| 2008-11-19 11:45:08 | |
| | |
| | |
| | ** FAILED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS SUBMITTED DO NOT CONTAIN |
| | ANY TITLE BLOCKS AS REQUIRED PER FAC 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE THE SEAL IN USE ON THE SIGNED, |
| | DATED AND SEALED PLANS HAS NOT BEEN A VALID SEAL IN THE |
| | STATE OF FLORIDA SINCE THE RULING FROM THE FLORIDA |
| | BOARD OF ENGINEERS IN FEBRUARY 2004. THE STATE GAVE AN |
| | EXTENSION TO DECEMBER 31ST 2005 HOWEVER NO USE OF THE |
| | SEAL AS SUBMITTED MAY BE USED AFTER THAT DATE ANYWHERE |
| | IN THE STATE OF FLORIDA. |
| | THIS IS NOT PERMITTED PER THE FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.001 AND FLORIDA STATUTES 471.025. THE |
| | LICENSE IS STILL CURRENT AND ACTIVE WITH THE STATE, |
| | PLEASE RENEW SEAL. |
| | |
| | 2) NOTE: PERMIT APPLICATION SUBMITTED CLEARLY STATES TO |
| | REMODEL BATHROOM, REMOVING WALL ETC HOWEVER NO DETAIL |
| | WAS SHOWN FOR ANY ELECTRICAL SCOPE OF WORK BEING |
| | REMOVED OR NEW BEING INSTALLED. |
| | PLANS SHOW THE DEMOLITION WORK HOWEVER NOT THE NEW |
| | DETAILS FOR NEW WORK. |
| | PLEASE BE SURE TO SEE FBC 13-415.1.ABC.1.1,.1.2 FOR ANY |
| | NEW LIGHTING CONTROL TO MEET PRESCRIPTIVE REQUIREMENTS. |
| | PLEASE SEE NFPA-101 7.8 FOR REQUIRED LIGHTING FOR |
| | EGRESS EVEN UNDER NORMAL OCCUPANCY. |
| | PLEASE SUBMIT PLANS FOR COMPLETION OF WORK. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |