| 2008-12-03 08:40:59 | |
| | ** DENIED REVIEW** |
| | |
| | |
| | |
| | 1) NOTE: PLANS SUBMITTED FOR PLAN REVIEW ONLY. EVEN |
| | ONCE ALL ITEMS FOR CODE COMPLIANCE ARE MET AND PERMIT |
| | APPLICATION HAS NOT BEEN MADE REVIEW WILL REMAIN IN |
| | FAILED STATUS. ITEMS SUCH AS LICENSING, CODES ETC ARE |
| | REVIEWED AT TIME OF APPLICATION. |
| | |
| | 2) NOTE: PLEASE BE SURE THE RELEVANT CODES ARE |
| | ADJUSTED. CODES ON THE COVER SHEET COMPARED TO |
| | ELECTRICAL PLANS FOR EXAMPLES ARE NOT THE SAME. |
| | PLEASE SEE COVER SHEET WHICH SHOULD REFLECT 2004 FBC W/ |
| | 2007 REVISIONS. |
| | PLEASE SEE COVER SHEET WHICH SHOULD REFLECT THE 2005 |
| | NFPA-70 (NATIONAL ELECTRICAL CODE) PLANS SHOW 2002. |
| | LIFE SAFETY SHEET DOES CONTAIN THE CORRECT 2005 NEC |
| | HOWEVER ELECTRICAL PLANS STATE *LATEST*. |
| | PLEASE ADJUST ALL SHEETS AS APPLICABLE. |
| | |
| | 3) NOTE: PLEASE SEE FBC 13-101.1.3 AND SECTION 202 FOR |
| | DEFINITIONS. PLEASE EXPLAIN HOW FLA-COM FORM *B* BE |
| | USED. PLEASE KNOW BASED ON DEFINITIONS, PLANS |
| | SUBMITTED, NO PERMIT APPLICATION FOR VALUE THE METHOD |
| | *B* MAY NOT BE USED. |
| | PLEASE SEE 13-400.C FOR EXAMPLE WHICH MENTIONS WHEN NOT |
| | MEETING THE DEFINITION OF A RENOVATED BUILDING, BASIC |
| | PRESCRIPTIVE REQUIREMENTS MUST BE MET. |
| | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER |
| | TABLES 13-415.2.B, OR 13-415.2.C. PLEASE CALL TO GO |
| | OVER AS SOME INFORMATION ON E3 IS SHOWN. |
| | |
| | 4) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE TIMER TYPE |
| | DEVICES AS SHOWN ARE NOT PERMITTED TO BE THE TYPE WHICH |
| | WOULD REQUIRE TWISTING ACTION ETC. PLEASE SEE SECTION |
| | GIVEN AS ALL CONTROLS FOR LIGHTING ETC NEED TO MEET ADA |
| | REQUIREMENTS. |
| | PLEASE ADJUST NOTES AND SPECIFICS FOR DEVICES. |
| | |
| | 5) NOTE: PLEASE PROVIDE WALL/FLOOR PENETRATION DETAILS |
| | FOR LISTED WALL ASSEMBLIES. 300.21. PLEASE SEE |
| | COMMENTARY IN NEC HANDBOOK WHICH WILL REFERENCE |
| | ACCEPTABLE STANDARDS. |
| | IF THE SAME DETAILS ON A4 ARE TO BE USED PLEASE MAKE |
| | NOTE ON ELECTRICAL PLANS REFERENCING TO THIS SHEET. |
| | |
| | 6) NOTE: PLEASE CLARIFY THE SECTION ON E3 SHOWN AS |
| | *DEMAND LOAD* WHICH SHOWS EXISTING FEEDERS AS 4- |
| | 500MCM. WHAT FEEDERS ARE THESE AS THE NEW FEEDERS ON |
| | RISER FROM GUTTER ARE NOT THE SAME. |
| | |
| | 7) NOTE: PLEASE NOTE A *FLOATING NEUTRAL KIT* REQUIRED |
| | AT THE TENANT METER. 250.6,250.24 ETC. |
| | |
| | 8) NOTE: PLEASE SHOW ANY NEW OR EXISTING FIRE ALARM |
| | DEVICES. PLEASE BE SURE TO SEE FBC 11-4.28.1,.2 AND .3 |
| | FOR MINIMUM LEVELS FOR ADA COMPLIANCE. |
| | (IF APPLICABLE IN THIS BUILDING). |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |