2009-03-10 07:46:09BUILDING PLAN REVIEW
 PERMIT: 08110243
 ADD: 464 FERN ST.
 CONT: NETCO TEK, INC.
 TEL: (561)307-8766
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3/10/09
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE INDICATED ON THE PLANS.
  
 3) *NO RESOIBSE NOT ADDRESSED* 2004 FBC EXISTING 301.5
 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. INDICATE THE
 LEVEL OF ALTERATION ON THE DRAWINGS.
  
 4) *NOT ADDRESSED* FBC 11-4.17.3 THE GRAB BARS SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH FIGURE 30(A) AND FIGURE
 30 (E).
  
 5) *NOT ADDRESSED* FBC 11-4.16.5 FLUSH CONTROLS SHALL
 BE HAND OPERATED OR AUTOMATIC AND SHALL COMPLY WITH
 SECTION 11-4.27.4. CONTROLS FOR FLUSH VALVES SHALL BE
 MOUNTED ON THE WIDE SIDE OF TOILET AREAS NO MORE THAN
 44 INCHES ABOVE THE FLOOR. THE FLUSH CONTROL FOR THE
 TOILET IS SHOWN ON THE NARROW SIDE OF THE WALL.
  
 6) *NOT ADDRESSED* PLEASE INDICATE WHAT MATERIALS WILL
 BE USED TO CONSTRUCT THE NEW WALLS, AND SHOW HOW THE
 WALLS WILL BE FASTENED TO THE FLOOR AND STRUCTURE
 ABOVE. 106.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE & EXTENT OF THE WORK
 PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 AND RULES AND REGULATIONS AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  
  