| 2008-12-18 13:18:51 | PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY AND NOT |
| | FOR PERMIT. |
| | |
| | 1) PROVIDE LIFE SAFETY PLAN ILLUSTRATING MAXIMUM TRAVEL |
| | DISTANCES. |
| | |
| | 2) LIFE SAFETY TO COMPY WITH FLORIDA FIRE PRVENTION |
| | CODE, 2004 AND NFPA 101, 2003 EDITION. |
| | |
| | 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY |
| | WITH NFPA 241. ADD TO BUILDING CODES ON SHEET A00A. |
| | |
| | 4) VERIFY IF PROJECT MEETS THE DEFINITION OF HIGHRISE |
| | BUILDING IN ACCORDANCE WITH NFPA 101, SEC. 3.3.2.7.7. |
| | |
| | 5) FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED BEFORE OR |
| | AT THE TIME OF THE FINAL INSPECTION. |
| | |
| | 6) IF THIS BUILDING IS DETERMINED TO BE A HIGHRISE BY |
| | DEFINITION, A MINIMUM OF TWO (2) FIRE DEPARTMENT |
| | CONNECTIONS ARE REQUIRED. OK ON SHEET C5.1 |
| | |
| | 7) NEW FDC'C SHALL BE PROVIDED WITH KNOX LOCKING CAPS. |
| | |
| | 8) TEMPORARY STANDPIPE IS REQUIRED WHEN BUILDING |
| | REACHES THREE (3) STORIES OR THIRT (30)' IN HEIGHT. |
| | |
| | 9) PROVIDE ADDITIONAL INFORMATION REGARDING AREA OF |
| | RESTRICTED EASEMENT AND HOW IF ANY THIS WILL IMPACT |
| | EMERGENCY RESPONDERS. |
| | |
| | 10) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS TO BE |
| | PROVIDED AT LOCATIONS NOT TO EXCEED (75)' TRAVEL |
| | DISTANCE REQUIREMENT. A SHEETS GENERAL NOTES |
| | |
| | 11) ALL WALKING SURFACES SHALL BE SLIP RESISTANT. |
| | ILLUSTRATE COMPLIANCE ON SHEET A104 ROOF PLAN. |
| | |
| | 12) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR |
| | HANDRAILS AND GUARDRAILS. |
| | |
| | 13) NEW GUARDRAILS SHALL BE MINIMUM (42)" IN HEIGHT. |
| | SHEET A104 ROOF PLAN |
| | |
| | 14) COMBUSTIBLE FURNITURE ON ROOF THAT IS LOCATED |
| | BENEATH OVERHANGS EXCEEDING (48)" IN WIDTH SHALL BE |
| | PROTECTED BY AN AUTOMATIC FIRE SPRINKLER SYSTEM. THIS |
| | REQUIREMENT APPLIES TO ANY ENCLOSURES, AREAS OR ROOMS |
| | ON THE ROOF. |
| | |
| | 15) PROVIDE A SPRINKLER LAYOUT FOR REVIEW AT TIME OF |
| | PERMIT APPLICATION. IN ADDITION, SEPARATE SHOP DRAWINGS |
| | AND PERMIT IS REQUIRED FOR FIRE SPRINKLER SYSTEM PRIOR |
| | TO EQUIPMENT INSTALLATION. |
| | |
| | 16) KNOX BOX ACCESS SYSTEM IS REQUIRED NEAR FRONT DOOR |
| | ENTRANCE. CONTACT BUREAU OF FIRE PREVENTION AT (561) |
| | 804-4756 FOR ASSISTANCE AT APPROPRIATE TIME. |
| | |
| | 17) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR |
| | WALLS AND CEILINGS. |
| | |
| | 18) ELEVATOR WARNING SIGNS ARE REQUIRED IN ELEVATOR |
| | LOBBIES. |
| | |
| | 19) PROVIDE ADDITIONAL INFORMATION REGARDING USE OF |
| | RE-FUEL AREA 104. |
| | |
| | 20) ILLUSTRATE OCCUPANT LOAD CALCULATIONS FOR WHOM |
| | MEANS OF EGRESS AND OTHER PROVISIONS ARE REQUIRED. NFPA |
| | 101, SEC. 28.1.7 |
| | |
| | 21) ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF |
| | ASME A117.1 AND SHALL BE OF SUFFICIENT SIZE TO |
| | ACCOMODATE A STRETCHER. OK SHEET A601, NOTE #1 |
| | |
| | 22) EMERGENCY INSTRUCTIONS FOR GUESTS SHALL BE PROVIDED |
| | ON OR IMMEDIATELY ADJACENT TO EVERY GUEST ROOM DOOR. |
| | NFPA 101, SEC. 28.7.4.1 |
| | |
