Plan Review Notes
Plan Review Notes For Permit 08110182
Permit Number 08110182
Review Stop B
Sequence Number 1
Notes
Date Text
2008-12-05 16:58:222004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION AND ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) THE ADDRESS IN THE TITLE BLOCK FOR THE PROJECT OF
 340 CROTON WAY IS INCORRECT. THE CORRECT ADDRESS IS 324
 CROTON WAY. FAC 61G1-16.004
  
 3) THE PROPOSED WEST ELEVATION ON A-4 HAS A TYPO THAT
 APPEARS TO INDICATE WINDOWS BEING RELOCATED PLEASE
 CORRECT. FBC 106.1.1* CITY AMENDMENTS
  
 4) ON SHEET A-2 THE EXISTING FIRST FLOOR PLAN SHOWS
 THREE WINDOWS IN THE KITCHEN AND THE EXISTING SOUTH
 ELEVATION ON A-3 SHOWS TWO WINDOWS AT THE SAME
 LOCATION. PLEASE CLARIFY. FBC 106.1.1* CITY AMENDMENTS
  
 5) THE EXISTING SITE PLAN ON A-1 DOES NOT SHOW THE
 EXISTING TWO STORY DECK AT THE REAR. FBC 106.1.1* CITY
 AMENDMENTS
  
 6) SHOW COMPLIANCE WITH SECTION R320 PROTECTION AGAINST
 TERMITES. R320.1 TERMITE PROTECTION SHALL BE PROVIDED
 BY REGISTERED TERMITICIDES, INCLUDING SOIL APPLIED
 PESTICIDES, BAITING SYSTEMS, AND PESTICIDES APPLIED TO
 WOOD, OR OTHER APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION (SEE SECTION 202, REGISTERED TERMITICIDE).
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.?
  
 7) THE DESIGN LOADS DATA ON S-1 AND S-2 LISTS THE WRONG
 EDITION OF ASCE 7 AND THE MEAN ROOF HEIGHT IS
 INCORRECT. ASCE 7-02 AND MEAN ROOF HEIGHT FOR THE
 STRUCTURE IS THE DISTANCE FROM GRADE TO THE AVERAGE OF
 THE ROOF EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST
 POINT ON THE ROOF SURFACE. SEE FBC CHAPTER 43 AND R202.
  
 8) SHOW COMPLIANCE WITH R803.2.3.1 SHEATHING
 FASTENINGS.
 WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO
 ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING
 MINIMUM DIMENSIONS:
 1. 0.113-INCH NOMINAL SHANK DIAMETER
 2. RING DIAMETER OF 0.012 OVER SHANK DIAMETER
 3. 16 TO 20 RINGS PER INCH
 4. 0.280 INCH FULL ROUND HEAD DIAMETER
 5. 2-INCH NAIL LENGTH
 WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G <
 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE
 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR
 GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE
 R803.2.3.1.
  
 9) THE TYP. FTG. DETAIL ON S-1 SPECIFIES A 6 X 6 WOOD
 COLUMN WITH ABA66 CONNECTOR. THE OTHER DETAILS SPECIFY
 8 X 8 COLUMNS. PLEASE CLARIFY. FBC 106.1.1* CITY
 AMENDMENTS
  
 10) PROVIDE A FRAMING DETAIL FOR THE LOWER ROOF THAT
 WRAPS AROUND THE SECOND FLOOR DECK. SPECIFY ALL
 CONNECTORS. R301.1
  
 11) PROVIDE A GABLE END DETAIL FOR A WOOD BEAM BELOW
 SPECIFIC TO THIS PROJECT. SPECIFY THE CONNECTORS.
 R301.1
  
 12) SPECIFY HOW THE SECOND FLOOR LEDGERS WILL BE
 ATTACHED TO THE EXISTING STRUCTURE. R301.1
  
 13) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE 2- 2 X 12 BEAMS SUPPORTING THE UPPER ROOF TO THE
 EXISTING STRUCTURE. R301.1
  
 14) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE 2- 2 X 12 BEAMS SUPPORTING THE UPPER ROOF TO THE
 WOOD COLUMNS. THE WALL SECTION ON S-2 HAS A QUESTION
 MARK. R301.1
  
 15) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 FOLLOWING ITEMS: EXTERIOR DOUBLE OUTSWING DOORS, SINGLE
 INSWING DOOR, WINDOWS, ASPHALT ROOF SHINGLES AND HOT
 MOP SYSTEM ON SECOND FLOOR DECK. FAC RULE 9B-72
  
 16) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]