Plan Review Notes
Plan Review Notes For Permit 08110178
Permit Number 08110178
Review Stop E
Sequence Number 3
Notes
Date Text
2009-05-14 12:24:48**PROVISO/ REDLINED NOTES **
  
 * TEMPORARY FAILED*
  
  
 ** THE FOLLOWING ITEMS SHALL BE ADDRESSED AND REVISED
 BEFORE ANY ROUGH ELECTRICAL INSPECTION. SEE NOTE #4
 WHICH NEEDS TO BE DONE AT THIS TIME. NOTE NUMBER FOUR
 WAS GIVEN ON INITIAL REVIEW HOWEVER HAS NOT BEEN
 ADDRESSED IN SECOND SET.
  
 1) NOTE: PLEASE SEE FBC 13-415.AB.1, .1.3 NOTED IN ALL
 PREVIOUS REVIEWS. THERE ARE LIGHTING FIXTURES WHICH DO
 NOT MEET SECTIONS GIVEN. ALL ACCENT/TASK LIGHTING SHALL
 CONTAIN SOME SORT OF CONTROL WHICH WILL TURN OFF
 FIXTURES IN SOME SORT OF AUTOMATED WAY. THESE MAY BE
 PART OF THE LIGHTING TIME CLOCK WITH OVER RIDES OR
 OCCUPANCY SENSOR TYPE DEVICES.
 THESE ARE LOCATED IN SEPARATION ROOM, PREP SINK, AND
 MED PREP AREAS.
 THE BASE SYSTEM AS SHOWN NEEDS TO BE MORE SPECIFIC ON
 PLANS WITH ACTUAL SYSTEM CHOSEN AND INSTALLED. THE TYPE
 OF SYSTEM WHICH MUST BE LISTED PER A NATIONAL
 RECOGNIZED TESTING LABORATORY SHALL BE SHOWN. ( NRTL)
 NEC 110.3, FBC 13-415.AB.1.1, .1.2 AND .1.3. SEE NEXT
 NOTE:
  
 2) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE PLANS DO
 CONTAIN A DEVICE WHICH IS NOTED AS BEING A *TWIST
 TIMER* DEVICE. DEVICE WHICH MAY BE ACCESSIBLE AND IN
 USE FOR ANYONE MEETING ADA GUIDELINES SHALL NOT BE OF
 TWISTING TYPE.
  
 3) NOTE: ** ALL LOW VOLTAGE SYSTEMS SHALL BE UNDER
 SEPARATE PERMITS. ANY ACCESS CONTROLS WOULD ALSO BE
 UNDER SEPARATE PERMIT WITH PLANS AND REVIEW BY THE FIRE
 MARSHAL AS WELL AS ELECTRICAL REVIEWS IN ACCORDANCE
 WITH NFPA-70 2005 AND NFPA-101 2006 CHAPTER 7.
  
 4) NOTE: THE SECOND SET OF PLANS CONTAINS ALMOST ALL OF
 THE ORIGINAL SHEETS SUBMITTED FROM SHEETS 230, 250, AND
 270 NEEDS TO BE RE-SEALED WITH CURRENT SEALS ACCEPTABLE
 IN THE STATE OF FLORIDA. THE OTHER NEW REVISED SHEETS
 IN SETS ARE OK AS THEY CONTAIN NEW SEAL. FAC61G1-16.002
 THIS WAS NOTED ON COMMENT #3 ON INITIAL REVIEW YET MANY
 OF THE OLDER SHEETS STILL CONTAIN OLD SEAL. THIS IS
 REQUIRED FOR ALL SHEETS WHETHER OR NOT COMMENT IS MADE
 BY ANY OTHER TRADE. THE ARCHITECT OF RECORD MAY COME
 INTO OFFICE, PRESENT IDENTIFICATION AND RE-SEAL PLANS
 WITH NEW SEAL IN ORDER TO GET PROJECT ISSUED FOR
 PERMIT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  