| Date |
Text |
| 2008-11-19 09:36:00 | ** FAILED REVIEW ** |
| | |
| | ** |
| | |
| | |
| | 1) NOTE: PLANS SHOW REMOVAL OF KITCHENS FROM BOTH UNITS |
| | WHICH ARE DWELLING UNITS. WHAT WILL THE NEW OCCUPANCY |
| | BE? FBC 303.1 |
| | THE WALLS AND OTHER LOCATIONS ARE BEING FINISHED TO AND |
| | END USE HOWEVER PLEASE SEE SECTION ABOVE AS THE |
| | OCCUPANCY WHICH WILL BE CHANGING FROM DWELLING TO |
| | OTHER. |
| | PLEASE SEE FBC CHAPTER 13 FOR ANY NEW BEING INSTALLED. |
| | PLEASE SEE FBC EXISTING BUILDING CODE CHAPTER 8 FOR USE |
| | AND CLASSIFICATION TO POSSIBLE HIGHER HAZARD. |
| | |
| | 2) NOTE: PLANS WILL BE REQUIRED TO SHOW THE FOLLOWING |
| | CODES: |
| | 2002 NFPA_72 |
| | 2003 NFPA-101 |
| | 2005 NFPA-70 |
| | |
| | 3) NOTE: PLEASE SEE CHAPTER 9 OF THE FBC FOR FIRE ALARM |
| | DEVICES ALONG WITH CHAPTER 11, SPECIFICALLY |
| | 11-4.28.1,.2 AND .3. |
| | |
| | 4) NOTE: THE APPLIED VALUATION SHALL INCLUDE ALL LABOR, |
| | MATERIALS, EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF |
| | THESE ITEMS ARE OWNER SUPPLIED. |
| | THE APPLIED VALUE OF $2,300.00 IS LOW. |
| | FBC 108.3 |
| | |
| | 5) NOTE: IT IS IMPORTANT TO KNOW AS THERE ARE SEVERAL |
| | UNKNOWN FACTORS AT THIS TIME THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH COULD NOT BE |
| | MADE AT THIS TIME. |
| | PLEASE CALL TO GO OVER ANY ITEMS OR QUESTIONS WHICH MAY |
| | HELP ALLEVIATE ANY DELAY OF THE PROJECT. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |