| 2008-12-05 16:58:22 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 2 ALTERATION AND ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) THE ADDRESS IN THE TITLE BLOCK FOR THE PROJECT OF |
| | 340 CROTON WAY IS INCORRECT. THE CORRECT ADDRESS IS 324 |
| | CROTON WAY. FAC 61G1-16.004 |
| | |
| | 3) THE PROPOSED WEST ELEVATION ON A-4 HAS A TYPO THAT |
| | APPEARS TO INDICATE WINDOWS BEING RELOCATED PLEASE |
| | CORRECT. FBC 106.1.1* CITY AMENDMENTS |
| | |
| | 4) ON SHEET A-2 THE EXISTING FIRST FLOOR PLAN SHOWS |
| | THREE WINDOWS IN THE KITCHEN AND THE EXISTING SOUTH |
| | ELEVATION ON A-3 SHOWS TWO WINDOWS AT THE SAME |
| | LOCATION. PLEASE CLARIFY. FBC 106.1.1* CITY AMENDMENTS |
| | |
| | 5) THE EXISTING SITE PLAN ON A-1 DOES NOT SHOW THE |
| | EXISTING TWO STORY DECK AT THE REAR. FBC 106.1.1* CITY |
| | AMENDMENTS |
| | |
| | 6) SHOW COMPLIANCE WITH SECTION R320 PROTECTION AGAINST |
| | TERMITES. R320.1 TERMITE PROTECTION SHALL BE PROVIDED |
| | BY REGISTERED TERMITICIDES, INCLUDING SOIL APPLIED |
| | PESTICIDES, BAITING SYSTEMS, AND PESTICIDES APPLIED TO |
| | WOOD, OR OTHER APPROVED METHODS OF TERMITE PROTECTION |
| | LABELED FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| | CONSTRUCTION (SEE SECTION 202, REGISTERED TERMITICIDE). |
| | UPON COMPLETION OF THE APPLICATION OF THE TERMITE |
| | PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL |
| | BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED |
| | PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING |
| | STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE |
| | TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. |
| | TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS |
| | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| | AND CONSUMER SERVICES.? |
| | |
| | 7) THE DESIGN LOADS DATA ON S-1 AND S-2 LISTS THE WRONG |
| | EDITION OF ASCE 7 AND THE MEAN ROOF HEIGHT IS |
| | INCORRECT. ASCE 7-02 AND MEAN ROOF HEIGHT FOR THE |
| | STRUCTURE IS THE DISTANCE FROM GRADE TO THE AVERAGE OF |
| | THE ROOF EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST |
| | POINT ON THE ROOF SURFACE. SEE FBC CHAPTER 43 AND R202. |
| | |
| | 8) SHOW COMPLIANCE WITH R803.2.3.1 SHEATHING |
| | FASTENINGS. |
| | WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO |
| | ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON |
| | CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE |
| | FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING |
| | MINIMUM DIMENSIONS: |
| | 1. 0.113-INCH NOMINAL SHANK DIAMETER |
| | 2. RING DIAMETER OF 0.012 OVER SHANK DIAMETER |
| | 3. 16 TO 20 RINGS PER INCH |
| | 4. 0.280 INCH FULL ROUND HEAD DIAMETER |
| | 5. 2-INCH NAIL LENGTH |
| | WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G < |
| | 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE |
| | 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR |
| | GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE |
| | R803.2.3.1. |
| | |
| | 9) THE TYP. FTG. DETAIL ON S-1 SPECIFIES A 6 X 6 WOOD |
| | COLUMN WITH ABA66 CONNECTOR. THE OTHER DETAILS SPECIFY |
| | 8 X 8 COLUMNS. PLEASE CLARIFY. FBC 106.1.1* CITY |
| | AMENDMENTS |
| | |
| | 10) PROVIDE A FRAMING DETAIL FOR THE LOWER ROOF THAT |
| | WRAPS AROUND THE SECOND FLOOR DECK. SPECIFY ALL |
| | CONNECTORS. R301.1 |
| | |
| | 11) PROVIDE A GABLE END DETAIL FOR A WOOD BEAM BELOW |
| | SPECIFIC TO THIS PROJECT. SPECIFY THE CONNECTORS. |
| | R301.1 |
| | |
| | 12) SPECIFY HOW THE SECOND FLOOR LEDGERS WILL BE |
| | ATTACHED TO THE EXISTING STRUCTURE. R301.1 |
| | |
| | 13) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE 2- 2 X 12 BEAMS SUPPORTING THE UPPER ROOF TO THE |
| | EXISTING STRUCTURE. R301.1 |
| | |
| | 14) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE 2- 2 X 12 BEAMS SUPPORTING THE UPPER ROOF TO THE |
| | WOOD COLUMNS. THE WALL SECTION ON S-2 HAS A QUESTION |
| | MARK. R301.1 |
| | |
| | 15) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | FOLLOWING ITEMS: EXTERIOR DOUBLE OUTSWING DOORS, SINGLE |
| | INSWING DOOR, WINDOWS, ASPHALT ROOF SHINGLES AND HOT |
| | MOP SYSTEM ON SECOND FLOOR DECK. FAC RULE 9B-72 |
| | |
| | 16) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |