| 2009-03-12 15:01:05 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 EXISTING BLDG CODE |
| | FBC-2004 CHAPTER 1 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. PLEASE INDICATE CODE IN EFFECT WHEN DESIGNING THE |
| | PLANS. SHOULD READ FBC-2004 WITH 2007 REVISIONS. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 2. PLEASE INDICATE THE LEVEL OF ALTERATION. SECTION |
| | 301.5. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 3. PLEASE SUBMIT A SANITARY RISER DIAGRAM SHOWING ALL |
| | PIPE SIZES, TRAPS & VENTS AS WELL AS THE CONNECTION |
| | POINT TO EXISTING DRAIN LINES AND VENTS. SECTION |
| | 106.3.5.1.3. |
| | ****SANITARY RISER DIAGRAM SUBMITTED, THE PRINTED NAME |
| | & SIGNATURE OF PERSON RESPONSIBLE FOR THE RISER DESIGN |
| | SHALL BE ON EACH COPY OF THE RISER DIAGRAM. SECTION |
| | 106.3.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |