| 2009-07-10 16:48:28 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW 2ND |
| | CHECKLIST. |
| | 2004 FL RESIDENTIAL CODE WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS (REPEAT COMMENT, NOT |
| | ADDRESSED AT ALL). REQUIRED BY SEC. 13-103.3 OF 2004 |
| | FBC PRIOR TO RECEIVE A BUILDING PERMIT. |
| | NOTE: MAKE SURE CORRECT 2004 REVISED FORM IS USED AND |
| | ALL INFORMATION AND REQUIRED SIGNATURES ARE PROVIDED. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | 3- PROVIDE ATTIC ACCESS FOR NEW ROOF AREA AS REQUIRED |
| | BY SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE. (REPEAT |
| | COMMENT, NOT ADDRESSED AT ALL). |
| | |
| | 4- SPECIFY HOW ARE CONCRETE TILES FASTENED AS REQUIRED |
| | BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC. (REPEAT |
| | COMMENT). INFORMATION SUBMITTED DON'T PROVIDE ENOUGH |
| | INFORMATION TO DETERMINE IF THE DESIGN PRESSURES OF |
| | SEC. R301 ARE MET WITH THE PROPOSED INSTALLATION. SEE |
| | PRODUCT APPROVAL TO DETERMINE IF PROPOSED TYPE OF |
| | FASTENERS WILL MEET THE UPLIFT MOMENT. |
| | |
| | 5- PROVIDE 2 COPIES OF ICYNENE INSULATION |
| | SPECIFICATIONS. ONLY ONE WAS PROVIDED. |
| | |
| | 6- FLORIDA PRODUCT APPROVAL SUBMITTED FOR ROOFING TILES |
| | IS FOR 2007 CODE VERSION AND IS PENDING FBC APPROVAL. |
| | SEE PRODUCT APPROVAL SUBMITTED. THIS PROJECT IS |
| | REVIEWED UNDER THE 2004 FBC. PROVIDE 2004 PRODUCT |
| | APPROVAL TO MATCH PLANS. |
| | |
| | 7- PROVIDE 2 COPIES OF FIREPLACE SPECIFICATIONS. ONLY |
| | ONE WAS SUBMITTED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |