2008-11-19 11:40:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. PLEASE COMPLETE THE INSTALLATION SCHEDULE. ONE
 COLUMN WHICH IS REQUIRED TO DETERMINE CODE COMPLIANCE
 WAS LEFT BLANK. THE SHUTTER CONNECTION MOUNTING TYPE
 SHOULD CORRELATE WITH THE ANCHOR CHARTS. FOR INSTANCE,
 CEILING MOUNT 5 WAS CIRCLED, SO THIS MAY BE THE TOP
 CONNECTION.
  
 2. PLEASE PROVIDE INFORMATION REGARDING SUBSTRATE; HOW
 HAVE YOU DETERMINED THAT THE SUBSTRATE IS CONCRETE, AND
 THAT THE CONCRETE MEETS THE REQUIRED STRENGTH OF 3KSI?
 SEE SHEET 11, ITEM 1(A).
  
 3. A 2" EDGE DISTANCE REQUIRES A FACTOR OF .50, SEE
 SHEET 11.
  
 4. SEE OPENING 2, CLARIFY HOW A 60" OPENING CAN HAVE A
 SPAN OF 60".
  
 5. TWO COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FOR
 PERMIT ISSUANCE. ONLY ONE INSTALLATION SCHEDULE WAS
 PROVIDED.
  
  