2008-11-25 10:20:58DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 *****PLAN REVIEW ONLY*****
  
 1. SHT A0.1 CODE REFERENCE SHALL ALSO INDICATE 2007
 AMENDMENTS/REVISIONS/SUPLIMENTS TO THE 2004 FBC.
  
 2. PLEASE INDICATE THE LEVEL OF ALTERATION PER SECTION
 301.5 OF THE EXISTING BUILDING CODE.
  
 3. SHT A1.0 DEMO KEYED NOTES #3. PLEASE IDENTIFY THE
 FIXTURES. IF THERE ARE PLUMBING FIXTURES, THEN DEAD
 ENDS ARE PROHIBITED PER SECTION 704.5. SECTION 106.1.2
 MORE INFORMATION REQUIRED.
  
 4. SHT P1.1 THE SIGNATURE OF THE ENGINEER IS REQUIRED
 WHEN SEALING THE PLANS. IT APPEARS THAT INITIALS WERE
 USED IN PLACE OF THE SIGNATURE. IF INDEED THIS IS THE
 LEGAL SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED,
 NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE
 ENGINEER SHALL BE SUBMITTED TO THIS OFFICE FOR OUR
 FILE. FAC 61G15-23.002(1)(2) & FS 471.025.
  
 5. SHT P1.1 ELECTRIC WATER HEATER DETAIL. THE RELIEF
 VALVE (T & P) SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE WATER HEATER.
 SECTION 504.6.1. PLEASE SHOW ON THE DETAIL.
  
 6. SHT P1.1 PLUMBING DRAWING NOTES #2.3 AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE FROM NOTES. SECTION
 604.9 & PDI-WH 201. WATER HAMMER ARRESTORS ARE REQUIRED
 FOR QUICK CLOSING VALVES ONLY. (ICE MACHINES, DISH
 WASHERS & AUTOMATIC CLOTHES WASHERS).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  