Plan Review Notes
Plan Review Notes For Permit 08110283
Permit Number 08110283
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-12 14:14:08 
 ** DENIED REVIEW **
  
 ** NOT SUBMITTED AS HISTORIC FOR EXISTING. NO
 SUPPORTING DOCUMENTS, PLANS ETC.
 PLEASE SEE NEW PORTION OF BUILDING AND MANY AREAS ARE
 CONSIDERED REVIEW UNDER FBC AND FBC EXISTING BUILDINGS
 AND ALL STATUTORY ADOPTED CODES, LAWS ETC.
  
  
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR *PLAN REVIEW * AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT APPLICATION. AS PER
 FLORIDA STATUTES 553.73 ONLY PERMIT APPLICATION BY
 LICENSED CONTRACTOR WILL *LOCK-IN* PROJECTS UNDER
 ADOPTED CODES.
 FOR EXAMPLE: IF THIS PROJECT WHICH HAS ONLY BEEN
 SUBMITTED AS PLAN REVIEW AND DOES APPLY FOR PERMIT
 UNTIL MARCH 1ST, 2009 THE NEW CODES COMING IN AFFECT
 WILL BE REQUIRED TO BE THE MINIMUM CODES FOR DESIGN.
 OTHER ITEMS SUCH AS LICENSING OF CONTRACTORS AND
 DESIGNERS WILL ALSO BE REVIEWED ONCE PERMIT APPLICATION
 IS MADE.
 EVEN ONCE PLANS ARE FOUND TO BE CODE COMPLIANT FOR
 ISSUANCE THEY WILL REMAIN IN A FAILED STATUS UNTIL
 PERMIT APPLICATION IS MADE.
  
 2) NOTE: IT IS IMPORTANT TO UNDERSTAND THAT THE PLANS
 SUBMITTED FOR REVIEW ARE NOT COMPLETE AT THIS TIME FOR
 MINIMUM CODE COMPLIANCE. IN FACT MOST OF THE SHEETS FOR
 ELECTRICAL AND OTHER TRADES EVEN STATE ON THE SHEETS *
 PERMIT REVIEW/NOT FOR CONSTRUCTION* ALTHOUGH THEY ARE
 SIGNED, DATED AND SEALED BY THE RESPECTIVE DESIGN
 PROFESSIONAL.
 AS THERE ARE MANY ITEMS NOT COMPLETED IN THE SETS AND
 SUPPORTING DOCUMENTS A FULL AND COMPLETE REVIEW OF
 DOZENS OF ITEMS COULD NOT BE DONE. PLANS MAY VERY WELL
 HAVE NEW COMMENTS WHEN RE-SUBMITTED.
 PLEASE SEE MANY OF THE NOTES BELOW WHICH WILL NOTE MANY
 OF THESE ITEMS.
  
 3) NOTE: PLEASE SEE THE SUBMITTED LANDSCAPE
 ARCHITECTURAL PLANS. THE ONLY SHEET IN THE SET IS SHEET
 5 OF 6. THIS SHEET WHICH CONTAINS THE PRINTED NAME AND
 LICENSE NUMBER OF A LANDSCAPE ARCHITECT IS IN FACT
 SIGNED, DATED AND SEALED BY THE ARCHITECT OF THE
 PROJECT AS LISTED ON ARCHITECTURAL SHEETS.
 THIS IS NOT PERMITTED UNDER FLORIDA STATUTES 481.221,
 FAC 61G1-16. NO DESIGN PROFESSIONAL SHALL AFFIX HIS/HER
 SEAL TO ANY PLANS, DOCUMENTS ETC WHICH ARE NOT UNDER
 THEIR DESIGN.
 PLEASE SUBMIT COMPLETE LANDSCAPE PLANS FOR SETS SHOWING
 ANY LANDSCAPE LIGHTING AND BE SURE TO COORDINATE WITH
 THE SUBMITTED ELECTRICAL PLANS.
 NEC 2005
 FBC 106.1.1 FOR COORDINATION, COMPLETION AND CLARITY OF
 PLANS.
  
 4) NOTE: PLEASE KNOW AT THIS TIME BASED ON THE CURRENT
 ADOPTED CODES THE FOLLOWING SHALL BE LISTED ON THE
 SUBMITTED PLANS. SOME OF THESE MAY ALREADY BE PRESENT
 HOWEVER MANY ARE NOT.
 THE SUBMITTAL OF PERMIT APPLICATION UNDER LICENSED
 CONTRACTOR AS NOTED ABOVE IN NOTE #1 WILL AFFECT
 ADOPTED CODES AND APPLICABILITY.
  
 2004 FBC W/2007 REVISIONS.
 2004 FBC W /2007 REVISIONS: CHAPTER 13 ENERGY
 EFFICIENCY CODE
 2005 NFPA-70 ( NEC).
 2003 NFPA-101
 2002 NFPA-72
 2003 NFPA-20
 2002 NFPA-110
  
 5) NOTE: PLEASE BE SURE TO SUBMIT COMPLETED ENERGY
 CALCULATIONS. PLEASE BE SURE ALL INFORMATION O THE
 INPUT DATA REPORT AND SUMMARY SHEETS COORDINATE WITH
 THE SUBMITTED PLANS. THERE ARE NUMEROUS ITEMS NOT
 COMPLETED ON THE SUBMITTED CALCULATIONS. THE INPUT DATA
 REPORT WILL BE NOTED AS IDR FOR THE REMAINDER OF THIS
 COMMENT.
 THE FOLLOWING ITEMS ARE EXAMPLES OF INCOMPLETE AND
 NON-CODE COMPLIANT MINIMUMS.
  
  
 A) PLEASE SEE THE SQUARE FOOTAGE ON THE SUBMITTED
 CALCULATIONS IS DIFFERENT FROM THE SUBMITTED PLANS. IN
 FACT THERE ARE TOTALS ON SHEETS AND SUBMITTED DOCUMENTS
 WHICH DIFFER GREATLY. TOTAL SQUARE FOOTAGE IS SHOWN AS
 116,250,117,490,101,648. NONE OF THESE COORDINATE.
 FBC 13-101, 13-400.3.A ETC
 FBC 106.1.1
  
 B) PLEASE SEE THE IDR, THE DOOR SECTION IS BLANK. THIS
 IS NOT POSSIBLE ARE THERE ARE CLEARLY DOORS FROM
 CONDITIONED SPACES TO UNCONDITIONED SPACES AND EXTERIOR
 OF BUILDING.
 FBC 13-403
  
 C) PLEASE SEE THE IDR, THE FLOORS SECTION IS BLANK.
 THIS IS NOT POSSIBLE. SAME AS ABOVE.
 FBC 13-404
  
 D) PLEASE SEE THE IDR, THE SKY-LIGHT SECTION IS BLANK.
 THIS IS NOT POSSIBLE. SAME AS ABOVE.
 FBC 13-401
  
 E) PLEASE SEE THE IDR, THE EXTERIOR LIGHTING SECTION IS
 BLANK. THERE IS IN FACT NO EXTERIOR FIXTURES ENTERED
 HOWEVER BASED ON THE SUBMITTED PLANS THIS IS ONCE AGAIN
 NOT POSSIBLE. THE PLANS CONTAIN DOZENS OF FIXTURES AND
 NONE HAVE BEEN FIGURED.
 FBC 13-415, 13-415.2.ABC.1.3.
  
 F) PLEASE SEE THE IDR FOR INTERIOR LIGHTING. THIS
 INDICATES SOME INTERIOR LIGHTING HOWEVER THERE ARE
 LITERALLY HUNDREDS OF MISSING INTERIOR LIGHTS. PLEASE
 SEE SECTIONS 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 G) PLEASE SUBMIT A COMPLETED FIXTURE LEGEND FOR ALL
 FIXTURES ON PLANS. REVIEW FOR CODE COMPLIANCE OF ENERGY
 CALCULATIONS CAN NOT BE DETERMINED AT THIS TIME.
 13-415.2, FBC 106.1.1, ADDITIONAL INFORMATION FOR
 COORDINATION, CLARITY AND MINIMUMS.
  
 THESE ARE SOME EXAMPLES ONLY OF NON-CODE COMPLIANCE.
 THIS IS GIVEN AS A BENEFIT TO DESIGN TEAM AND IT IS NOT
 A COMPLETE LIST OF ALL ITEMS ON THE SUBMITTED DOCUMENTS
 WHICH DO NOT MEET MINIMUMS UNDER SECTIONS GIVEN.
 ** THERE ARE MANY OTHER ITEMS.
  
 6) NOTE: PLEASE SUBMIT AND SHOW COMPLETE DESIGN FOR
 LIGHTING CONTROLS MEETING MINIMUMS FOR FBC 13-415.1,
 13-415.1.ABC.1.1,1.2, .1.3 AND .1.4.
 THE PLANS DO INDICATE SOME ITEMS FOR CODE COMPLIANCE
 HOWEVER THERE ARE NUMEROUS ITEMS MISSING.
  
 7) NOTE: PLEASE SUBMIT PLANS WITH COMPLETED CIRCUITING.
 PLEASE BE SURE ALL ITEMS ON PLANS COORDINATE WITH THE
 SUBMITTED PANEL SCHEDULES. PLEASE ALSO SEE 700.12E FOR
 CIRCUITING OF BATTERY BACK UP EMERGENCY AND EXIT
 LIGHTING. (SEE COMMENTS BELOW WITH RESPECT
 EMERGENCY/EXIT LIGHTING).
 PLANS ARE MISSING CIRCUITING IN MANY LOCATIONS AND
 ITEMS SUCH AS CONDUCTOR SIZES, LOADS ETC CAN NOT BE
 VERIFIED FOR MINIMUM COMPLIANCE AT THIS TIME.
 240.4,310.16,408.4.
 FBC106.1.1, 106.3.5.1.2 FOR CLARITY, COORDINATION ETC.
  
 8) NOTE: PLEASE SEE FPL AND NEC FOR MINIMUM STANDARDS
 AND WALL RATINGS OF VAULTS. THESE ARE NOT SPRINKLED AND
 SHALL MEET NEC MINIMUM STANDARDS OF 3 HOUR RATINGS OF
 ALL WALLS, FLOORS AND CEILINGS.
 450.41,450.42,450.43 ETC
  
 9) NOTE: PLEASE SEE PLANS AS THERE ARE ROOMS AND AREAS
 IN WHICH DO NOT CONTAIN DESIGNATIONS AND IDENTIFICATION
 OF EQUIPMENT. AN EXAMPLE OF THIS WOULD BE THE ROOM/AREA
 OUTSIDE OF DOUBLE QUEEN 128 WHICH APPEARS TO INDICATE A
 TRANSFORMER BY A STANDARD KNOWN SYMBOL HOWEVER NO OTHER
 INFORMATION IS NOTED OR SHOWN.
 NEC 450 IS GIVEN IN GENERAL AS NO INFORMATION IS SHOWN.
 PLEASE SEE POWER PLANS.
  
 10) NOTE: THE ELECTRICAL PLANS ALONG WITH ARCHITECTURAL
 MAKE NOTE OF LIGHTING IN THE RESTRICTED EASEMENT AREAS.
 HOW ARE THESE LIGHTS FED AND FROM WHERE?
 PLEASE ALSO OBTAIN AND SUBMIT INFORMATION ON WHAT
 EQUIPMENT IS LOCATED IN THESE AREAS. THIS WILL
 CERTAINLY AFFECT REVIEW OF WALL RATINGS ETC.
 SOME AREAS LIKE THE NORTHEAST STAIRS NOTES THIS AS A
 RESTRICTED EASEMENT AREA YET THE STAIR IS THE EGRESS
 FOR THE UPPER FLOORS. THERE ARE SEVERAL QUESTIONS YET
 TO BE ANSWERED.
 FBC 106.1.1, NEC 2005 CHAPTERS2,3,4 ETC
  
 11) NOTE: STAIRS ON LOWER LEVELS ARE SHOWING GENERAL
 PURPOSE RECEPTACLES WHICH IS NOT PERMITTED. PLEASE SEE
 FBC CHAPTER 10 FOR ITEMS REQUIRED AND ITEMS PERMITTED
 IN EXIT STAIRS.
 1019.1.2
  
 12) NOTE: PLEASE COMPLETE PLANS WITH ALL EGRESS
 LIGHTING FOR MINIMUM LEVELS IN NFPA-101 7.8, 7.8.1.3
 AND 7.9, 7.9.1.1,7.9.1.2 ETC WITH BATTERY BACK UP. THE
 STAIRS WILL REQUIRE BATTERY BACK UP ALONG WITH MAIN
 ELECTRICAL ROOMS, GENERATOR ROOMS, ELEVATOR EQUIPMENT
 ROOMS, FIRE PUMP ROOM (IN LATER COMMENT).
 PLEASE BE SURE TO SEE 700.12E, 700.16.
 PLEASE SUBMIT PHOTO-METRIC PLANS FOR ALL EGRESS. STAIRS
 REQUIRE 10FT CANDLES MINIMUM UNDER NORMAL AND IS
 PERMITTED TO GO DOWN TO 1FT CANDLE UNDER EMERGENCY
 CONDITIONS. THIS IS BASE ON AN AVERAGE.
 FBC 1006.2.3
 IF THE BUILDING WILL NOT BE OCCUPIED UNDER GENERATOR
 POWER A LETTER FROM OWNER STATING THE BUILDING WILL BE
 COMPLETELY EVACUATED WHEN UNDER GENERATOR BACK UP SHALL
 BE SUBMITTED. THIS INCLUDES ALL EMPLOYEES AND ANY OTHER
 PERSONNEL. IF THE BUILDING IS OCCUPIED UNDER GENERATOR
 AT ANYTIME NORMAL POWER IS LOST, BATTERY BACK UP
 FIXTURES FOR ALL MINIMUM LEVELS SHALL BE INSTALLED.
 ** PLEASE CALL TO GO OVER.
  
 13) NOTE: PLEASE KNOW THE OCCUPANCY OF THE BUILDING
 WOULD BE REQUIRED TO REMAIN AS A HOTEL. IF THE INTENT
 IS TO CHANGE THE OCCUPANCY TO RESIDENTIAL FOR PART OR
 ALL OF THE BUILDING AT A LATER DATE IT WOULD OF
 INTEREST TO LOOK UP FLORIDA STATE HOUSE BILL 7121 WHICH
 WOULD GREATLY AFFECT THIS PROJECT. THIS HOUSE BILL
 GREATLY AFFECTED NUMEROUS FLORIDA STATUTES FOR NOT ONLY
 HIGH-RISES BUT MANY OTHER BUILDINGS.
 ITEMS SUCH AS ON-SITE FUEL REQUIREMENT FOR HIGH-RISE
 BUILDING WOULD BE AFFECTED. IF THIS BUILDING WILL
 REMAIN A HOTEL THEN THIS COMMENT IS FOR INFORMATION
 ONLY.
 ALL BUILDINGS UNDER THE LIFE SAFETY CODE ARE TO BE
 EVACUATED WHEN UNDER LOSS OF POWER FROM THE NORMAL
 UTILITY SOURCE.
  
 14) NOTE: PLEASE SEE FLORIDA STATUTE 553.885. THIS
 BUILDING CONTAINS GAS APPLIANCES AND SHALL CONTAIN
 CARBON MONOXIDE DETECTORS/ALARMS. PLEASE SEE THE
 FOLLOWING WHICH WAS EXTRACTED FROM THE FLORIDA STATUTES
 ON LINE FOR EASE OF REVIEW OF REQUIREMENT.
  
 553.885 CARBON MONOXIDE ALARM REQUIRED.--
 (1) EVERY BUILDING, OTHER THAN A HOSPITAL, AN INPATIENT
 HOSPICE FACILITY, OR A NURSING HOME FACILITY LICENSED
 BY THE AGENCY FOR HEALTH CARE ADMINISTRATION, FOR WHICH
 A BUILDING PERMIT IS ISSUED FOR NEW CONSTRUCTION ON OR
 AFTER JULY 1, 2008, AND HAVING A FOSSIL-FUEL-BURNING
 HEATER OR APPLIANCE, A FIREPLACE, OR AN ATTACHED GARAGE
 SHALL HAVE AN APPROVED OPERATIONAL CARBON MONOXIDE
 ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES. FOR A NEW HOSPITAL, AN INPATIENT
 HOSPICE FACILITY, OR A NURSING HOME FACILITY LICENSED
 BY THE AGENCY FOR HEALTH CARE ADMINISTRATION, AN
 APPROVED OPERATIONAL CARBON MONOXIDE DETECTOR SHALL BE
 INSTALLED INSIDE OR DIRECTLY OUTSIDE OF EACH ROOM OR
 AREA WITHIN THE HOSPITAL OR FACILITY 1WHERE A
 FOSSIL-FUEL-BURNING HEATER, ENGINE, OR APPLIANCE IS
 LOCATED. THIS DETECTOR SHALL BE CONNECTED TO THE FIRE
 ALARM SYSTEM OF THE HOSPITAL OR FACILITY AS A
 SUPERVISORY SIGNAL.
  
  
 15) NOTE: THERE IS NOT ENOUGH INFORMATION SUBMITTED FOR
 FIRE PUMP AND FIRE PUMP CONTROLLER. THE RISER AND PLANS
 INDICATE A NEW FEED FROM FPL YET THE ROUTING IS SHOWN
 FROM ONE SIDE OF THE BUILDING TO THE OTHER UNDERGROUND.
 PLEASE CONFIRM THIS AS THIS IS AN EXISTING BUILDING.
 WILL ALL NEW SERVICE ENTRANCE CONDUCTORS BE ROUTED
 UNDERGROUND?
 PLEASE SEE NFPA-20 2003 FOR MANY OF THE FOLLOWING SUB
 COMMENTS.
 CHAPTERS 5,9 AND 10.
 THIS IS A CHANGE OF OCCUPANCY TO A HIGHER HAZARD, THE
 FIRE PUMP AND ALL ASSOCIATED EQUIPMENT SHALL MEET
 CURRENT CODES.
  
 A) PLEASE SEE 9.6.2.2 FOR REQUIRED ON-SITE FUEL FOR
 8HRS OF OPERATION ALONG WITH LOADS FOR LIFE SAFETY.
 PLEASE ALSO SEE SECTIONS FOR ADDITIONAL 5% FOR
 EXPANSION AND 5% FOR SUMP.
  
 B) PLEASE SEE 5.12.6 FOR REQUIRED DRAINAGE. NO
 INFORMATION WAS PROVIDED.
  
 C) PLEASE SEE 9.3.1 FOR FEEDERS OR SERVICE ENTRANCE
 CONDUCTORS. PLEASE ALSO SEE NFPA-70 695.6 A, B, AND C.
  
  
 D) PLEASE SEE LOCATION SHALL CONTAIN ACCESS DIRECTLY
 FROM OUTSIDE. THE ENTRANCE TO THIS ROOM AT THIS TIME IS
 NOT ACCEPTABLE. THIS ROUTE TAKES ANYONE THROUGH
 NUMEROUS LOCKED DOORS, EQUIPMENT ROOMS ETC.
 PLEASE SEE SECTION 9.2 AND COMMENTARY.
  
 E) PLANS SUBMITTED DO NOT CONTAIN ANY FIRE SPRINKLER
 PLANS AS REQUIRED. FS 633.
 PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT TO
 HOW THE EXISTING FIRE PUMP IS ADEQUATE FOR NEW
 SPRINKLER LOAD OF ADDITION.
 NO INFORMATION ON JOCKEY PUMP, OR PRESSURE MAINTENANCE
 PUMP WHICH IS A LEGALLY REQUIRED SYSTEM.
  
 F) PLANS/RISER INDICATES WHAT WOULD BE TWO METHODS OF
 OVER CURRENT PROTECTION FOR FIRE PUMP. THIS IS NOT
 NORMAL. PLEASE PROVIDE INFORMATION ON WHETHER OR NOT
 THE EXISTING FIRE PUMP CONTROLLER WITH ATS IS SERVICE
 ENTRANCE RATED WITH THE FACTORY LOCKED ROTOR SETTINGS.
 PLEASE ALSO SEE COMMENTS BELOW WITH RESPECT TO
 GROUNDING OF SERVICE WHICH IS NOT SHOWN. 695
 FBC 106.1.1
  
 G) PLEASE SEE 9.6.4 WITH RESPECT TO TRANSFER OF POWER.
  
 H) PLEASE SEE 5.12.4 AS BATTERY BACK UP LIGHTING IS
 REQUIRED. PLEASE BE SURE TO SEE 700.12E AND 700.16 FOR
 UNIT EQUIPMENT.
  
 ** THERE ARE NUMEROUS CODE SECTIONS AND UNANSWERED
 QUESTIONS OR INFORMATION NOT YET SHOWN OR SUBMITTED.
 PLEASE GO OVER NFPA-70 695, 701, ETC AND NFPA-20 (ALL).
  
 16) NOTE: PLEASE SEE NEC 250.20, 250.50, 250.24, 250.6
 ETC. A GROUNDED CONDUCTOR (NEUTRAL) IS ALWAYS REQUIRED
 TO THE FIRST MEANS OF SERVICE DISCONNECT EVEN WHEN ONLY
 FEEDING MOTOR LOADS. AS SHOWN THIS SERVICE FOR THE FIRE
 PUMP WOULD NOT BE GROUNDED AND DOES NOT FALL UNDER
 ELECTRICAL SYSTEMS WHICH ARE NOT TO BE GROUNDED.
 PLEASE REVISE RISER TO INCLUDED GROUNDED/NEUTRAL
 CONDUCTOR TO THE FIRST MEANS OF SERVICE DISCONNECT.
 PLEASE SEE PREVIOUS COMMENTS WITH RESPECT TO THE TWO
 MEANS OF OVER CURRENT PROTECTION.
  
 17) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING. ONCE AGAIN THIS IS A CHANGE
 IN OCCUPANCY TO A HIGHER HAZARD AND MUST MEET CURRENT
 CODES.
 GENERATOR, ATS DEVICES, FIRE PUMP, FIRE PUMP
 CONTROLLER, FUEL TANKS (REVIEWED BY
 OTHERS).110.3,695,90.7.
  
 18) NOTE: PLEASE SEE 230.95, 240.13 ETC AS THE MAIN
 SWITCHBOARD BEING DOES NOT INDICATE THE REQUIRED GROUND
 FAULT PROTECTION.
 ** IT IS IMPORTANT TO KNOW AS THE OVER CURRENT
 PROTECTION AND OTHER INFORMATION WAS NOT SUBMITTED FOR
 GENERATOR AND OTHER SYSTEMS THERE MAY BE A NEED TO
 INSTALL 4-POLE TRANSFER SWITCHES FOR SOME OF THE BACK
 UP SYSTEMS OR ALL. PLEASE SEE NEC 700.7D, 700.26 AND
 NFPA-110 6.2.15. GROUND FAULT PROTECTION IS REQUIRED ON
 MAIN DISTRIBUTION SYSTEM AND NOT ON BACK UP OF
 EMERGENCY/LIFE SAFETY SYSTEMS. HOWEVER GROUND FAULT
 SENSING IS A REQUIREMENT. PLEASE SEE WHITE PAPERS FROM
 LEADING MANUFACTURES SUCH AS ASCO, CATERPILLAR ETC.
 WHEN A SYSTEM HAS GROUND FAULT PROTECTION ON THE
 PRIMARY AND GROUND FAULT SENSING ON THE SECONDARY WHEN
 A FAULT OCCURS THERE IS A COORDINATION LOSS WHEN A
 SEPARATION OF THE NEUTRAL CONDUCTORS AND USE OF A
 4-POLE TRANSFER SWITCH IS NOT INSTALLED. THIS IS NOT ON
 ALL BACK UP SYSTEMS HOWEVER AS MUCH INFORMATION ON THE
 BACK UP IS NOT PROVIDED THIS IS NOTED AS IT MAY BE
 REQUIRED TO USE 4-POLE TRANSFER SWITCHES AND CREATE A
 SEPARATELY DERIVED GENERATOR GROUND.
  
 19) NOTE: PLEASE SEE 110.14, 240.21, 240.4, AND 310.16.
 ALL TAPPED CONDUCTORS ON THE SECONDARY SIDE OF ANY
 TRANSFORMER SHALL TERMINATE IN OVER CURRENT PROTECTION
 WHICH LIMITS THE LOAD ON THE TAPPED CONDUCTORS. THE
 500MCM INSTALLED FROM THE SECONDARY SIDE OF THE
 TRANSFORMERS AS SHOWN ON RISER ARE RATED AT 380AMPS
 WITH OVER CURRENT PROTECTION SET AT 400AMPS. THIS IS
 NOT PERMITTED. TYPICALLY WHEN EQUIPMENT IS BELOW
 800AMPS (240.4B) AND THE OVER CURRENT PROTECTION DOES
 COORDINATE WITH THE STANDARD OVER CURRENT PROTECTION IN
 240.6 YOU ARE PERMITTED TO GO TO THE NEXT STANDARD SIZE
 OF OVER CURRENT PROTECTION. HOWEVER THIS IS NOT
 PERMITTED ON THE SECONDARY SIDE OF TRANSFORMERS. THIS
 HAS BEEN GONE OVER WITH CODE PANELIST IN SEVERAL
 INTERNATIONAL ASSOCIATION OF ELECTRICAL INSPECTORS
 (IAEI) MEETINGS ON STATE, AND NATIONAL LEVELS.
 PLEASE ADJUST.
  
 20) NOTE: PLEASE PLACE NOTE ON PLANS FOR REQUIRED ARC
 FLASH SIGNAGE AND PROTECTION. 110.16
  
 21) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE RATING
 OF EQUIPMENT AND ROOM IN WHICH THE GENERATOR IS
 LOCATED. PLEASE SEE CHAPTER 7 OF NFPA-110.
 AS MOST OF THE NEEDED INFORMATION IS NOT SHOWN PLEASE
 SEE SOME OF THE ITEMS NEEDED ON PLANS LISTED BELOW.
 MANY OF THE SECTIONS BELOW WHICH ARE BEING GIVEN MAY
 ALSO RELATE TO OTHER TRADE REVIEWS HOWEVER THEY ALSO
 RELATE CLOSELY TO ELECTRICAL SYSTEMS, EQUIPMENT,
 DESIGNS ETC WHICH WILL BE AFFECTED BY MANY OF THESE
 ITEMS. THIS GENERATOR IS A LIFE SAFETY, AND LEGALLY
 REQUIRED EPSS. SEE CHAPTER 4,4.1 FOR CLASSIFICATIONS.
  
 A) THE LOCATION SHALL BE PER SECTION 7.2.
 7.2.1 THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR
 LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE
 PERMITTED TO BE INSTALLED IN THIS ROOM.
 7.2.1.1 THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE
 RATING OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED
 OUTSIDE THE BUILDING CAPABLE OF RESISTING THE ENTRANCE
 OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY
 LOCAL BUILDING CODES.
 7.2.1.2 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
 7.2.2 EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME
 ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS
 INSTALLED.
 7.2.2.1 TRANSFER SWITCHES SHALL BE PERMITTED TO BE
 INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE
 TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF
 NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN
 EQUIPMENT ENCLOSURES.
 7.2.3* THE ROOMS, SHELTERS, OR SEPARATE BUILDINGS
 HOUSING LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE
 DESIGNED AND LOCATED TO MINIMIZE THE DAMAGE FROM
 FLOODING, INCLUDING THAT CAUSED BY THE FOLLOWING:
 (1) FLOODING RESULTING FROM FIRE FIGHTING
 (2) SEWER WATER BACKUP
 (3) SIMILAR DISASTERS OR OCCURRENCES
 7.2.4* MINIMIZING THE POSSIBILITY OF DAMAGE RESULTING
 FROM INTERRUPTIONS OF THE EMERGENCY SOURCE SHALL BE A
 DESIGN CONSIDERATION FOR LEVEL 1 AND LEVEL 2 EPSS
 EQUIPMENT.
  
 ** PLEASE SEE COMMENTARY FOR ONE OF TWO ACCEPTABLE
 LEVELS. THE * 100YEAR STORM* LEVEL OR THE LEVEL SET BY
 THE *SLOSH* CHARTS BASED ON A CATEGORY 4 HURRICANE.
 (SEA, LAKE, OVERLAND SURGES BY HURRICANES).
  
 B) PLEASE BE SURE TO SEE 7.3.1 THE LEVEL 1 OR LEVEL 2
 EPS EQUIPMENT LOCATION(S) SHALL BE PROVIDED WITH
 BATTERY-POWERED EMERGENCY LIGHTING.
  
 C) PLEASE SEE 7.3.3 AS THE MINIMUM FOOT CANDLES SHALL
 BE 30 FT CANDLES. PLEASE PROVIDE PHOTO-METRICS SHOWING
 LEVELS.
  
 D) PLEASE BE SURE TO SEE 7.5 FOR VIBRATION ISOLATORS
 FROM STRUCTURE ETC.
  
 E) PLEASE SEE 7.7 FOR REQUIRED VENTILATION DIRECTLY
 FROM OUTSIDE. PLEASE ALSO SEE 7.10 FOR EXHAUST SYSTEMS.
 THIS COULD GREATLY AFFECT THE DESIGN. SEE COMMENTS FROM
 OTHER TRADES SUCH AS MECHANICAL REVIEWER.
  
 F) PLEASE SEE 7.8 FOR COOLING WHICH DOES NOT PERMIT
 RELYING ON UTILITY.
  
 G) PLEASE SEE 7.9 FOR FUEL PIPING. (INFORMATION YET
 THIS WILL AFFECT ELECTRICAL PLANS.). ANY REMOTE FILLING
 WITH ELECTRICAL SHUT OFF, FILL ALARMS ETC IS NOT KNOWN
 AT THIS TIME. NOT ENOUGH INFORMATION SHOWN.
  
 22) NOTE: PLEASE SUPPLY LIGHTING PHOTO-METRICS LEVELS
 FOR ELEVATOR PITS. PLEASE SEE NEC 620.23 COMMENTARY,
 ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.
  
  
 23) NOTE: PLEASE BE SURE TO SHOW ALL HORN AND STROBE
 DEVICES IN COMPLIANCE FOR MINIMUMS PER FBC 11-4.28.1,
 .2 AND .3.
 PLEASE BE SURE ALL LOCATIONS, HEIGHTS AND LEVELS ARE
 INDICATED.
 KEEP IN MIND THERE ARE MANY CIRCUMSTANCES IN WHICH THE
 FLORIDA BUILDING CODE IS MORE RESTRICTIVE THAN NFPA-72.
  
 24) NOTE: PLEASE SEE FBC 3006.2 FOR VENTILATION
 REQUIREMENTS OF ELEVATOR EQUIPMENT/MACHINE ROOMS. THE
 ELECTRICAL AND MECHANICAL PLANS ARE NOT REAL CLEAR ON
 ANY NEW OR EXISTING SYSTEMS FOR NEW AND EXISTING
 EQUIPMENT ROOMS.
  
 25) NOTE: PLEASE KNOW THAT ANY LIGHTING OUTSIDE THE
 PROPERTY LINE SHALL BE UNDER SEPARATE PERMITS. THESE
 WOULD BE CONSIDERED RIGHT OF WAY AREAS AND ARE NOT
 PERMITTED TO BE FED FROM THIS BUILDING ELECTRICAL
 SYSTEM.
 ** NOTE FOR INFORMATION.
  
 26) NOTE: PLEASE KNOW THAT ANY LIGHTNING PROTECTION
 SYSTEM WHICH MAY BE PROPOSED SHALL BE UNDER SEPARATE
 PERMIT. ANY PROPOSED SYSTEM SHALL ALSO COMPLY WITH
 NFPA-780.
 PLEASE PLACE NOT ON PLANS ACCORDINGLY.
 THERE ARE NUMEROUS SYSTEMS WHICH ARE IN THE MARKET
 PLACE WHICH DO NOT CONFORM TO ANY ADOPTED STANDARD OR
 CODE.
  
 27) NOTE: PLEASE KNOW THE POOL WILL BE REQUIRED TO BE
 UNDER SEPARATE PERMIT. PLEASE PLACED NOTE ON PLANS.
 PLEASE ALSO KNOW THAT PLANS SHALL CLEARLY STATE NO DUSK
 TO DAWN SWIMMING OR PLEASE SUBMIT PHOTO-METRICS TO PALM
 BEACH COUNT HEALTH DEPARTMENT FOR REVIEW AND STAMPING.
 ** PHOTO-METRICS FOR EGRESS AREAS ARE ALREADY NEEDED
 AND MAY USE THE SAME LAYOUT. PLEASE VERIFY LIGHTING
 LEVELS WITH PBCHD.
  
 28) NOTE: THE LOW VOLTAGE SYSTEMS AS SUBMITTED WILL BE
 UNDER SEPARATE PERMITS. PLANS MAY COME IN WITH BASE
 BUILDING AND WILL BE REVIEWED. WHEN PERMIT APPLICATION
 IS MADE FOR THE LOW VOLTAGE PERMITS CONTRACTOR WILL
 REFERENCE BASE BUILDING PLANS AND PERMIT IS ISSUED AS A
 *TURNAROUND PERMIT*.
  
 29) NOTE: PLEASE BE SURE TO SHOW ALL CONDUCTORS ON
 COMPLETED PANELS SCHEDULES PER 310.16, 240.4, AND 408.4
  
 30) NOTE: PLEASE PROVIDE ALL LOADS ON ALL PANELS.
 PLEASE BE SURE TO COMPLETE LOAD CALCULATIONS.
 NEC 220
 FBC 106.1.1,106.3.5.1.2 ADDITIONAL INFORMATION,
 CLARITY, COORDINATION.
  
 31) NOTE: PLEASE SEE 210.8B2 FOR REQUIRED GFI
 PROTECTION FOR ALL 15/20AMP 120 CIRCUITS IN
 KITCHEN/SERVING AREAS.
 THIS IS REQUIRED FOR ALL WHETHER OR NOT FEEDING COUNTER
 SPACES.
  
 32) NOTE: PLEASE PROVIDE DETAIL FOR ALL VERTICAL
 SUPPORT OF CONDUCTORS PER 300.19
  
 33) NOTE: PLEASE PROVIDE BUS-DUCT CURBING DETAIL.
 PLEASE SEE 368.10C1 AND 2
  
 34) NOTE: PLEASE SEE NEC 680.22 FOR TYPES OF FIXTURES
 AND LOCATIONS OF FIXTURES AROUND POOL. PLEASE BE SURE
 TO ALSO SEE 411.4B FOR LV TYPE FIXTURES. AS THE
 LIGHTING FOR POOL AREA IS NOT COMPLETE ALONE WITH A
 FIXTURE LEGEND CODE COMPLIANCE FOR MANY ITEMS CAN NOT
 BE DETERMINED.
  
 35) NOTE: PLEASE BE SURE TO SUBMIT WIND LOAD
 INFORMATION FOR ROOF TOP AND OTHER LIGHT POLES.
 FBC 1609
 FBC 106.1.14
 PLEASE BE SURE TO INCLUDE THE EFFECTIVE PROJECTED AREAS
 OF FIXTURES.
  
