| 2009-02-02 15:22:54 | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: *** SAME EXACT NOTES FROM PREVIOUS REVIEW. NO |
| | CHANGES WERE MADE OR CORRECTIONS MADE TO PLANS. THIS IS |
| | A CHANGE IN OCCUPANCY TO LOCATION. PLEASE SEE FBC |
| | CHAPTER 3, 13 FOR CHANGES IN OCCUPANCY. PLEASE SEE FBC |
| | EXISTING BUILDING CODE CHAPTER 8 FOR CHANGES IN |
| | OCCUPANCY. |
| | PLEASE SEE NFPA-72, 70, 101 ALSO FOR MINIMUM |
| | REQUIREMENTS. |
| | PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR ALL NEW AS |
| | THIS IS NOW A COMMERCIAL OCCUPANCY AND ALL PLANS NEED |
| | TO SHOW MINIMUM COMPLIANCE WITH THIS TYPE OF OCCUPANCY. |
| | LOAD CALCULATIONS, NEC 220 |
| | CIRCUITING, NEC 240.4,310.16,408.4 ETC |
| | ENERGY EFFICIENCY, CHAPTER 13, LIGHTING CONTROLS |
| | 13-415.1.ABC.1 |
| | PANELS, 408.4, |
| | PERFORMANCE CALCULATIONS, 13-415.2 |
| | NOTES ARE BROAD AS NO INFORMATION WAS SHOWN. |
| | ** MAY NOT QUOTE CODES FOR MINIMUM DESIGN IN LIEU OF |
| | SPECIFIC CODE COMPLIANCE DETAILS. |
| | |
| | |
| | ** IT IS NOTED ONCE AGAIN THAT AS THERE ARE SEVERAL |
| | UNKNOWN FACTORS AND MISSING INFORMATION, THERE MAY VERY |
| | WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN |
| | NOT BE MADE AT THIS TIME. |
| | |
| | 2) NOTE: PLANS WHICH WERE BROUGHT BACK IN AND SUBMITTED |
| | ARE NOT SIGNED, DATED OR SEALED BY THE DESIGN |
| | PROFESSIONAL OF RECORD. |
| | SEE FS 481.221 |
| | |
| | 3) NOTE: VALUE FOR SCOPE OF WORK INCREASED HOWEVER WORK |
| | AS NOTED IS STILL LOW AND UNKNOWN WORK IS NOT INCLUDED. |
| | FBC 108.3 |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |