| 2008-12-29 16:03:57 | ** DENIED REVIEW ** |
| | |
| | SOME NOTES FORM PREVIOUS REVIEW ARE STILL IN NEED OF |
| | ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS REVIEW IN WHICH |
| | THERE WAS A NOTE ** IMPORTANT**. THIS WAS NOTED SO THAT |
| | ALL OLD/VOIDED SHEETS WERE TO BE REMOVED FROM SETS AND |
| | FOR ALL NEW REVISED SHEETS TO BE INSERTED INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. THIS WAS NOT DONE IN FACT |
| | THE NEW SHEET WERE JUST PLACED ON TOP OF THE OLD SETS. |
| | PLEASE BE SURE THIS ID DONE IN A NEAT AND ORDERLY |
| | FASHION WITH REVISED PLANS. |
| | |
| | 2) NOTE: PERMIT APPLICATION HAS NOT BEEN MADE AT THIS |
| | TIME. PLEASE KNOW THE FLORIDA BUILDING CODE WILL BE |
| | CHANGING ON MATCH 1ST, 2009. |
| | ONLY ONCE PERMIT APPLICATION IS MADE BY LICENSED |
| | CONTRACTOR AND ALL CODE COMPLIANCE COMMENTS ARE |
| | ADDRESSED WILL THE REVIEW GO INTO A PASSED STATUS. |
| | THERE ARE MANY ASPECTS OF THE REVIEW WHICH ENTAIL |
| | REVIEW OF ALL LICENSING INCLUDING THAT OF DESIGNERS AT |
| | THE TIME OF APPLICATION, REVIEW AND PERMITTING. |
| | |
| | 3) NOTE: PLEASE PROVIDE LIGHTING CONTROLS PER FBC |
| | 13-415.1.ABC.1.1, .1.2, .1.3. |
| | THE RESPONSE LETTER MENTIONS THE STORE CONTAINS AN |
| | ENERGY MANAGEMENT SYSTEM HOWEVER THE PLANS STILL |
| | INDICATE ONLY STANDARD SINGLE POLE SWITCHES. THESE DO |
| | NOT MEET THE CODE SECTIONS FOR SEPARATE SPACES. |
| | PLEASE REVISE PLANS ACCORDINGLY. |
| | SEPARATE SPACES WITH FLOOR TO CEILING PARTITIONS MAY BE |
| | CONTROLLED FROM SYSTEM HOWEVER AUTOMATIC OVER RIDES |
| | WOULD BE REQUIRED OR MEET AUTOMATED CONTROLS FOR THESE |
| | AREAS SEPARATELY FROM THE SYSTEM. |
| | |
| | 4) NOTE: PLEASE SPECIFY WHICH METHOD OF CALCULATION IS |
| | BEING USED. PLEASE SEE TABLES B AND C. BUILDING AREA |
| | METHOD IN TABLE *C* DOES NOT CONTAIN THE SAME |
| | ALLOWANCES AS SPACE BY SPACE. |
| | 13-415.2,13-415.2.ABC.1.1,.1.2, 13-415.2.B, 13-415.2.C. |
| | |
| | 5) NOTE: PLEASE COMPLETE TITLE BLOCK FOR ELECTRICAL |
| | ENGINEERING FIRM AS LISTED ON COVER SHEET. PLEASE SEE |
| | FAC 61G15-23.002 FOR MISSING INFORMATION SUCH AS THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER. THIS IS ALSO |
| | REQUIRED PER FS 471.023. |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |