| 2009-03-10 07:46:09 | BUILDING PLAN REVIEW |
| | PERMIT: 08110243 |
| | ADD: 464 FERN ST. |
| | CONT: NETCO TEK, INC. |
| | TEL: (561)307-8766 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3/10/09 |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| | SHALL BE INDICATED ON THE PLANS. |
| | |
| | 3) *NO RESOIBSE NOT ADDRESSED* 2004 FBC EXISTING 301.5 |
| | A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A |
| | COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. INDICATE THE |
| | LEVEL OF ALTERATION ON THE DRAWINGS. |
| | |
| | 4) *NOT ADDRESSED* FBC 11-4.17.3 THE GRAB BARS SHALL BE |
| | CONSTRUCTED IN ACCORDANCE WITH FIGURE 30(A) AND FIGURE |
| | 30 (E). |
| | |
| | 5) *NOT ADDRESSED* FBC 11-4.16.5 FLUSH CONTROLS SHALL |
| | BE HAND OPERATED OR AUTOMATIC AND SHALL COMPLY WITH |
| | SECTION 11-4.27.4. CONTROLS FOR FLUSH VALVES SHALL BE |
| | MOUNTED ON THE WIDE SIDE OF TOILET AREAS NO MORE THAN |
| | 44 INCHES ABOVE THE FLOOR. THE FLUSH CONTROL FOR THE |
| | TOILET IS SHOWN ON THE NARROW SIDE OF THE WALL. |
| | |
| | 6) *NOT ADDRESSED* PLEASE INDICATE WHAT MATERIALS WILL |
| | BE USED TO CONSTRUCT THE NEW WALLS, AND SHOW HOW THE |
| | WALLS WILL BE FASTENED TO THE FLOOR AND STRUCTURE |
| | ABOVE. 106.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7) 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE & EXTENT OF THE WORK |
| | PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | AND RULES AND REGULATIONS AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | PHONE (561)805-6726 |
| | FAX (561) 805-6676 |