| 2008-12-10 07:49:40 | BUILDING PLAN REVIEW |
| | PERMIT: 08110263 |
| | ADD: 4631 N CONGRESS AV |
| | CONT: "PLAN REVIEW/ |
| | TEL: (561)635-6935/ NAT HEALY |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1C) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS NOT INCLUDING ALL |
| | AMENDMENTS. |
| | |
| | 2) ENERGY CALCULATIONS PLEASE REVIEW 13-400.0.C.4 |
| | RENOVATED BUILDINGS. |
| | RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION |
| | 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR |
| | COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE |
| | ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR |
| | THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT |
| | MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW |
| | HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING |
| | SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE |
| | MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE |
| | SYSTEM(S) BEING CHANGED. |
| | |
| | RENOVATION. ANY STRUCTURAL REPAIR, RECONSTRUCTION OR |
| | RESTORATION TO A STRUCTURE, THE COSTS OF WHICH EQUALS |
| | OR EXCEEDS, OVER A ONE-YEAR PERIOD, A CUMULATIVE TOTAL |
| | OF 30 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE |
| | WHEN THAT VALUE IS ASSESSED, EITHER: |
| | 1. BEFORE THE IMPROVEMENT OR REPAIR IS STARTED; OR |
| | 2. BEFORE THE DAMAGE OCCURRED, IF THE STRUCTURE HAS |
| | BEEN DAMAGED. |
| | FOR THE PURPOSES OF THIS CODE, RENOVATION OCCURS WHEN |
| | THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR |
| | OTHER STRUCTURAL PART OR MECHANICAL SYSTEM OF THE |
| | BUILDING COMMENCES, WHETHER OR NOT THAT ALTERATION |
| | AFFECTS THE EXTERNAL DIMENSIONS OF THE STRUCTURE. |
| | |
| | WITH THIS ONLY BEING A PLAN REVIEW AND NOT A PERMIT |
| | APPLICATION IT APPEARS THE WORK TO BE COVERED UNDER |
| | THIS PERMIT WILL NOT MEET THE 30% OF THE VALUE OF THE |
| | BUILDING, REQUIRING FORM 400 C, ONCE THE VALUE IS KNOWN |
| | WE WILL HAVE THE CRITERIA TO ASSESS WHICH METHOD B OR C |
| | SHOULD HAVE BEEN USED. |
| | |
| | 3) SHEET A-1 DOES NOT INDICATE WHAT AREAS ARE ALREADY |
| | THERE AND WHAT IS TO BE CONSIDERED NEW WORK. ADDITIONAL |
| | INFORMATION REQUIRED 106.1.2. |
| | |
| | 4) SHEET A-3 DETAIL 4 & 5 BOTH INDICATE SOFFIT DETAILS |
| | BUT DO NOT PROVIDE WHAT TYPE OF ATTACHMENT METHOD WILL |
| | BE USED TO INSTALL SOFFITS TO DECK ABOVE? 2508.1, TABLE |
| | 2508.1 & GA-216. |
| | |
| | 5) SHEET A-4 INDICATES WALL ASSEMBLIES FOR RATED WALLS |
| | BUT DOES NOT PROVIDE FLOOR PENETRATIONS FOR HORIZONTAL |
| | ASSEMBLIES. 712.4.1.2. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |