2008-11-12 15:20:30PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. NOTE: CONTRACTOR IS APPYLING FOR A PERMIT TO INSTALL
 SOLAR POOL PANELS TO HEAT A POOL. PLEASE KNOW THAT THIS
 WORK IS NOT IN THE SCOPE OF A POOL CONTRACTOR PER FS
 489.105 DEFINITIONS, (3) CONTRACTOR (J) A COMMERCIAL
 POOL/SPA CONTRACTOR CAN ONLY INSTALL A PACKAGE POOL
 HEATER. A SOLAR POOL HEATER IS NOT A PACKAGE POOL
 HEATER. PLEASE KNOW THAT A CERTIFIED SOLAR CONTRACTOR
 OR A LICENSED PLUMBING CONTRACTOR IS REQUIRED PER FS
 489.105 (3) (M), AND (O). PLEASE REFERENCE THE ATTACHED
 FS 489.105 DEFINITIONS, (3) CONTRACTOR (J), (M), (O)
 AND FAC-61G4-15.021 TO THESE COMMENTS INDICATING THIS.
  
 END OF COMMENTS:
  