| | 23) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE |
| | MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH |
| | BACKGROUND. ADD TO APPROPRIATE ELEVATION SHEET |
| | |
| | 24) SHEET A701 REFERENCES CARD READERS. SEPARATE SHOP |
| | DRAWINGS AND PERMIT REQUIRED FOR ACCESS-CONTROL |
| | EQUIPMENTINSTALLATION. WORK TO COMPLY WITH NFPA 101, |
| | SEC. 7.2.1.6.2 (ACCESS-CONTROLLED EGRESS DOORS.) |
| | |
| | 25) PROPER CLEARANCES TO BE MAINTAINED NEAR FIRE |
| | PROTECTION EQUIPMENT. THE EXISTING FIRE DEPARTMENT |
| | CONNECTION APPEARS TO BE OBSTRUCTED BY THE PROPOSED |
| | MEMORIAL WALL. |
| | |
| | 26) SHEET C4.3, NOTE #4 SHOULD READ CITY OF WEST PALM |
| | BEACH AS AUTHORITY HAVING JURISDICTION. IN ADDITION TO |
| | ELECTRONIC SUPERVISION, DOUBLE CHECK DETECTOR ASSEMBLY |
| | TO BE SECURED WITH CHAIN AND LOCK. |
| | |
| | 27) PLEASE VERIFY THE LOCATION OF THE DOUBLE CHECK |
| | DETECTOR ASSEMBLY. |
| | |
| | 28) FIRE DAMPERS TO BE TESTED FOR CLOSURE PER THE |
| | REQUIREMENTS OF UL 555 PRIOR TO FINAL INSPECTION. |
| | |
| | 29) FIRE ALARM SYSTEM SHALL MEET THE TWO HOUR |
| | SURVIVABILITY REQUIREMENTS FOR HIGHRISE BUILDINGS IF |
| | APPLICABLE. NFPA 72, 2002 EDITION |
| | |
| | 30) COOLING TOWERS TO COMPLY WITH NFPA 214. |
| | |
| | 31) DUCT SMOKE DETECTORS IN ADDITION TO FAN SHUT DOWN |
| | SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM AND |
| | INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS. SHEET E300 NOTE #5D |
| | |
| | 32) PROJECT PHYSICAL ADDRESS IS REQUIRED ON EACH SHEET |
| | OF PLANS AND SUPPORTING DOCUMENTS. |
| | |
| | 33) EMERGENCY LIGHTING FACILITIES ARE NOT SHOWN INSIDE |
| | STAIRWELLS WITH THE EXCEPTION OF STAIR #3. |
| | |
| | 34) FIRE COMMEND ROOM IS NOT CLEARLY SHOWN ON SHEET |
| | E103. EMERGENCY LIGHTING IS REQUIRED AND THE DOOR SHALL |
| | BE PROVIDED WITH APPROPRIATE SIGNAGE. |
| | |
| | 35) IT APPEARS THAT ADDITIONAL EXIT SIGNS ARE NEEDED ON |
| | ROOF. SHEET E107 |
| | |
| | 36) SOME OF THE ENCLOSED AREAS/ROOMS ON THE ROOF ARE |
| | MISSING EMERGENCY LIGHTS. |
| | |
| | 37) SOME OF THE ELECTRICAL SHEETS (TYPICAL ROOM PLANS) |
| | REFERENCE SMOKE DETECTORS INSIDE GUEST ROOMS. DEVICES |
| | PROVIDED IN EVERY GUEST ROOM SHALL BE APPROVED SINGLE |
| | STATION SMOKE ALARMS, NFPA 101 SEC. 28.3.4.5 AND SHALL |
| | NOT INITIATE A GENERAL FIRE ALARM. ELECTRICAL SHEETS |
| | SEEM TO ILLUSTRATE BOTH TYPES OF DEVICES IN ROOMS. |
| | |
| | 38) SMOKE ALARMS SHALL BE LOCATED MINIMUM OF THREE (3)' |
| | FROM AC DIFFUSERS. |
| | |
| | 39) CUTTING AND WELDING OPERATIONS ARE PROHIBITED |
| | WITHOUT BUREAU OF FIRE PREVENTION APPROVAL AND STRICT |
| | COMPLIANCE WITH NFPA 51B. |
| | |
| | 40) PROVIDE VOICE MESSAGE LANGUAGE FOR FIRE ALARM |
| | EVACUATION SIGNAL. |
| | |
| | 41) A MANUAL PULL STATION SHALL BE LOCATED AT THE HOTEL |
| | DESK OR OTHER CONVENIENT CENTRAL CONTROL POINT UNDER |
| | CONTINUOUS SUPERVISION. NFPA 101, SEC. 28.3.4.2 (2). |
| | |
| | 42) FIRE COMMAND ROOM SHALL COMPLY WITH THE |
| | REQUIREMENTS OF NFPA 101, SEC. 11.8.5. |
| | |
| | |
| | MIKE WENNERGREN, ASST. FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |