Plan Review Notes
Plan Review Notes For Permit 08110217
Permit Number 08110217
Review Stop E
Sequence Number 2
Notes
Date Text
2008-12-29 16:03:57** DENIED REVIEW **
  
 SOME NOTES FORM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING.
  
 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS REVIEW IN WHICH
 THERE WAS A NOTE ** IMPORTANT**. THIS WAS NOTED SO THAT
 ALL OLD/VOIDED SHEETS WERE TO BE REMOVED FROM SETS AND
 FOR ALL NEW REVISED SHEETS TO BE INSERTED INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. THIS WAS NOT DONE IN FACT
 THE NEW SHEET WERE JUST PLACED ON TOP OF THE OLD SETS.
 PLEASE BE SURE THIS ID DONE IN A NEAT AND ORDERLY
 FASHION WITH REVISED PLANS.
  
 2) NOTE: PERMIT APPLICATION HAS NOT BEEN MADE AT THIS
 TIME. PLEASE KNOW THE FLORIDA BUILDING CODE WILL BE
 CHANGING ON MATCH 1ST, 2009.
 ONLY ONCE PERMIT APPLICATION IS MADE BY LICENSED
 CONTRACTOR AND ALL CODE COMPLIANCE COMMENTS ARE
 ADDRESSED WILL THE REVIEW GO INTO A PASSED STATUS.
 THERE ARE MANY ASPECTS OF THE REVIEW WHICH ENTAIL
 REVIEW OF ALL LICENSING INCLUDING THAT OF DESIGNERS AT
 THE TIME OF APPLICATION, REVIEW AND PERMITTING.
  
 3) NOTE: PLEASE PROVIDE LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.1, .1.2, .1.3.
 THE RESPONSE LETTER MENTIONS THE STORE CONTAINS AN
 ENERGY MANAGEMENT SYSTEM HOWEVER THE PLANS STILL
 INDICATE ONLY STANDARD SINGLE POLE SWITCHES. THESE DO
 NOT MEET THE CODE SECTIONS FOR SEPARATE SPACES.
 PLEASE REVISE PLANS ACCORDINGLY.
 SEPARATE SPACES WITH FLOOR TO CEILING PARTITIONS MAY BE
 CONTROLLED FROM SYSTEM HOWEVER AUTOMATIC OVER RIDES
 WOULD BE REQUIRED OR MEET AUTOMATED CONTROLS FOR THESE
 AREAS SEPARATELY FROM THE SYSTEM.
  
 4) NOTE: PLEASE SPECIFY WHICH METHOD OF CALCULATION IS
 BEING USED. PLEASE SEE TABLES B AND C. BUILDING AREA
 METHOD IN TABLE *C* DOES NOT CONTAIN THE SAME
 ALLOWANCES AS SPACE BY SPACE.
 13-415.2,13-415.2.ABC.1.1,.1.2, 13-415.2.B, 13-415.2.C.
  
 5) NOTE: PLEASE COMPLETE TITLE BLOCK FOR ELECTRICAL
 ENGINEERING FIRM AS LISTED ON COVER SHEET. PLEASE SEE
 FAC 61G15-23.002 FOR MISSING INFORMATION SUCH AS THE
 CERTIFICATE OF AUTHORIZATION NUMBER. THIS IS ALSO
 REQUIRED PER FS 471.023.
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  