Text |
| 2008-11-25 10:20:58 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | *****PLAN REVIEW ONLY***** |
| | |
| | 1. SHT A0.1 CODE REFERENCE SHALL ALSO INDICATE 2007 |
| | AMENDMENTS/REVISIONS/SUPLIMENTS TO THE 2004 FBC. |
| | |
| | 2. PLEASE INDICATE THE LEVEL OF ALTERATION PER SECTION |
| | 301.5 OF THE EXISTING BUILDING CODE. |
| | |
| | 3. SHT A1.0 DEMO KEYED NOTES #3. PLEASE IDENTIFY THE |
| | FIXTURES. IF THERE ARE PLUMBING FIXTURES, THEN DEAD |
| | ENDS ARE PROHIBITED PER SECTION 704.5. SECTION 106.1.2 |
| | MORE INFORMATION REQUIRED. |
| | |
| | 4. SHT P1.1 THE SIGNATURE OF THE ENGINEER IS REQUIRED |
| | WHEN SEALING THE PLANS. IT APPEARS THAT INITIALS WERE |
| | USED IN PLACE OF THE SIGNATURE. IF INDEED THIS IS THE |
| | LEGAL SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED, |
| | NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE |
| | ENGINEER SHALL BE SUBMITTED TO THIS OFFICE FOR OUR |
| | FILE. FAC 61G15-23.002(1)(2) & FS 471.025. |
| | |
| | 5. SHT P1.1 ELECTRIC WATER HEATER DETAIL. THE RELIEF |
| | VALVE (T & P) SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| | FITTING LOCATED IN THE SAME ROOM AS THE WATER HEATER. |
| | SECTION 504.6.1. PLEASE SHOW ON THE DETAIL. |
| | |
| | 6. SHT P1.1 PLUMBING DRAWING NOTES #2.3 AIR CHAMBERS |
| | ARE NOT APPROVED. PLEASE DELETE FROM NOTES. SECTION |
| | 604.9 & PDI-WH 201. WATER HAMMER ARRESTORS ARE REQUIRED |
| | FOR QUICK CLOSING VALVES ONLY. (ICE MACHINES, DISH |
| | WASHERS & AUTOMATIC CLOTHES WASHERS). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |