEASE CONTACT HOLLY MCGRATH, LABORATORY SUPERVISOR AT |
| | HER OFFICE, (561) 822-2271, OR BY FAX (561) 822-2279. |
| | OR BY E-MAIL [email protected]. INTERCEPTOR SIZE WILL BE |
| | DETERMINED AND A WRITTEN DETERMINATION WILL BE |
| | SUBMITTED WITH RESPONSE COMMENTS. ARTICLE III SECTION |
| | 90-124(7). |
| | |
| | 7. SHTS A102 & A103 SHOWS ACCESSIBLE KING SUITE WHICH |
| | DOES NOT REFLECT THE GUESTROOM SUMMARY ON SHT A100 |
| | WHICH INDICATES ACCESSIBLE KING UNIT. PLEASE CLARIFY & |
| | CORRELATE. SECTIONS 106.1.1 & 11-9.1.4. |
| | |
| | 8. SHTS A102 & A103 ROOMS FOR PERSONS WITH HEARING |
| | IMPAIRMENTS SHALL BE IN ADDITION TO ROOMS THAT ARE |
| | ACCESSIBLE. SECTION 11-9-1.3. PLEASE INDICATE THE |
| | LOCATION OF THESE UNITS. |
| | |
| | 9. SHTS A104 & L5/6 ROOF INFORMATION DOES NOT MATCH. |
| | PLEASE CORRELATE. SECTIONS 106.1.1 & 1101.1 AND TABLE |
| | 1106.3. |
| | |
| | 10. SHT A104 NO SECONDARY ROOF DRAINAGE IS SHOWN. |
| | SECTION 1107. PLEASE INDICATE LOCATION OF REQUIRED |
| | SECOND ROOF DRAINAGE. |
| | |
| | 11. A104 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF/DECK DRAINS. SHOW THE AREA BEING DRAIN |
| | FOR EACH DRAIN AND INDICATE 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH AREA TO |
| | VERIFY DRAIN & RWL SIZES. SECTIONS 106.1.2, 1106 & 1107 |
| | & TABLES 1106.3 & 1106.7. -- PLEASE DESIGNATE EACH |
| | DRAIN AND RWL WITH A NUMBER OR LETTER TO VERIFY |
| | CALCULATIONS AND TRACK PIPE SIZING THROUGH THE BUILDING |
| | FROM ROOF TO UNDERGROUND. |
| | |
| | 12. SHT A104 NO INFORMATION FOR THE ROOF DRAINAGE OVER |
| | THE STAIR B OR THE ELEVATOR HAS BEEN SUBMITTED. |
| | INDICATE THE PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106 & 1107. INDICATE IF THERE ARE PARAPET |
| | WALLS AROUND THESE ROOFS. |
| | |
| | 13. SHT A105 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF/DECK DRAINS. SHOW THE AREA BEING DRAIN |
| | FOR EACH DRAIN AND INDICATE 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH AREA. |
| | SECTIONS 106.1.2, 1106 & 1107 & TABLES 1106.3 & 1106.7. |
| | |
| | 14. SHT A106 SUBMIT A DETAIL FOR THE OVERFLOW SCUPPERS. |
| | INDICATE HEIGHT & WIDTH AS WELL AS THE DISTANCE OFF THE |
| | ROOF TO THE FLOW LINE OF THE OVERFLOW SCUPPER. SECTIONS |
| | 106.1.2, 1503.4.3 & TABLE 1106.7. |
| | |
| | 15. SHT A309 BREAKROOM SINK SHALL BE ACCESSIBLE. SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | A. 11-4.24-3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE |
| | D. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | E. 11-4.24.7 FAUCETS |
| | |
| | 16. SHTS A310 & A311 SHOW COMPLIANCE FOR THE FOLLOWING: |
| | ___W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | ___STALL |
| | A. 11-4.17.3 SIZE & ARRANGEMENT - FIG 30(E) |
| | ___URINAL: |
| | A. 11-4.18.3 CLEAR FLOOR SPACE |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | ___LAVS: |
| | A. 11-4.19.2 CLEARANCES (29") |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.19.6 MIRRORS |
| | ___TOILET ROOMS: |
| | A. 11-4.22.3 UNOBSTRUCTED TURNING AREA |
| | |
| | 17. SHT A311 DETAIL E. THE CABINET IS NOT APPROVED FOR |
| | THE LAV. FORWARD APPROACH CLEAR FLOOR SPACE IS REQUIRED |
| | PER SECTION 11-4.19.3. THE LAV SHALL BE A MINIMUM 15" |
| | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO BE |
| | CENTERED ON THE 30" DIMENSION OF THE CLEAR FLOOR SPACE. |
| | PLEASE INDICATE ON PLANS. |
| | |
| | 18. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.15 WITH ALL SUBSECTIONS |
| | AS WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 19. SHTS A323 & A327 INDICATES 10 ACCESSIBLE UNITS, BUT |
| | SHT A00A FBC CHAPTER 11 ACCESSIBILITY INDICATES 7. |
| | PLEASE CORRELATE. SECTIONS 106.1.1 & 11-9.1.2. |
| | |
| | 20. SHTS A347 & A349 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | ___W/C'S: |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.16.4 GRAB BARS (36" SHOWN FOR SIDEWALL - 42" |
| | REQD) - (NOT SHOWN ON DETAIL 2E SHT A349) |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | ___LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCE |
| | B. 11-4.19.4 EXPOSED PIPES & CLEARANCE |
| | C. 11-4.19.5 FAUCETS |
| | ___SHOWER: |
| | A. 11-4.21.2 SIZE & CLEARANCE |
| | B. 11-4.21.3 SEAT (HEIGHT) |
| | |
| | 21. SHT FS1-1 EQUIPMENT SCHEDULE ITEM #4 INDICATES |
| | QTY-2, BUT FLOOR PLAN ONLY SHOWS 1. PLEASE CORRELATE. |
| | SECTIONS 106.1.1 & 701.1. INDICATE THE LOCATION OF BOTH |
| | ITEMS. |
| | |
| | 22. SHT D102 DEMO SHEET FOR THE 2ND AND 3RD FLOORS HAS |
| | NOT BEEN SUBMITTED. PER SECTION 106.1 TWO OR MORE SETS |
| | OF PLANS ARE REQUIRED. PLEASE SUBMIT COMPLETE SETS OF |
| | PLANS FOR REVIEW. |
| | |
| | 23. SHTS P102, P103, P104 & P105. INDICATE THE RISER |
| | NUMBERS FOR EACH WATER RISER IN ORDER TO TRACK THE |
| | RISERS THROUGH THE BUILDING AND VERIFY CODE COMPLIANCE |
| | OF RISERS. SECTIONS 106.1.2, & 601.1. |
| | |
| | 24. SHT P106 NOTE STATES POOL SHOWER BY POOL |
| | CONTRACTOR. THE SHOWER SHALL BE INSTALLED BY A LICENSED |
| | PLUMBING CONTRACTOR PER FS 489. PLEASE CORRECT NOTE. |
| | |
| | 25. SHTS P202, P203, P204 & P205. SHOW THE LOCATION OF |
| | ALL SANITARY RISERS AND IDENTIFY RISERS WITH RISERS |
| | NUMBERS TO REFLECT THE RISERS ON SHTS P703, P704 & |
| | P705. THIS WILL ENABLE THE REVIEWER TO TRACK PIPING |
| | THROUGH THE BUILDING FROM BUILDING DRAIN TO VTR FOR |
| | EACH RISER AND VERIFY CODE REQUIREMENTS. SECTIONS |
| | 106.1.2 & TABLES 710.1(1) & 710.1(2). |
| | |
| | 26. SHT P205 DOES NOT RELFECT RISER DIAGRAMS ON SHTS |
| | P703, P704 & P705 WHICH SHOWS THE VENTS CONNECTING TO |
| | THE LAVS AND SHOWERS. PLEASE CORRELATE. SECTION 106.1.1 |
| | & TABLE 916.1. |
| | |
| | 27. SHT P307 MAIN BUILDING STORM RISER. TOP OF RISER |
| | SHOWING 2 AREA DRAINS 1,708 SF & ONE AREA DRAIN 745 SF |
| | ALSO SHOWS A 5" LINE ABOVE THE ROOF. MORE INFORMATION |
| | IS REQUIRED. PLEASE INDICATE WHERE THIS STORM LINE |
| | TERMINATES AND IF THERE ARE MORE AREAS DRAINING INTO |
| | THE RISER. SECTION 106.1.2 & TABLE 1106.3. |
| | |
| | 28. SHT P308 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED TO ISSUE PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. LENGHTS NOT SHOWN. |
| | |
| | B. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | C. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | D. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | INFORMATIONAL: - (WELD PIPE INDICATED. - WELD |
| | CERTIFICTIONS & WELDING PROCEDURE REQUIRED AT TIME OF |
| | APPLICATION FOR GAS PERMIT) |
| | |
| | 29. SHT P402 DETAIL #2 INDICATE WHERE SUPPLY LINES FOR |
| | THE BAR CONNECT TO THE WATER MAINS. SECTIONS 106.1.2 & |
| | 601.1. |
| | |
| | 30. SHT P403 DETAIL #2 A RELIEF VENT IS REQUIRED FOR |
| | THE AIR ADMITTANCE VALVE. SECTION 917.3.2. PLEASE |
| | INDICATE ON FLOOR PLAN AND RISER DIAGRAM. |
| | |
| | 31. SHT P405 DETAIL #1 SHOWS NO WATER SUPPLY TO THE |
| | URINAL. PLEASE SHOW ON PLANS. SECTIONS 106.1.2 & 601.1. |
| | |
| | 32. SHT P405 DETAIL #3 SHOWS THE WATER HAMMER ARRESTORS |
| | IN THE CEILING. WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE |
| | CEILING. PDI-WH 201. |
| | |
| | 33. SHT P501 WATER PIPING NOTES #2. NO COPPER JOINTS |
| | UNDER THE SLAB. SECTION 303.2. PLEASE INDICATE IN NOTE. |
| | |
| | 34. SHT P501 WATER PIPING NOTES #3 BACKFLOW PREVENTOR |
| | TO BE INSTALLED BY A LICENSED PLUMBING CONTRACTOR PER |
| | FS 489. PLEASE INDICATE IN NOTE. |
| | |
| | 35. SHT P501 WATER HEATER SCHEDULE NOTE #2 CODE |
| | REQUIREMENT IS THE FBC-2004 PLUMBING & MECHANICAL WITH |
| | 2007 AMENDMENTS, NOT THE STANDARD CODE AS INDICATED. |
| | PLEASE CORRECT THE CODE REFERENCE. SECTION 106.1.1. |
| | |
| | 36. SHT P601 DETAIL #1 DOES NOT RELFECT THE FLOOR PLAN |
| | AT THE EWC-A. PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 37. SHT P601 DETAIL #1 SUPPLY RISERS (LOWER LEVEL) |
| | SHOWS 3 COLD WATER SUPPLY LINES TO 3 WASH MACHINES AND |
| | 2 COLD WATER SUPPLY LINES TO THE LAST WASH MACHINE. |
| | PLEASE CLAIFY. SUBMIT A DETAIL SHOWING THE PIPING TO |
| | THE WASH MACHINES. SECTIONS 106.1.2 & 601.1 |
| | |
| | 38. SHT P601 DETAIL #1 SUPPLY RISERS (LOWER LEVEL). |
| | WATER HAMMER ARRESTORS ARE REQUIRED ON THE SUPPLY LINES |
| | TO THE WASH MACHINES AND SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE". SECTION 604.9 & |
| | PDI-WH 201. |
| | |
| | 39. SHT P602 A WATER HAMMER ARRESTOR IS REQUIRE A THE |
| | ICE MAKER PER SECTION 604.9 AND SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE". SECTION 604.9 & |
| | PDI-WH 201. |
| | |
| | 40. SHT P602 RISER 3A NEAR ANNEX BUILDING DOES NOT |
| | REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| | 106.1.1 & 601.1. |
| | |
| | 41. SHT P602 NO WATER SUPPLY CONNECTION TO THE WATER |
| | MAINS TO THE BAR AREA. PLEASE CLARIFY. SECTIONS |
| | 106.1.1, 106.1.2 & 601.1. |
| | |
| | 42. SHT P602 TWO RISERS DESIGNATED 7A ARE REVERSE FROM |
| | THE FLOOR PLAN. PLEASE INDICATE ON THE FLOOR PLAN, (7A |
| | REVERSE), OR SUBMIT A REVERSE RISER DIAGRAM THAT |
| | REFLECT THE FLOOR PLAN. SECTIONS 106.1.1, 106.1.2 & |
| | 601.1. |
| | |
| | 43. SHT P701 SANITARY RISERS (LOWER LEVEL). THE SUMP |
| | PUMP FROM THE ELEVATOR CONNECTION TO THE SANITARY |
| | SYSTEM IS PROHIBITED. SECTION 301.6. A LINE TO WHERE |
| | THE CONTENTS CAN BE PUMPED TO A CONTAINER AND DISPOSED |
| | IN AN APPROVED HAZARDOUS WASTE FACILITY IS REQUIRED. |
| | |
| | 44. SHT P701 SANITARY RISERS (LOWER LEVEL) SHOWS A 4" |
| | VENT UP THAT IS NOT FOUND ON SHT P702. PLEASE CLARIFY. |
| | SECTION 106.1.1 & TABLE 916.1. |
| | |
| | 45. SHT P702 SANITARY RISERS (1ST FLOOR) DOES NOT |
| | REFLECT THE FLOOR PLAN. RISER 9A IS NOT SHOWN ON THE |
| | FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1 & 901.1. |
| | |
| | 46. SHT P702 SANITARY RISERS (1ST FLOOR) DOES NOT |
| | REFLECT THE FLOOR PLAN. NOTE: "SEE SHT P701 FOR |
| | CONTINUATION" PIPING WAS NOT FOUND ON THE FLOOR PLAN. |
| | PLEASE CORRELATE. SECTIONS 106.1.1 & 901.1. |
| | |
| | 47. SHT P702 SANITARY RISERS (1ST FLOOR) DOES NOT |
| | REFLECT THE FLOOR PLAN. A BRANCH LINE TO 4" SS UP |
| | UPSTREAM OF THE ELEVATOR BRANCH LINE IS SHOWN ON THE |
| | FLOOR PLAN BUT NOT ON THE RISER DIAGRAM. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 901.1. |
| | |
| | 48. SHT P702 SANITARY RISERS (1ST FLOOR). SHOW PIPE |
| | SIZES FOR THE FLOOR DRAIN AND THE FLOOR SINK BY THE |
| | PREP HAND SINK. TABLES 710.1.(1) & 710.1(2). |
| | |
| | 49. SHTS P703, P704 & P705 ALL VENT STACKS SHALL |
| | CONNECT AT THE BASE OF THE WASTE/SOIL STACKS. SECTION |
| | 903.4. PLEASE SHOW ON RISERS. |
| | |
| | 50. SHT P706 DETAIL #1 RISER DOES NOT REFLECT THE FLOOR |
| | PLAN ON SHT P205 AT 4" VENT UP NEAR RISER 15B. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 901.1. |
| | |
| | 51. SHT P801 ELEVATOR SUMP CONNECTION DETAIL NOT |
| | APPROVED. SECTION 301.6. A LINE TO WHERE THE CONTENTS |
| | CAN BE PUMPED TO A CONTAINER AND DISPOSED IN AN |
| | APPROVED HAZARDOUS WASTE FACILITY IS REQUIRED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |