| Plan Review Notes For Permit 08110263 |
| Permit Number |
08110263 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-03-02 17:24:35 | *** REDLINED PLANS*** | | | | | | *NOTE: E-1 WAS REVISED FOR HEIGHTS OF DEVICES FOR ADA | | | COMPLIANCE ALONG WITH PULL STATIONS HOWEVER THE MINIMUM | | | CANDELA LEVELS AS NOTED IN PREVIOUS REVIEWS WERE NOT | | | INDICATED. | | | THE MINIMUM CD LEVEL IS 75 PER FBC 11-4.28.3(4). | | | REDLINED ON SHEET E-1. PLANS STAMPED OK. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | | | | |
|