Plan Review Notes
Plan Review Notes For Permit 08110283
Permit Number 08110283
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-12-18 13:18:51PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY AND NOT
 FOR PERMIT.
  
 1) PROVIDE LIFE SAFETY PLAN ILLUSTRATING MAXIMUM TRAVEL
 DISTANCES.
  
 2) LIFE SAFETY TO COMPY WITH FLORIDA FIRE PRVENTION
 CODE, 2004 AND NFPA 101, 2003 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241. ADD TO BUILDING CODES ON SHEET A00A.
  
 4) VERIFY IF PROJECT MEETS THE DEFINITION OF HIGHRISE
 BUILDING IN ACCORDANCE WITH NFPA 101, SEC. 3.3.2.7.7.
  
 5) FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED BEFORE OR
 AT THE TIME OF THE FINAL INSPECTION.
  
 6) IF THIS BUILDING IS DETERMINED TO BE A HIGHRISE BY
 DEFINITION, A MINIMUM OF TWO (2) FIRE DEPARTMENT
 CONNECTIONS ARE REQUIRED. OK ON SHEET C5.1
  
 7) NEW FDC'C SHALL BE PROVIDED WITH KNOX LOCKING CAPS.
  
 8) TEMPORARY STANDPIPE IS REQUIRED WHEN BUILDING
 REACHES THREE (3) STORIES OR THIRT (30)' IN HEIGHT.
  
 9) PROVIDE ADDITIONAL INFORMATION REGARDING AREA OF
 RESTRICTED EASEMENT AND HOW IF ANY THIS WILL IMPACT
 EMERGENCY RESPONDERS.
  
 10) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS TO BE
 PROVIDED AT LOCATIONS NOT TO EXCEED (75)' TRAVEL
 DISTANCE REQUIREMENT. A SHEETS GENERAL NOTES
  
 11) ALL WALKING SURFACES SHALL BE SLIP RESISTANT.
 ILLUSTRATE COMPLIANCE ON SHEET A104 ROOF PLAN.
  
 12) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDRAILS.
  
 13) NEW GUARDRAILS SHALL BE MINIMUM (42)" IN HEIGHT.
 SHEET A104 ROOF PLAN
  
 14) COMBUSTIBLE FURNITURE ON ROOF THAT IS LOCATED
 BENEATH OVERHANGS EXCEEDING (48)" IN WIDTH SHALL BE
 PROTECTED BY AN AUTOMATIC FIRE SPRINKLER SYSTEM. THIS
 REQUIREMENT APPLIES TO ANY ENCLOSURES, AREAS OR ROOMS
 ON THE ROOF.
  
 15) PROVIDE A SPRINKLER LAYOUT FOR REVIEW AT TIME OF
 PERMIT APPLICATION. IN ADDITION, SEPARATE SHOP DRAWINGS
 AND PERMIT IS REQUIRED FOR FIRE SPRINKLER SYSTEM PRIOR
 TO EQUIPMENT INSTALLATION.
  
 16) KNOX BOX ACCESS SYSTEM IS REQUIRED NEAR FRONT DOOR
 ENTRANCE. CONTACT BUREAU OF FIRE PREVENTION AT (561)
 804-4756 FOR ASSISTANCE AT APPROPRIATE TIME.
  
 17) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS.
  
 18) ELEVATOR WARNING SIGNS ARE REQUIRED IN ELEVATOR
 LOBBIES.
  
 19) PROVIDE ADDITIONAL INFORMATION REGARDING USE OF
 RE-FUEL AREA 104.
  
 20) ILLUSTRATE OCCUPANT LOAD CALCULATIONS FOR WHOM
 MEANS OF EGRESS AND OTHER PROVISIONS ARE REQUIRED. NFPA
 101, SEC. 28.1.7
  
 21) ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF
 ASME A117.1 AND SHALL BE OF SUFFICIENT SIZE TO
 ACCOMODATE A STRETCHER. OK SHEET A601, NOTE #1
  
 22) EMERGENCY INSTRUCTIONS FOR GUESTS SHALL BE PROVIDED
 ON OR IMMEDIATELY ADJACENT TO EVERY GUEST ROOM DOOR.
 NFPA 101, SEC. 28.7.4.1
  
 23) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE
 MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH
 BACKGROUND. ADD TO APPROPRIATE ELEVATION SHEET
  
 24) SHEET A701 REFERENCES CARD READERS. SEPARATE SHOP
 DRAWINGS AND PERMIT REQUIRED FOR ACCESS-CONTROL
 EQUIPMENTINSTALLATION. WORK TO COMPLY WITH NFPA 101,
 SEC. 7.2.1.6.2 (ACCESS-CONTROLLED EGRESS DOORS.)
  
 25) PROPER CLEARANCES TO BE MAINTAINED NEAR FIRE
 PROTECTION EQUIPMENT. THE EXISTING FIRE DEPARTMENT
 CONNECTION APPEARS TO BE OBSTRUCTED BY THE PROPOSED
 MEMORIAL WALL.
  
 26) SHEET C4.3, NOTE #4 SHOULD READ CITY OF WEST PALM
 BEACH AS AUTHORITY HAVING JURISDICTION. IN ADDITION TO
 ELECTRONIC SUPERVISION, DOUBLE CHECK DETECTOR ASSEMBLY
 TO BE SECURED WITH CHAIN AND LOCK.
  
 27) PLEASE VERIFY THE LOCATION OF THE DOUBLE CHECK
 DETECTOR ASSEMBLY.
  
 28) FIRE DAMPERS TO BE TESTED FOR CLOSURE PER THE
 REQUIREMENTS OF UL 555 PRIOR TO FINAL INSPECTION.
  
 29) FIRE ALARM SYSTEM SHALL MEET THE TWO HOUR
 SURVIVABILITY REQUIREMENTS FOR HIGHRISE BUILDINGS IF
 APPLICABLE. NFPA 72, 2002 EDITION
  
 30) COOLING TOWERS TO COMPLY WITH NFPA 214.
  
 31) DUCT SMOKE DETECTORS IN ADDITION TO FAN SHUT DOWN
 SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM AND
 INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS. SHEET E300 NOTE #5D
  
 32) PROJECT PHYSICAL ADDRESS IS REQUIRED ON EACH SHEET
 OF PLANS AND SUPPORTING DOCUMENTS.
  
 33) EMERGENCY LIGHTING FACILITIES ARE NOT SHOWN INSIDE
 STAIRWELLS WITH THE EXCEPTION OF STAIR #3.
  
 34) FIRE COMMEND ROOM IS NOT CLEARLY SHOWN ON SHEET
 E103. EMERGENCY LIGHTING IS REQUIRED AND THE DOOR SHALL
 BE PROVIDED WITH APPROPRIATE SIGNAGE.
  
 35) IT APPEARS THAT ADDITIONAL EXIT SIGNS ARE NEEDED ON
 ROOF. SHEET E107
  
 36) SOME OF THE ENCLOSED AREAS/ROOMS ON THE ROOF ARE
 MISSING EMERGENCY LIGHTS.
  
 37) SOME OF THE ELECTRICAL SHEETS (TYPICAL ROOM PLANS)
 REFERENCE SMOKE DETECTORS INSIDE GUEST ROOMS. DEVICES
 PROVIDED IN EVERY GUEST ROOM SHALL BE APPROVED SINGLE
 STATION SMOKE ALARMS, NFPA 101 SEC. 28.3.4.5 AND SHALL
 NOT INITIATE A GENERAL FIRE ALARM. ELECTRICAL SHEETS
 SEEM TO ILLUSTRATE BOTH TYPES OF DEVICES IN ROOMS.
  
 38) SMOKE ALARMS SHALL BE LOCATED MINIMUM OF THREE (3)'
 FROM AC DIFFUSERS.
  
 39) CUTTING AND WELDING OPERATIONS ARE PROHIBITED
 WITHOUT BUREAU OF FIRE PREVENTION APPROVAL AND STRICT
 COMPLIANCE WITH NFPA 51B.
  
 40) PROVIDE VOICE MESSAGE LANGUAGE FOR FIRE ALARM
 EVACUATION SIGNAL.
  
 41) A MANUAL PULL STATION SHALL BE LOCATED AT THE HOTEL
 DESK OR OTHER CONVENIENT CENTRAL CONTROL POINT UNDER
 CONTINUOUS SUPERVISION. NFPA 101, SEC. 28.3.4.2 (2).
  
 42) FIRE COMMAND ROOM SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 101, SEC. 11.8.5.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  