 36) NOTE: PLEASE SEE 250.50, 250.66, THE GROUNDING
 ELECTRODE SIZE TO FOOTER STEEL SHALL BE BASED ON
 250.66. THIS IS NOT THE SOLE CONNECTION.
  
 37) NOTE: PLEASE PROVIDE A GROUNDING ELECTRODE RISER
 FOR ATTACHMENT OF ALL SYSTEMS. 250.58. THIS CAN BE
 SHOWN ON RISER SHEET.
 250.20.250.30, 250.50 ETC
  
 38) NOTE: PLEASE PROVIDE NOTE FOR COLOR CODING OF
 277/480V SYSTEMS AS FOLLOWS. BROWN, PURPLE, YELLOW. ALL
 EXISTING SYSTEMS IN THE CITY OF WEST PALM BEACH ARE
 BASED ON THIS COLOR CODING DUE TO PREVIOUS LOCAL
 AMENDMENTS. THE NEC DOES NOT CONTAIN COLOR CODING FOR
 SUCH SYSTEMS AND ORANGE IS FOR OPEN DELTA HIGH LEG
 SYSTEMS. IN THE INTEREST OF CONSISTENCY AND SAFETY OF
 ELECTRICAL SYSTEMS PLEASE ADJUST SPECS AND PLEASE ADD
 NOTES TO RISER AND/OR ELECTRICAL NOTES.
 90.4.
  
 39) NOTE: PLEASE PROVIDE BACK UP INFORMATION ON FIRE
 ALARM PANELS. I COULD NOT LOCATE BACK UP BATTERY BACK
 UP NOTES ON PLANS. THE USE OF THE GENERATOR AS THE
 PRIMARY BACK UP IS NOT PERMITTED AS NOTED ABOVE WITH
 RESPECT TO OCCUPANCY OF THE BUILDING. NFPA-72 4.4.1.3
  
 40) NOTE: PLEASE SEE BUILDING REVIEW NOTES WITH RESPECT
 TO REQUIRED NOTES ON PLANS WITH RESPECT TO FS 633 FOR
 FIRE AND LIFE SAFETY DESIGN.
 FBC 109.3.6.4.4.
  
 41) NOTE: PLEASE CLARIFY WHY THE MAIN SWITCH BOARD
 EQUIPMENT LOCATED ON E104 IS SHOWN AS THREE YET RISER
 IS INCOMPLETE WITH THE SAME. THE PLANS ACTUALLY STATE
 TWO SECTIONS?
 110.3, 230.70 ETC
 FBC 106.1.1 FOR ADDITIONAL INFORMATION AND CLARITY.
  
 42) NOTE: PLEASE 210.63, 210.8B3, 4 AND 5. PLEASE BE
 SURE TO COMPLETE ALL REQUIRED RECEPTACLES.
  
 43) NOTE: PLEASE BE SURE TO SEE 13-415.1,
 13-415.1.ABC.1.3 FOR AUTOMATED LIGHTING CONTROLS
 REQUIRED IN HOTEL ROOMS.
  
 44) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL 1KP
 SHOWN AS 150AMP ON RISER YET 200AMP ON PANEL SCHEDULE.
 230,220,408
 FBC 106.1.1 FOR COORDINATION AND CLARITY.
  
 45) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL
 SCHEDULE FOR RB YET NOT ON RISER.
 230, 215, 220, 408 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 46) NOTE: PLEASE COORDINATE RISER AND PANELS. SAME AS
 NOTED ABOVE PANEL 2H SHOWN AS 200AMP AND 150AMP. IF 2H
 IS TYPICAL AS NOTED FOR OTHER FLOORS COORDINATION IS
 NEEDED AS THE OTHER FLOORS ARE SHOWN AS 150AMP ON
 RISER.
 230,220,408 ETC
 FBC 106.1.1
  
 47) NOTE: PLEASE COORDINATE ALL EQUIPMENT AS NOTED IN
 NOTES 44,45 AND 46 ABOVE. THERE ARE OTHER PANELS AND
 EQUIPMENT WHICH ARE NOT THE SAME.
 THERE ARE SEVERAL OTHERS.
  
 **** AS NOTED IN THE BEGINNING OF THE REVIEW COMMENTS.
 IT IS IMPORTANT TO SUBMIT 100% PLANS AND DOCUMENTS FOR
 A COMPLETE REVIEW FOR CODE COMPLIANCE. WHEN SUBMITTING
 FOR PERMIT THIS WILL GREATLY AFFECT THE REVIEWS,
 ISSUANCE, DELAYS AND POSSIBLE FEES ASSOCIATED WITH
 PROJECT. THE NAME AND CONTACT INFORMATION WILL BE GIVEN
 BELOW. IF CONTACTING REVIEWER BY PHONE AND VOICEMAIL IS
 ENCOUNTERED PLEASE LEAVE A MESSAGE ALONG WITH CONTACT
 PHONE NUMBER. THE CALL WILL BE RETURNED AS SOON AS
 POSSIBLE.
 COMMUNICATION IS THE KEY TO THE SUCCESS OF THIS PROJECT
 AS WITH ANY OTHERS.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  